DAB PUMPS ACTIVE DRIVER M/M 1.1 Operating and maintenance manual

INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE
ACTIVE DRIVER M/M 1.1
ACTIVE DRIVER M/T 1.0
ACTIVE DRIVER M/T 2.2
ACTIVE DRIVER T/T 3.0
ACTIVE DRIVER T/T 5.5

ACTIVE DRIVER M/M 1.1
ACTIVE DRIVER M/T 1.0 - ACTIVE DRIVER M/T 2.2
ACTIVE DRIVER T/T 3.0 - ACTIVE DRIVER T/T 5.5
DICHIARAZIONE DI CONFORMITÀ
La Ditta DAB PUMPS s.p.a. - Via M. Polo,14 - Mestrino (PD) - ITALIA - sotto la propria
esclusiva responsabilità dichiara che i prodotti summenzionati sono conformi a:
− Direttiva della Compatibilità elettromagnetica 89/336 e successive modifiche.
− Direttiva Bassa Tensione 73/23 e successive modifiche.
DÉCLARATION DE CONFORMITÉ
La société DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – sous sa propre
responsabilité exclusive déclare que les produits susmentionnés sont conformes à:
− Directive de la Compatibilité électromagnétique 89/336 et modifications successives.
− Directive Basse Tension 73/23 et modifications successives.
DECLARATION OF CONFORMITY
The Company DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – under is own
exclusive responsibility declares that the products listed above comply with:
− Directive on Electroma.gnetic Compatibility 89/336 and subsequent modifications.
− Directive on Low Voltage 73/23 and subsequent modifications.
KONFORMITÄTSERKLÄRUNG
Die Firma DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIEN – erklärt
eigenverantwortlich, dass die vorstehend beschriebenen Produkte den folgenden Richtlinien
entsprechen:
− Richtlinie zur elektromagnetischen Verträglichkeit 89/336 und folgende Änderungen.
− Niederspannungsrichtlinie 73/23 und folgende Änderungen.
CONFORMITEITSVERKLARING
De firma DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – verklaart onder
haar eigen, exclusieve verantwoording dat de hieronder genoemde producten voldoen aan:
− Richtlijn elektromagnetische compatibiliteit 89/336 en successievelijke wijzigingen.
− Laagspanningsrichtlijn 73/23 en successievelijke wijzigingen.
DECLARACIÓN DE CONFORMIDAD
La empresa DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIA – declara bajo su
total responsabilidad que los productos anteriormente mencionados cumplen la:
− Directiva de Compatibilidad Electromagnética 89/336 y sucesivas modificaciones.
− Directiva de Baja Tensión 73/23 y sucesivas modificaciones.
FÖRSÄKRAN OM CE-ÖVERENSSTÄMMELSE
Företaget DAB PUMPS s.p.a. – Via M. Polo 14, Mestrino (PD) – ITALIEN – förklarar på eget
ansvar att ovannämnda produkter är i överensstämmelse med:
− EMC-direktivet 89/336/EEG jämte ändringar.
− Lågspänningsdirektivet 73/23/EEG jämte ändringar.

ACTIVE DRIVER M/M 1.1
ACTIVE DRIVER M/T 1.0 - ACTIVE DRIVER M/T 2.2
ACTIVE DRIVER T/T 3.0 - ACTIVE DRIVER T/T 5.5
∆ΗΛΩΣΗ ΣΥMMOPΦΩΣΗΣ
Ηεταιρεία DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALY – δηλώνει
νπεύθυνα πως τα πρϊόντα που αναφέρονται παραπάνω, εναρµονίζονται µε:
− Тην οδηγία περί µαγνητικής συµβατότητας 89/336/EOK και µετέπειτα τροποποιήσεις.
− Την οδηγία περί χαµηλής τάσης 73/23/EOK και µετέπειτα τροποποιήσεις.
UYGUNLUK BEYANNAMESİ
- Via M. Polo, 14 – Mestrino (PD) – ITALY – adresinde yerleşik DAB PUMPS s.p.a. Şirketi,
sadece kendi sorumluluğu altnıda sözü geçen ürünlerin aşağidaki yönetmeliklere uygun oldğunu
beyan etmektedir:
− 89/336 sayılıelektromanyetik Uygunluk Yönergesi ve daha sonraki değişiklikler.
− 73/23 sayılıAlçak Gerilim Yönergesi ve daha sonraki değişiklikler.
VYHLÁSENIE O ZHODE
SpoločnosťDAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – Taliansko, vyhlasuje na
vlastnú výhradnú zodpovednosť, že výrobky uvedené v d’alšom texte zodpovedajú.
− Smernici Elektromagnetická kompatibilita č. 89/336 a nasledujúcim úpravám.
− Smernici Nízke napätie č. 73/23 a nasledujúcim úpravám.
ЗАЯВЛЕНИЕ ОCOOTBETCTBИИ
Фирма DAB PUMPS s.p.a. – Вия M. Поло, 14 – Местрино (ПД) – ИТАЛИЯ – под
собственную исключительную ответственность заявлет, что вышеуказанные изделия
соответствуют:
− Директиве по Электромагнитной совместимости 89/336 ипоследующим изменениям.
− Директиве по Низкому напряжению 73/23 ипоследующим изменения.
DECLARAŢIE DE CONFORMITATE
Întreprinderea DAB PUMPS s.p.a. – Via M. Polo, 14 – Mestrino (PD) – ITALIA – pe exclusiva
proprie răspundere declarăcăprodusele mai sus menţionate sunt conforme cu:
− Directiva Compatibilităţii electromagnetice 89/336 şi următoarele modificări.
− Directiva de JoasăTensiune 73/23 şi următoarele modificări.
ﺔﻘﺑﺎﻄﻣ ةدﺎﻬﺷ
ﻰﻟإ ﺔﻘﺑﺎﻄﻣ ﻩﻼﻋأ ةرﻮآﺬﻤﻟا تﺎﺠﺘﻨﻤﻟا نﺄﺑ حّﺮﺼﺗ ﺔﺻﺎﺨﻟا ﺎﻬﺘﻴﻟوﺆﺴﻣ:
-ﻢﻗر ﺔﻴﺋﺎﺑﺮﻬﻜﻟا ﺔﻴﺴﻴﻄﻨﻐﻤﻟا ﺔﻘﺑﺎﻄﻤﻟا نﻮﻧﺎﻗ89/336ﻪﺑ ﺔﻘﺣﻼﻟا تﻼﻳﺪﻌﺘﻟاو.
-ﻢﻗر ﺾﻔﺨﻨﻤﻟا ﺪﻬﺠﻟا نﻮﻧﺎﻗ73/23ﻪﺑ ﺔﻘﺣﻼﻟا تﻼﻳﺪﻌﺘﻟاو.
Mestrino (PD), 31/03/2004
Attilio Conca
Legale Rappresentante
Legal Representative

