Cyclogic CL-MC03** Series User manual

Modbus Interface Module
INSTRUCTION MANUAL
Model :
Document Rev . 1
CL-MC03** Series
+ - + - + - + -

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
FOR INSTALLER
FOR INSTALLER
Contents
Before using the device, carefully read this installaon/instrucon manual to ensure proper operaon.
Keep this manual for future reference and give it to the technician when the device is reinstalled or
repaired.
1. Supplied Parts
2. Safety Precauons
3. Product General
4. System Configuraon before installing Modbus Interface Module
5. How to Install
6. Modbus Protocol
1. Confirming the supplied parts
Check that the box includes the following part(s) in addion to this installaon manual:
CL-MC03** Series Modbus Interface Module
2. Safety Precauons
· Thoroughly read the following safety precauons before use.
· Hazards that can occur from incorrect handling are classified by the symbols below:
Warning
Cauon
Noce
Indicate a potenally hazardous situaon which, if not avoided, could result in death or
serious injury.
Indicate a potenally hazardous situaon which, if not avoided, could result in minoror
moderate injury. It could also be usedto alert against unsafe pracces.
Indicates a situaon that could result in equipment orproperty-damage only accidents.
· Aer reading this manual, keep this manual for future reference. When the device is reinstalled or
repaired, give this manual to those who provide these services. When the user changes, make sure
that the new user receives this manual.
Warning
· Only a dealer or qualified technician should install, relocate, reinstall, or repair the device.
Improper installaon or repair may result in electrical shock or fire.
· Properly install the device on a stable, load-bearing surface.
Device installed on an unstable surface may fall and cause injury.

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
· Only use the specified cables; securely connect each so that the terminals do not bear any cable weight.
Improperly connected or short-circuited cables may produce heat and cause a fire.
· All electrical work should be performed by an authorized electrician according to local regulaons and
instrucons outlined in this manual.
Capacity shortage to the power supply circuit or improper installaon may result in electrical shock or fire.
· Do not make any modificaons or alternaons to the device.
Modificaons or improper repair may result in electric shock or fire. Consult your dealer for repair.
· Properly install the device according to the instrucons in this Installaon/Instrucon Manual.
Improper installaon may result in electric shock or fire.
Cauon
· Do not install the device in a locaon where a flammable gas leak may occur.
Gas may leak, collect around the device, ignite, and/or explode.
· Do not install the device in environments where large amounts of oil (including machine),
sulfidizing gas, or acidic, alkaline, chemical sprays are present.
These types of substances may damage internal parts, cause device performance to be reduced, and
cause electrical shock.
· Do not install the device in a bathroom, kitchen, or any room where steam could form.
Condensaon may develop and cause electrical shock and/or the device to malfuncon.
· Do not install the device in a locaon where there is direct sunlight or where the temperature may
become greater than 40°C (104°F) or less than 0°C (32°F).
If the device is installed in such place, it may result in deformaon or malfuncons.
· When installing the device in a hospital, communicaon facility, etc., provide sufficient protecon
against frequency noise.
Power generators and inverters, high-frequency medical, or radio communicaon equipment may
interfere with the normal operaon of this device. Subsequently, the device may also affect medical
treatment, image broadcasng, etc., by creang frequency noise.
· Include some slack in the power supply wires.
Tension on the wires may cause them to excessively heat up and/or break, resulng in a fire.
· Use standard wires with the proper current capacity
to avoid the possibility of current leak, excessive heat, and/or fire.
· Do not touch the main circuit board; also, make sure that dust does not accumulate on the circuit
board.
· Do not immerse the device in water.
Doing so may lead to electric shock or malfuncons.

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
This soluon enables full integraon of SAMSUNG DVM, CAC, FJM & RAC equipment into BMS systems
using Modbus RTU protocol.
Parameters that can be controlled include ON/OFF, Mode, Set Point, Fan Speed and louvre control where
applicable. Data can be read back to the BMS system including room temperature and fault status.
Descripon
3.1. General Specificaons
3. Product General
+ - + - + - + -
Items Descripon
Size 100mm x80mm x24mm
(3.94 x3.15 x0.94 inch)
Power SupplyDC12 ~24V
NetworkF1/F2 ControlBoard Network
AC Units Up to 64 Indoorunits controlledas a group
CompabilitySAMSUNG DVM, CAC, FJM &RAC
( W x H x D )
Model name CL-MC0301C CL-MC0308C CL-MC0316C CL-MC0332C CL-MC0364C
# of indoor unit
to control &
monitor
1 8 16 32 64
4. System Configuraon before installing Modbus Interface Module
4.1. Dip Switch Sengs
DIP SW2 : Adjust the inial seng according to the SAMSUNG AC type.
[ IMPORTANT ] If you set this SW wrong, unl will not work or respond.
■ Protocol seng to control or monitor SAMSUNG AC
DIPSW2Access
ON RAC/FJM :Model numberAR*****, AJ*****
OFF DVM/CAC:Model numberAM*****, AC****
DIP SW1 : In case of updang firmware, set this DIP switch.
■ Firmware update
DIPSW1Access
ON Disable (Default)
OFF Enable (use when you download the firmware only)