ENGLISH
25
INDEX page
1. GENERAL 25
2. WARNINGS 25
3. APPLICATIONS 26
4. TECHNICAL DATA AND LIMITATIONS OF USE 26
5.
ELECTRICAL CONNECTIONS OF THE ACTIVE DRIVER TO THE ELECTROPUMP
26
6. CONNECTION TO THE POWER SUPPLY LINE 26
7. HYDRAULIC CONNECTIONS 27
8. CHARACTERISTICS – INTERPRETATIONS – OPERATION 27
8.1 Characteristics and interpretations 27
8.2 Operation: keyboard setting 28
8.3 Operation: parameters for the user 29
8.4 Operation: parameters for the installer 29
8.5 Operation: technical assistance displays and settings 31
9. DISPLAYS 33
9.1 Displays of the main values 33
9.2 Monitor displays 33
10. ACCESS TO MANUAL MODE OF THE MACHINE 33
11. GENERAL SYSTEM RESET 34
12. RESTORING THE FACTORY SETTINGS 34
13. ERROR AND STATUS CONDITIONS 34
14. TABLE OF INDICATIONS ON THE DISPLAY 36
1. GENERAL
Read this documentation carefully before installation. Installation and functioning must comply
with the safety regulations in force in the country in which the product is installed. The entire
operation must be carried out in a workmanlike manner.
Failure to comply with the safety regulations not only causes risk to personal safety and damage to
the equipment, but invalidates every right to assistance under guarantee.
2. WARNINGS
2.1 Skilled personnel
It is advisable that installation be carried out by competent, skilled personnel in
possession of the technical qualifications required by the specific legislation in force.
The term skilled personnel means persons whose training, experience and instruction, as well as
their knowledge of the respective standards and requirements for accident prevention and working
conditions, have been approved by the person in charge of plant safety, authorizing them to perform
all the necessary activities, during which they are able to recognize and avoid all dangers.
(Definition for technical personnel IEC 364).
2.2 Safety
Use is allowed only if the electric system is in possession of safety precautions in accordance with the
regulations in force in the country where the product is installed (for Italy, IEC 64/2).
2.3 Responsibility
The Manufacturer does not vouch for correct operation of the ACTIVE DRIVER or for any damage
that it may cause if it has been tampered with, modified and/or run outside the recommended work
range or in contrast with other indications given in this manual. The Manufacturer declines all
responsibilit
y
for possible errors in this instructions manual, if due to misprints or errors in cop
y
in
g
.
The Manufacturer reserves the right to make any modifications to products that it may consider
necessary or useful, without affecting the essential characteristics.
2.4 PARTICULAR WARNINGS
Before working on the electrical or mechanical part of the system, always turn off the mains voltage.
Wait at least five minutes after the power supply to the machine has been switched off before opening
the appliance. The condenser of the continuous intermediate circuit remains charged with dangerously high
voltage even after the mains voltage has been switched off.
Only firmly wired mains connections are admissible. The appliance must be earthed (IEC 536 class 1, NEC
and other relevant standards).
Mains terminals may carry dangerous voltage even when the motor is stopped.
In determined calibration conditions, after a power cut the converter may start automatically.
Pay attention: the motor terminals U, V and W (for the Active Driver M/M 1.1 the motor terminals R
and S). may carry dangerous voltages even when the converter is not operating.
Do not operate the appliance in direct sunlight.
This appliance may not be used as an “EMERGENCY STOP mechanism” (see EN 60204, 9.2.5.4).

ENGLISH
26
3. APPLICATIONS
The Active Driver M/T is fed with a single-phase line and it drives electropumps with a standard three-phase 230V
asynchronous motor.
The Active Driver M/M is fed with a single-phase line and it drives electropumps with a standard single-phase 230V
asynchronous motor.
The Active Driver T/T is fed with a line three-phase and it drives electropumps with a standard three-phase 400V
asynchronous motor.
4. TECHNICAL DATA AND LIMITATIONS OF USE
A.D. M/M 1.1 A.D. M/T 1.0 A.D. M/T 2.2 A.D. T/T 3.0 A.D T/T 5.5
− Max phase current of the motor: 8,5 A 4,7 A 9,3 A 7,5 A 13,3 A
− Line voltage: 230 V
single-phase 230 V
single-phase 230 V
single-phase 400 V
three-phase 400 V
three-phase
− Line frequency: 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz
− Electropump voltage: 230 V
single-phase 230V
three-phase 230 V
three-phase 400 V
three-phase 400 V
three-phase
− Weight of the unit
(packing excluded): 4 Kg. 3,8 Kg. 3,8 Kg. 5 Kg. 5Kg.
− Work position: Any position Any position Any position Facing upward
Facing upward
− Max fluid temperature: 50°C 50°C 50°C 50°C 50°C
− Max working temperature: 60°C 60°C 60°C 60°C 60°C
− Max. pressure: 10 bar 10 bar 10 bar 10 bar 10 bar
− Regulating range:
from 1 to 6 bar from 1 to 9 bar from 1 to 9 bar from 1 to 9 bar from 1 to 9 bar
− Maximum dimensions (LxHxD): 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm 22x28x18 cm
− Fluid input hydraulic coupling: 1 ¼” male 1 ¼” male 1 ¼” male 1 ¼” male 1 ¼” male
− Fluid output hydraulic coupling: 1 ½”female 1 ½”female 1 ½”female 1 ½”female 1 ½”female
− Degree of protection: IP 55 IP 55 IP 55 IP 55 IP 55
− Protections: - dry running
- overload
- excess temperature of the electronics
- abnormal feeding voltages (excluding A.D. M/M and A.D. M/T 1.0)
- direct short-circuit between the output phases
5. ELECTRICAL CONNECTIONS OF THE ACTIVE DRIVER TO THE ELECTROPUMP
5.1
Ensure that all the terminals are fully tightened, paying particular attention to the earth
terminal .
5.2 Check that all the connecting cables are in excellent conditions, with the external sheathing
unbroken.
5.3 The motor of the installed electropump must comply with the data in the table in Chapter 4.
The user connected to the ACTIVE DRIVER M/M 1.1 must not exceed 8,5 A as phase current.
The user connected to the ACTIVE DRIVER M/T 1.0 must not exceed 4,7 A as phase current.
The user connected to the ACTIVE DRIVER M/T 2.2 must not exceed 9,3 A as phase current.
The user connected to the ACTIVE DRIVER T/T 3.0 must not exceed 7,5 A as phase current.
The user connected to the ACTIVE DRIVER T/T 5.5 must not exceed 13,3 A as phase current.
5.4 Connect the electropump to the output cable of the ACTIVE DRIVER, paying particular attention to
the earth connection.
The incorrect connection of the earth lines to a terminal other than the earth terminal
may cause irremediable damage to the whole appliance!
The incorrect connection of the power supply line on output terminals intended for the
load may cause irremediable damage to the whole appliance!
6. CONNECTION TO THE POWER SUPPLY LINE
6.1 Connect the ACTIVE DRIVER to the power supply line by means of the power socket.
(See values in chapter 4).
6.2 If an extension to the power cable is used the following minimum sections must be respected:
Section of each lead (mm²) Maximum length of the line (metres)
1.5 15
2.5 30
4 60

ENGLISH
27
6.3 The ACTIVE DRIVER is already provided with current protections. If a magnetothermal switch is
installed in line, it must have a max. capacity of 16A.
6.4 The connection of the line to the ACTIVE DRIVER must include the earth line. The total earth
resistance must not exceed 100 Ohm.
6.5 To protect the system it is recommended to install a differential switch with correct
dimensions, type:
Class A, with adjustable dispersion current, selective, protected against sudden
tripping.
The automatic differential switch must be marked with the following two symbols:
7. HYDRAULIC CONNECTIONS
7.1 Always install a check valve on the pipe upstream from the ACTIVE DRIVER.
For the purposes of operation of the ACTIVE DRIVER it does not matter whether the valve is fitted
on the suction or on the delivery of the pump.
7.2 The hydraulic connection between the ACTIVE DRIVER and the electropump must not have any
derivations.The dimensions of the pipe must be suitable for the electropump installed.
7.3
The ACTIVE DRIVER works at constant pressure. This regulation is appreciated if the hydraulic
system downstream from the system is of suitable dimensions.
Systems made with pipes that have too narrow a section introduce load losses which the appliance
cannot compensate; the result is that the pressure is constant on the device but not on the user.
When electrical and hydraulic installation have been completed, supply power to the system and check the
direction of rotation of the electropump. If it is not correct, invert two phases on the motor terminal board.
8. CHARACTERISTICS – INTERPRETATIONS – OPERATION
The ACTIVE DRIVER is an innovative integrated system for controlling electropumps with variable speed, able to
keep a constant pressure while the flow rate varies.
The ACTIVE DRIVER is composed of an inverter, a pressure sensor and a flow sensor.
With the exclusion of models M/M 1.1 and M/T 1.0 the ACTIVE DRIVER is provided with 3 inputs and 2 outputs so
as to be able to realise certain interface solutions with more complex installations.
Figure 1 shows the logical function diagram for the connection of the user input terminals.
Figure 2 shows the logical function diagram for the connection of the alarm output terminals.
Figure 3 shows the connection diagram for 2 ACTIVE DRIVER units, for the exchange function.
8.1 CHARACTERISTICS AND INTERPRETATIONS
Ref. FUNCTION
L – N
SINGLE-PHASE
R – S – T
THREE-PHASE
Power supply line connection terminals.
Line earth system connection terminal.
U - V- W
THREE-PHASE
R – S
SINGLE-PHASE
Three-phase pump 230 V connection terminals
Pump earth system connection terminal.
J22 - 1 Power supply terminal: + 12V DC – 50Am.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22 - 2 Connection terminal of input i3 for general disabling command.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22 - 3 Connection terminal of input i2 for selecting set point 1.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22 - 4 0V connection terminal (GND) for joining I
3
– I
2
to GND.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22 - 5 Connection terminal of input i1 for protection against dry running.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)