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
NOTICE : Modbus Interface Module needs 12~24V DC power to operate.
5. How to install
5.1. Wire Connecons
1. Choose a place where to install the CL-MC03** series. The device provides two mounng holes that
can be used to mechanically affix the case to a solid surface. Double-sided tape may be used to affix
the device. When using tape, ensure that the tape is approved for use within the ancipated
operang temperature ranges.
2. Connect the CL-MC03** cable to the terminals F1/F2 on the indoor unit control board for
communicaon between SASMUNG indoor unit and Cyclogic Modbus Interface Module.
3. Connect the CL-MC03** cable to the terminals V1/V2 on the indoor unit control board for supplying
power.
4. Connect the CL-MC03** cable to the 3rd party controller.
4.2. Modbus Slave Address Seng with Rotary Switch
RSW1
(Ten)
RSW2
(One)
RSW1 : 10 digit
RSW2 : one digit
Inial sengs(Modbus Address) can be configured via 2 rotary switches on the circuit board. The circuit
board can be accessed by unfastening the four screws on the back of the case.
Device Configuraon
RX+ RX-
Modbus RTU F1 F2
Communicaon
+-
12~24V DC
+ - + - + - + -
+ - + - + - + -
Dry
Contact
No Connector Descripon
1MODBUS INT Connecon for3rd partycontroller
2RS-485 Connecon forSAMSUNG AC’s F1/F2
communicaon
3 MODBUS EXT N/A
4 POWER Connecon forpowersupply of DC12 ~ 24V
5 DO Contact when erroroccurs (DC 12 ~ 24)
6DRY CONT Connecon forforced ON/OFF

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
5.2. Connecon Diagram
+ - + - + - + -
F1/F2
[Outdoor Unit][MODBUS INT]
Case 1 (DVM, CAC)
Case 2 (RAC)
+ - + - + - + -
[MODBUS INT]
[Outdoor Unit]
F1/F2
Master Modbus
Controller
Master Modbus
Controller
+ - + - + - + -
F1/F2
[Outdoor Unit][MODBUS INT]
RSW1
(Ten)
RSW2
(One)
RSW1
(Ten)
RSW2
(One)
* DIP SW2 : OFF
* DIP SW2 : ON * DIP SW2 : ON

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
6.1 MODBUS CONFIGURATION
6. Modbus Protocol
Mode
Length
Addresses
Baud
Parity
Stop bits
6.2 MODBUS REGISTER
The CL-MC03** supports two types of register, Read Holding Registers and Preset Single Register.
Modbus RTU Slave
500m
0 to 63 (indoor units)
19600
Even
1
Register Type Access Funcon
Preset Single Register Write Controls andCommandRegisters
HoldingRegister ReadReadbackandMonitoringRegisters
All analogue and digital values are accessed through these registers. All register values are 2 byte(16bit)
values.
Funcon Code
(hex code)Funcon Name
03 (03h) ReadHoldingRegisters
06(06h) Preset Single Registers
Registers are accessed using standard Modbus funcons. The following two funcons are supported
by the CL-MC03**.