ENGLISH
28
Ref. FUNCTION
J22 - 6 0V connection terminal (GND) for joining I
1
to GND.
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J22 - 7 Connection terminal: 0V DC (GND).
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
J14 – o1 Remote alarm connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
250 Vac – 6 A max resistive load – 3 A max inductive load
J14 – o2 Pump operating connection terminal. (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
250 Vac – 6 A max resistive load – 3 A max inductive load
J9
Connection terminals for interconnection and exchange.
ATTENTION: For interconnection cables with a length of more than 1 m, it is
recommended to use screened cable with the braiding connected to earth (central pin
number 2) on both appliances.
ATTENTION: Scrupulously respect the connection sequence between the two
appliances! (excluding A.D. M/M 1.1)
Fig. 1 Fig. 2
Fig. 3
8.2 OPERATION : KEYBOARD SETTINGS
MODE The MODE key allows you to move on to the next items in the individual menus.
SET The SET key allows you to quit the current menu and return to normal operating status.
+ Press to increase the currently modifiable parameter.
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after
which the identifying symbol appears.
- Press to decrease the currently modifiable parameter.
Each time it is pressed, the value of the parameter is displayed for at least 6 seconds, after
which the identifying symbol appears.
When the + key or the – key is pressed, the selected value is modified and saved immediately.
Even the accidental shut-down of the machine during this phase does not cause the loss of the
newly set parameter. The SET key is used only to return to the display of the machine status. It is
not fundamental to press the SET key in order to save the changes made.
1
2
3
4
5
6
7
+12V
GND
J 22
IN 3
IN 2
IN 1
o1
o2
J 14
3
2
1
3
2
1
J 9 J 9
Primary
Active Driver
Secondary
Active Driver
ACTIVE DRIVER M/T 2.2

ENGLISH
29
8.3 OPERATION : PARAMETERS FOR THE USER
Access keys MODE & SET for 2 seconds
8.3.1 SP : Setting the set point pressure ( in bar )
From normal operating status, hold down the MODE and SET keys simultaneously until the letters
SP appear on the display. In these conditions the + and – keys allow you respectively to increase and
decrease the desired pressure value.
The regulating range is from 1.0 to 6.0 bar for the A.D. M/M 1.1 and from 1.0 to 9.0 bar for the other models.
Press SET to return to normal operating status.
As well as the working pressure the ACTIVE DRIVER allows you to set two other values:
RP: expresses in bars the decrease in pressure, with respect to SP, that makes the pump restart.
DP: expresses in bars the desired decrease in pressure at low flow rates.
The three parameters are related to each other.
Diagram for regulating pressure according to in flow rate
SP
Example:
SP = 4.5 bar
DP = 1.0 bar
RP = 0.7 bar Q
During normal operation the system will be pressurised at 4.5 bar.
In case of low flow rates (losses) the system will be pressurised at 3.5 bar.
The electropump restarts when the pressure falls below 2.8 bar.
8.4 OPERATION : PARAMETERS FOR THE INSTALLER
Access keys MODE & SET & - for 5 seconds
If an error or malfunction occurs during this phase, the display is not changed. Depending on
the type of error, the electropump may switch off. However it is still possible to make the
desired calibration. To know the type of error that has occurred you must return to the mode
in which you see the operating status by pressing the SET key.
From normal operating status, hold down the MODE & SET & - keys simultaneously until the letters “rC”
appear on the display. In these conditions the + and – keys allow you respectively to increase and decrease
the value of the parameter while the MODE key allows you to move on to the next parameter in cyclic mode.
Press SET to return to normal operating status.
8.4.1 rC : Setting the rated current of the electropump (excluding A.D. M/M 1.1)
This parameter must be set the same as the current on the motor data plate (Amps) in the configuration
in which it is used (power supply 230V for A.D. M/T - power supply 400V for A.D. T/T).
8.4.2 rt : Setting the direction of rotation (excluding A.D. M/M 1.1)
Possible values: 0 and 1
If the direction of rotation of the electropump is not correct, it is possible to invert the direction of
rotation by changing this parameter.
If it is not possible to observe the direction of rotation of the motor, proceed as follows:
- Open a user and observe the frequency (parameter Fr with MODE key from GO) and the current
(parameter C1).
- Without changing the amount of water taken, change the parameter rt and observe the frequency Fr
and the current C1 again.
- The correct parameter rt is the one which, with the same amount of water taken, requires a lower
frequency Fr and current C1.
p
DP
RP
Pressure set in the system
Reduced pressure for low flow rates
Electropump restarting threshold
5 l/min

ENGLISH
30
8.4.3 od: Setting the operating mode of the ACTIVE DRIVER
Possible values: 1 and 2
The ACTIVE DRIVER leaves the factory in mode 1 for working without expansion vessels or with
small vessels. If there is an expansion vessel near the ACTIVE DRIVER, with a half-inch or larger
fitting, you must change to mode 2.
8.4.4 rP: Setting the fall in pressure for restarting
Expresses, in bars, the fall in pressure that makes the pump restart.
rP may be set from a minimum of 0.1 to a maximum of 1.5 bar.
rP has a limitation system depending on the combination of the values SP and dP so that there is always
a minimum restarting pressure of 0.3 bar.
8.4.5 Ad : Setting the interconnection address (excluding A.D. M/M 1.1)
With the ACTIVE DRIVER system it is possible to realise booster sets composed of two elements
communicating by means of serial interconnection (see fig.3). In this type of installation it is necessary
for the two units to have a different identifying address (Ad).
The admissible values are: “- -”, 1 and 2:
- When “Ad” is “- -” the communication is disabled.
- When “Ad” is “1” it is called Secondary ACTIVE DRIVER (booster).
- When “Ad” is “2” it is called Primary ACTIVE DRIVER (leader).
Attention: If two interconnected ACTIVE DRIVER units are set with the same “Ad” value, the
communication does not work and there may be malfunctions in regulation.
When the communication does not work (due to incorrect setting of the “Ad” value, for wiring
problems, or other reasons), the two ACTIVE DRIVER units will work as though they were two
completely independent machines, but they will indicate the impossibility of dialogue by making the
display blink when the states “Go” or “Sb” are shown.
When the “Ad” values are correctly set, some regulating parameters are aligned. In particular the
secondary ACTIVE DRIVER copies the following values from the primary ACTIVE DRIVER:
- SP : Setting of the set point pressure.
- rP : Setting of the restarting pressure drop.
- Eb : Enabling of the booster pump.
- CM : Method of exchange.
- dP : Setting of the pressure differential at low flow rates.
- P1 : Setting of the input function 2 set point P1.
Note: During operation it is possible to change all the parameters of the ACTIVE DRIVER on each of
the two machines.
8.4.6 Eb : Enable booster (pre-set value 2) (excluding A.D. M/M 1.1)
When two ACTIVE DRIVER units are interconnected with each other, in the case where only one
ACTIVE DRIVER is not able to satisfy the user, there is the possibility of activating the two
electropumps at the same time.
Eb = 1 : The leader-booster operating mode is disabled, so only one electropump at a time will
be active.
If during operation the leader electropump is not able to satisfy the user, the booster
electropump will not be switched on.
Eb = 2 : The leader-booster operating mode is enabled, so 2 electropumps can be activated at the
same time.
If during operation the leader electropump is not able to satisfy the user, the booster
electropump will also be switched on and will work at the maximum frequency, while
the leader machine will continue to modulate the rotation frequency according to the
user.

ENGLISH
31
8.5 OPERATION : TECHNICAL ASSISTANCE DISPLAYS AND SETTINGS
Access keys MODE & SET & + for 5 seconds
8.5.1 tb: Setting the reaction time of the water lack blockage
The setting of the reaction time of the water lack blockage allows you to select the time (in seconds)
taken by the ACTIVE DRIVER system to indicate the lack of water in the electropump. The variation
of this parameter may be useful if it is known that there is a delay between the moment in which the
electropump is switched on and the moment in which it actually starts delivering.
8.5.2 GP: Setting the gain of the proportional coefficient of the PI
For nearly all systems, the GP parameter set in the factory is the optimum one. However, if there
should be any problems in regulation, this setting may be adjusted. Indicatively it may be said that, for
example, the presence of great swings in pressure or of a slow response of the system to variations in
pressure may be compensated by high GP values. Instead the occurrence of “vibrations” in pressure
(extremely rapid pressure swings around the set point value) may be attributed to too high a GP value.
8.5.3 GI: Setting the gain of the integral coefficient of the PI
The integral value must be increased when the system is not very elastic, that is where there is absence
of any expansion. On the contrary, in systems with deformable pipes or with delays due to considerable
distances between the electropump and the ACTIVE DRIVER, the integral value must be lowered.
To obtain satisfactory pressure regulations, you generally have to adjust both GP and GI. In
fact it is the correct agreement between these two parameters which allows the optimum
pressure regulation.
8.5.4 FS: Setting the maximum rotation frequency of the electropump
The ACTIVE DRIVER allows the electropump to be fed for short periods at a frequency higher than
the rated one, returning then to 50 Hz without heating the motor.
When increasing the power supply frequency take care not to exceed the max. current of 9.3
A, otherwise there is a risk of blockage due to current overload in the power stages oF.
8.5.5 dP: Setting the pressure differential at low flow rates
In mode od=01, the setting of the allowed excursion for the pressure set point permits you to select a
pressure interval lower than the set point (SP) at which the ACTIVE DRIVER will regulate the
pressure in the event of low flow rates.
The advantage of selecting a dP different from zero lies in the redimensioning of the flow rate if there
are losses n the system and allows an energy saving so that the electropump can be operated at low
speeds when the requested flow rates are low.
To select the possible dP values, the ACTIVE DRIVER is equipped with a limiting system which
intervenes when pressure set points lower than 2.0 bar are set. In this case the dP is limited to 0.5. See
example on page 29.
8.5.6 Ft: Setting the low flow rate threshold
The ACTIVE DRIVER system possesses a flow sensor. Whenever the electropump is switched off a
new zero is acquired. The ACTIVE DRIVER switches off the electropump when the flow rate reading
is lower than 0 flow (ZF) + the set Ft parameter.
8.5.7 CM : Method of exchange (pre-set value 1) (excluding A.D. M/M 1.1)
When two ACTIVE DRIVER units are interconnected to work in exchange it is possible to choose
between two different strategies for alternating the switching on of the two electropumps.
CM = 0 : The primary ACTIVE DRIVER is always the regulation leader and the secondary
ACTIVE DRIVER will be active as a booster (if Eb=2) or as a reserve (if Eb=1). If the
secondary machine remains unused for 23 hours, it becomes the leader until it has
accumulated one minute of regulation.
If during operation the leader electropump is unable to satisfy the user and the
secondary electropump is set as a booster (Eb=2), the latter will work at maximum
frequency, while the leader ACTIVE DRIVER will continue to modulate the rotation
frequency according to the user.
If the user decreases, the booster machine is switched off, while the leader machine
continues regulating.