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
6.3 Readback Data
Unit data is available for each of the indoor units on the F1,F2 network. Unit Input registers are
numbered using the indoor unit numbering in the range 40001~40014 + N(indoor unit address) x 20
added to an offset relang to a specific feature.
IndoorUnit Addresses Length
(Byte)Name Value Notes Read/
Write
IDU00 IDU01 …. IDU63
40001 40021 …. 41261 2IDUON/OFF STATUS0 OFF R
1ON R
40002 40022 …. 41262
2
IDUOPERATION MODE 0AUTOR
1COOLING R
2 DRY (DEHUMIDIFICATION) R
3FANR
4 HEAT R
11 AUTOCOOL R
12 AUTODRY R
13 AUTOFANR
14 AUTOHEAT R
40005 40025 …. 41265 2SET TEMPERATURE SET TEMP = Data/10R
40006 40026 …. 41266 2ROOM TEMPERATURE ROOM TEMP = Data/10R
40009 40029…. 41269
2
IDUFANSPEED CONTROL 0AUTOMATIC R
1LOW R
2MIDDLE R
3 HIGH R
4 TURBO R
4001040030…. 41270
2
IDUDECO PANELLOUVER
SWING
0SWING OFF R
1 SWING ON :UPPER &LOWER LOUVER R
2 SWING ON :RIGHT &LEFT LOUVER R
3SWING ON :UPPER&LOWER/RIGHT&LEFT
LOUVER R
40011 40031 …. 41271
2
Supply Air(Discharge)
Temperature
(Duct unit only)
SET TEMP = Data/10R
40012 40032 …. 41272
2
States of Supply
Air(Discharge)
Temperature Control
0DISABLE R
1 ENABLE R
40013 40033 …. 41273 2Set Temp. of Cooling
Supply Air (Duct unit only) SET TEMP = Data/10R
40014 40034 …. 41274 2Set Temp. of Heang
Supply Air (Duct unit only) SET TEMP = Data/10R
The CL-MC03** supports two types of register, Read Holding Registers and Preset Single Register.

URL hp://www.cyclogic.net
Email
Tel +82 317099303
CL-MC03** Series Modbus Interface Module Installaon Instrucons, Oct. 2016
@2016 Cyclogic Inc.
Document Rev . 1
Modbus Interface Module
6.4 Control Data
Unit data is available for each of the indoor units on the F1,F2 network. Unit Input registers are
numbered using the indoor unit numbering in the range 40001~40014 + N(indoor unit address) x 20
added to an offset relang to a specific feature.
IDU00 IDU01 …. IDU63
Length
(Byte) Name Value Notes Read/
Write
40001 40021 …. 41261
2
IDUON/OFF &MODE Data 1 W
0 OFF W
1ON W
2
Data 2
0AUTOW
1COOLING W
DRY (DEHUMIDIFICATION) W
3FANW
4 HEAT W
11 AUTOCOOL W
12 AUTODRY W
13 AUTOFANW
14 AUTOHEAT W
SET TEMP = Data/10 W
40009 40029…. 41269
2
IDUFANSPEED CONTROL
0AUTOMATIC W
1LOW W
2MIDDLEW
3 HIGHW
4 TURBO W
2
IDUDECO PANELLOUVER
SWING 0SWING OFF W
1SWING ON :UPPER &LOWER
LOUVER W
2SWING ON :RIGHT &LEFT
LOUVER W
3SWING ON :UPPER&LOWER
/RIGHT&LEFT LOUVER W
40011 40031 …. 41271 2Supply Air(Discharge)
Temperature (Duct unit only) SET TEMP = Data/10 W
40012 40032 …. 41272
2
States of Supply
Air(Discharge)Temperature
Control
0DISABLEW
1ENABLEW
40013 40033 …. 41273 2Set Temp. of CoolingSupply
Air (Duct unit only) SET TEMP = Data/10 W
40014 40034 …. 41274 2Set Temp. of HeangSupply
Air (Duct unit only) SET TEMP = Data/10 W
2
Data2
Data 1
40005 40025 …. 41265 2SET TEMPERATURE
IndoorUnit Addresses
W
Table of contents
Popular Control Unit manuals by other brands

caenrfid
caenrfid Lepton3x1 Technical information manual

SPX FLOW
SPX FLOW APV DELTA VRA instruction manual

q-Tech
q-Tech sms lite quick start guide

Oriental motor
Oriental motor ASTEP AR Series quick start guide

Tripp Lite
Tripp Lite SRCOOLNETLX Installation and quick start guide

SIGMA TEK
SIGMA TEK SAI 041 operating manual

Resolution
Resolution RE124DG DSC-to-GE Wireless Translator quick guide

GiBiDi
GiBiDi BA24 Instructions for installation

DF ROBOT
DF ROBOT DFPLayer Mini manual

SIGMA TEK
SIGMA TEK AI 022-1 operating manual

Delta
Delta T17TH Series Installation

Control Technologies
Control Technologies CTI 2557-A Installation and operation guide