ENGLISH
32
CM = 1 : The primary and secondary ACTIVE DRIVER alternate in being the regulation leader.
The exchange takes place each time the leader ACTIVE DRIVER goes into stand-by
mode or after 2 hours of continuous activity.
If during operation the leader electropump is unable to satisfy the user and the
secondary electropump is set as a booster (Eb=2), the latter will work at maximum
frequency, while the leader ACTIVE DRIVER will continue to modulate the rotation
frequency according to the user.
If the user decreases, the leader machine goes into stand-by and becomes the booster
(off), while the booster machine becomes the leader (and starts regulating at variable
speed).
For each of the two exchange modes, if one of the machine breaks down, the other becomes the leader
and carries out regulation at constant pressure up to its maximum available power.
8.5.8 AE : Enabling the anti-frost function (pre-set value 1)
Starts rotating the motor-impeller assembly in order to avoid mechanical blockages.
When the anti-frost function is enabled, if the ACTIVE DRIVER measures a temperature that is too
low with a risk of frost, it automatically starts running the electropump at a low number of revs (25
Hz).
8.5.9 Setup of the auxiliary digital inputs IN1; IN2; IN3 with the parameters i1; i2; i3
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
The function assigned to each of the digital inputs IN1; IN2; IN3 may be activated or modified by
means of the parameters i1; i2; i3.
The setup of the parameters i1,i2,i3 may always assume the values:
0 => function disabled
1 - 3 - 5 => function active on high active input tied to the supply voltage + 12V(see fig. 1)
2 - 4 => function active on low active input tied to GND 0V (see fig. 1)
ATTENTION: The values 3 – 4 – 5 ONLY FOR INPUT IN3 AND PARAMETER i3.
Table summarising the configuration of the digital inputs IN1, IN2, IN3
Parameter Value
0 1 2 3 4 5
With the
intervention of the
command the
system goes into
block and alarm
status with
indication F1 on
the display.
i1
Each function is
disabled
F1 never
appears.
Protection
against dry
running
With input IN1
closed.
Protection
against dry
running
With input IN1
open.
- - - - - -
With the
intervention of the
command the
active set point =
P1.
i2
Each function is
disabled
F2 never
appears.
Active set point
=P1
With input IN2
closed.
Active set point
=P1
With input IN2
open.
- - - - - -
With the
intervention of the
command the
ACTIVE DRIVER
is deactivated with
indication F3 on
the display.
i3
Each function is
disabled
(default)
F3 never
appears.
ACTIVE DRIVER
disabled
With input IN3
closed.
ACTIVE DRIVER
disabled
With input IN3
open.
ACTIVE DRIVER
disabled.
With input IN3
closed
+ eliminate
blockages and
reset.
ACTIVE DRIVER
disabled.
With input IN3
open
+ eliminate
blockages and
reset.
Eliminate
blockages and
reset.
8.5.10 Setting the set point P1 function of input 2 (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
When the parameter i2 is set at a value other than zero, with the input 2 it is possible to select one of the
two settable set points. The first is SP. The second is P1. The regulating range is from 1.0 to 9.0 bar.

ENGLISH
33
8.5.11 O1: Setting output 1 function ( “active alarm” ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
O2: Setting output 2 function ( “pump operating ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Assigning the parameters that associate functions with the digital outputs OUT1; OUT2
Assigning the
parameters
Value
0 1 2 3
o1
Each function is disabled.
Contact always open
Each function is disabled.
Contact always closed
In case of blocking errors
the contact closes (default)
In case of blocking errors
the contact opens
o2
Each function is disabled.
Contact always open
Each function is disabled.
Contact always closed
When the electropump is
operating the contact closes
(default)
When the electropump is
operating the contact
opens
9. DISPLAYS ( see table no. 14 page 36 )
9.1 DISPLAYS OF THE MAIN VALUES
Access key MODE
From normal operating status, pressing the MODE key displays the following values:
Fr: Display of the current rotation frequency (in Hz).
UP: Display of pressure (in bar).
C1: Display of the phase current of the electropump (in A).
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
UE: Display of the version of the software with which the appliance is equipped.
9.2 MONITOR DISPLAYS
Access keys SET & - for 2 seconds
From normal operating status, pressing the key SET & - enters the MONITOR function where the
following values are displayed:
( NB: to scroll through the values press the MODE key)
UF: Display of the flow
Display of the instantaneous flow.
Parameter to be used only as a reference in programming.
ZF: Display of zero flow
Display of the reading of the flow sensor on which zero was acquired (with electropump switched off).
During normal operation the ACTIVE DRIVER will use this parameter to switch off the electropump.
FM: Display of the maximum rotation frequency (in Hz)
tE: Display of the temperature of the power stages (in °C)
GS: Display of running status
SP = pump operating to maintain pressure “SP”.
P1 = pump operating to maintain pressure “P1” (input 2 active).
AG = pump operating for “anti-frost”.
FF: Display of fault history (+ & - to scroll through the alarms)
There is a queue of 16 positions for containing the last 16 faults which have occurred during system
operation. By pressing the – key you can go back in history and stop at the oldest fault present, whereas
by pressing the + key you can go forward in history and stop at the most recent fault present.
The decimal point identifies the last fault to have occurred in chronological order.
The history contains at the most 16 positions. Each new fault is inserted in the most recent position
(decimal point). For each fault after the sixteenth, the oldest one in the queue is erased. The history of
the faults is never erased but only updated as new faults occur. Manual reset and switching off of the
appliance do not erase the history of faults.
10. ACCESS
TO MANUAL MODE OF THE MACHINE
Access keys SET & + & - for 5 seconds
During this phase all the controls and protection systems of the ACTIVE DRIVER are
disabled!

ENGLISH
34
Use of the keys.
Keys pressed Action
“SET” & “+” & “-“ Press them together for a few moments until the display shows MA
+ Increases the frequency and rotation of the electropump
- Decreases the frequency and rotation of the electropump
MODE
Moves on to the next item in the following menu
FP = Setting of the test frequency in manual mode (Hz) ≤at the set FS value
UP = Display of pressure (bar)
C1 = Display of the electropump phase current (A)
rt = Setting of the direction of rotation
UF = Display of flow
ZF = Display of zero flow
MODE & - The electropump runs at the set frequency as long as the keys are held down
MODE & - & +
(for 2 seconds)
The electropump remains operating at the set frequency
The electropump may be switched off by pressing MODE & -
SET Press to leave manual mode
When the system is in manual mode the whole display blinks.
11. GENERAL SYSTEM RESET
Access keys MODE & SET & + & -
To restart the appliance without disconnecting the power supply press the 4 keys simultaneously.
MODE & SET & + & -
12. RESTORING THE FACTORY SETTINGS
Access keys SET & + for 2 seconds when switching on
The factory settings are indicated in table no. 14 on page 36.
To reset the factory values:
Switch off the appliance, press and hold down the SET and + keys while switching on the appliance again, release
the two keys only when the letters EE appear. In this case the ACTIVE DRIVER restores the factory settings.
When it has finished setting all the parameters the ACTIVE DRIVER returns to normal operation.
In this phase, in the models in which RC is active, the motor current is set at 0 as factory
default, so when you try to start the electropump it will immediately give the error EC.
Go to the installer’s display and settings menu (keys MODE & SET & - for 5 seconds ) and
set the correct motor data plate current (parameter rC as in paragraph 8.4.1.)
13. ERROR AND STATUS CONDITIONS
The ACTIVE DRIVER is equipped with a protection system against malfunctions. If any malfunctions
occur, this is indicated on the display and, depending on the type of error, the electropump may switch
off.
In cases of blockage due to water lack (bL), blockage due to current overload in the electropump (oC),
blockage due to current overload in the output stages (oF), blockage due to direct short circuit between the
phases of the output terminal (SC) and of low line (LL) indication, you may try to exit the error conditions
by pressing the “+” and “–” keys simultaneously. If the error condition remains, you must take steps to
eliminate the cause of the malfunction. Error conditions
Error and status conditions
Display indication Description
bL Blockage due to water lack
LP Blockage due to low supply voltage
HP Blockage due to high rectified voltage
LL Low line voltage indication
ot Blockage due to overheating of the power stages
oC Blockage due to current overload in the electropump motor
oF Blockage due to current overload in the output stages
SC Blockage due to direct short circuit between the phases of the output terminal
EC Blockage due to incorrect setting of the rated current
E0...E7 Blockage due to internal error 0...7
F1 Blockage due to input 1 status
F3 Blockage due to input 3 status

ENGLISH
35
13.1 “bL” Blockage due to water lack
In conditions of zero flow the system switches off the pump. If, by mistake, a pressure set-point is set
which is higher than the maximum pressure that the electropump can supply, the system indicates
“blockage due to water lack” (bL) even if there is really no lack of water. Then you must lower the
switch-off pressure to a reasonable value that normally does not exceed 2/3 of the head of the installed
electropump.
13.2 “LP” Blockage due to low supply voltage (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
When the line voltage at the supply terminal falls below 180V, the ACTIVE DRIVER goes into block
status due to low line voltage. This is reset only automatically when the voltage at the terminal rises
above 200V.
If the dimensions of the wiring are not suitably large, this block may occur when the electropump is
started even if higher voltages are measured with the machine in stand-by mode.
13.3 “LL” Blockage due to low supply line (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
This indication is given when more than 5 falls in the supply voltage (LP) are recorded in the space of
an hour. However the appliance continues operating regularly. Repeated switch-offs of the appliance do
not cause the appearance of the “LL” signal.
If the signal “Low line voltage” (LL) is given, the system does not block and the normal indications of
operating status or error continue to alternate on the display.
The ACTIVE DRIVER is equipped with an electronic protection for current overloads in the
electropump motors.
13.4 “SC” Blockage due to direct short circuit between the phases of the output terminal
The ACTIVE DRIVER is equipped with protection against the direct short circuit which may occur
between the phases U, V, W of the “PUMP” output terminal. When this block status is indicated, you
are advised to eliminate the short circuit and to check the wiring carefully to ensure it is unbroken and
the installation in general. Once these checks have been made you can try to reset operation by
simultaneously pressing the “+” and “–” keys; anyway, this will have no effect until 10 seconds have
passed from the moment in which the short circuit occurred.
Whenever a short circuit occurs, an event counter is increased and saved in the permanent memory
(EEPROM).
AFTER THE HUNDREDTH SHORT CIRCUIT THE MACHINE BLOCKS PERMANENTLY
AND IT WILL NO LONGER BE POSSIBLE TO UNBLOCK IT!
13.5 MANUAL RESET of error condition
In error status the operator can reset the error by forcing a new attempt, pressing the “+” and “-” keys
simultaneously.
13.6 Self-reset of error conditions
For some malfunctions and block conditions, the system makes attempts at automatic reset of the
electropump.
The following table shows the sequences of the operations performed by the ACTIVE DRIVER for the
different types of blockage.
Automatic resets of error conditions
Display indication Description Sequence of automatic reset
bL Blockage due to water lack
- An attempt every 10 minutes for a total of 6 attempts
- An attempt every 1 hour for a total of 24 attempts
- An attempt every 24 hours for a total of 30 attempts
LP Blockage due to low supply
voltage
- Reset when voltage returns to a value in the range
220V - 20% + 10%
HP Blockage due to high
voltage
- Reset when the internal voltage returns in acceptable
conditions
Ot Blockage due to overheating
of the power stages
- Reset when the temperature of the power stages falls
below 70°C again
OC Blockage due to current
overload - An attempt every 10 minutes for a total of 6 attempts
oF
Blockage due to current
overload in the output
stages
- An attempt every 10 minutes for a total of 6 attempts

ENGLISH
36
14. INDICATIONS ON THE DISPLAY
Identifying s. Description Factory parameters
Indications on the display in normal operation A.D.
M/M 1.1 A.D.
M/T 1.0 A.D.
M/T 2.2 A.D.
T/T 3.0 A.D.
T/T 5.5
Go Electropump operating
Sb Electropump waiting
User displays and settings (keys MODE & SET 2 seconds )
SP Setting the set-point pressure ( in bar ). Default: 3 bar 3.0 bar 3.0 bar 3.0 bar 3.0 bar 3.0 bar
Installer displays and settings
(keys MODE & SET & - 5 seconds )
rC Setting the rated current of the electropump 0.0 A 0.0 A 0.0 A 0.0 A
rt Setting the direction of rotation 00 00 00 00
od Setting the operating mode 01 01 01 01 01
rP Setting the pressure drop for restarting 0.3 bar 0.3 bar 0.3 bar 0.3 bar 0.3 bar
Ad Setting the interconnection address “- -” “- -” “- -” “- -”
Eb Enabling the booster 02 02 02 02
Technical assistance displays and settings
(keys MODE & SET & + 5 seconds )
tb Setting the reaction time of the water lack blockage 10 s 10 s 10 s 10 s 10 s
GP Setting the gain of the proportional coefficient of the PI 1.0 1.0 1.0 1.0 1.0
GI Setting the gain of the integral coefficient of the PI 1.0 1.0 1.0 1.0 1.0
FS Setting the maximum rotation frequency of the electropump 50 50 50 50 50
dP Setting the pressure differential at low flow rates 0.0 bar 0.0 bar 0.0 bar 0.0 bar 0.0 bar
Ft Setting the low flow rate threshold 15 15 15 15 15
CM Exchange method 01 01 01 01
AE Setting the enabling of anti-frost function 01 01 01 01 01
i 1 Setting the function of input 1 (float) 01 01 01
i 2 Setting the function of input 2 (set point selection) 01 01 01
i 3 Setting the function of input 3 (enable ) 01 01 01
P1 Set point 1: input 2 function 2.5 bar 2.5 bar 2.5 bar
O 1 Setting the function of output 1 (default value: 2; function: ON
alarm ) 02 02 02
O 2 Setting the function of output 2 (default value: 2; function: ON
operating ) 02 02 02
Displays of the main values (MODE key)
Fr Display of the current rotation frequency (in Hz)
UP Display of pressure (in bar)
C1 Display of the phase current of the electropump (in A)
UE Display of the version of the software with which the appliance is
equipped
DISPLAY (keys SET & “-” for 2 seconds )
UF Display of the flow
ZF Display of zero flow
FM Display of the maximum rotation frequency (in Hz)
tE Display of the temperature of the power stages (in °C)
GS Display of running status
FF Display of fault history ( “+” e “-” to scroll )
Access to manual mode (keys SET & + & - 5 seconds ) (d)
MA Operation in manual mode
System reset (keys MODE & SET & + & - )
“ZF” General reset ( ZF appears when leaving reset and restarting )
Restoring the factory settings
(keys SET & + for 2 seconds when switching on)
EE Saving and reading the factory settings on the EEprom
Error and status conditions
bL Blockage due to water lack
LP Blockage due to low supply voltage
HP Blockage due to high supply voltage
LL Low line voltage
ot Blockage due to overheating of the power stages
oC Blockage due to current overload in the electropump motor
oF Blockage due to current overload in the output stages
SC Blockage due to direct short circuit between the phases of the
output terminal
EC Blockage due to incorrect setting of the rated current
E0…E7 Internal error 0…7
F1 Blockage due to input 1 status
F3 Blockage due to input 3 status

DAB PUMPS S.p.A.
Via M. Polo, 14-35035 Mestrino (PD) - Italy
Tél. +39 049 90 48811 - Fax + 39 049 9048847
http://www.dabpumps.com
Ventes Italie zone Nord :
tél. 049 9048873 Fax 049 9048888
Ventes Italie zone Centre Sud :
tel. 049 9048874 Fax 049 9048888
Gestion Dépôts :
tél. 049 9048875 Fax 049 9048888
Service après-vente :
tél. 049 9048911 Fax 049 9048920
DAB PUMPS Ltd
Unit 4,Stortford Hall Industrial Park,
Dunmow Road, Bishops Stortford,
Hertfordshire,
CM23 5GZ
Tel. 01279 652776
DAB PUMPEN DEUTSCHLAND
GmbH
Tackweg 11
D – 47918 Tonisvorst
Tel. 0049 2151 82136 0
Fax 0049 2151 82136 36
DAB PUMPS B.V.
Albert Einsteinweg, 4
NL - 5151 DRUNEN
Tel. 0031 4163 80408
Fax 0031 4163 80181
DAB POMPES S.A.
Brusselstraat, 150
B-1702 Groot-Bijgaarden
Tel. 0032 2 4668353
Fax 0032 2 4669218
03/06 cod.0013.550.91
Other manuals for ACTIVE DRIVER M/M 1.1
1
This manual suits for next models
4
Table of contents
Popular Control Unit manuals by other brands

Danfoss
Danfoss AMZ 112 installation guide

UniData Communication Systems
UniData Communication Systems Neon 2000 Family manual

Walvoil
Walvoil DPC130X Service manual

Graco
Graco 256653 Installation-Parts

American Standard
American Standard Ultima Selectronic 6064.013 installation instructions

Eelectron
Eelectron AD84C01KNX Product handbook