Dacor RV30 User manual

IMPORTANT
1. Before beginning installation, please thoroughly read and become familiar with these instructions.
2. Installation and service must be completed by a qualified installer or service agency.
3. Installer: Please leave these Installation Instructions with the owner.
4. Owner: Please keep these instructions for local electrical inspector’s use and for future reference.
5. Read the accompanying Use & Care Manual prior to operating this appliance.
TABLE OF CONTENTS
Verifying package contents Page 2
Installation planning Page 2
Overall dimensions Page 2
Electrical power supply requirements Page 2
Duct Planning Pages 2-3
Countertop preparation Pages 4
Installing the raised vent Page 5
Blower installation Page 5
Electrical connection Pages 5-6
Verifying proper operation Page 7
Cooktop/Range installation Page 7
Part No. 85515 Rev. D
TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ANSI/UL 858-2001 AND CAN/CSA-C22.2 NO. 64
STANDARD FOR HOUSEHOLD ELECTRIC COOKING AND LIQUID HEATING APPLIANCES.
NOTES:
Contain helpful hints and tips to facilitate the installation.
CONVENTIONS USED IN THESE INSTRUCTIONS
WARNINGS:
Must be followed carefully to avoid personal injury or damage.
SAVE AND READ THESE INSTRUCTIONS
Installation Instructions
Raised Vent

1
WARNINGS:
1. Read all instructions before
using the appliance.
3. Install or locate this appliance
only in accordance with these
installation instructions.
4. Use this appliance only for its
intended use as described in
this manual.
6. Do not operate this appliance
if it has a damaged electrical
cord or plug, if it is not
working properly or if it has
been damaged or dropped.
7. This appliance should be
serviced only by qualified
service personnel. Contact the
nearest DACOR Authorized
Servicer at (800) 772-7778,
or at www.dacor.com for
examination, repair or
adjustment.
8. Do not cover or block any
openings on the appliance.
10. Do not immerse the electrical
cord or plug in water.
11. Keep the electrical cord away
from heated surfaces.
12. Sufficient air is needed
for proper combustion
and exhausting of gases
through the flue (chimney)
of fuel burning equipment
to prevent back drafting.
Follow the heating equipment
manufacturer’s guideline
and safety standards such
as those published by he
national Fire Protection
Association (NFPA), and
the American Society for
Heating, Refrigeration and
Air Conditioning Engineers
(ASHRAE), and the local code
authorities.
13. When cutting or drilling into
wall or ceiling, do not damage
electrical wiring and other
hidden utilities.
14. Duct fans must always be
vented to the outdoors.
15. To reduce the risk of fire, use
only metal duct work to install
raised vents.
16. For general ventilating use
only. Do not use to exhaust
hazardous or explosive
materials and vapors.
17. TO REDUCE THE RISK OF A
RANGE TOP GREASE FIRE:
• Never leave surface units
unattended at high settings.
Boilovers cause smoking and
greasy spillovers that may
ignite. Heat oils slowly on low
or medium settings.
• Always turn hood ON when
cooking at high heat or when
cooking flaming foods.
• Clean ventilating fans
frequently. Grease should not
be allowed to accumulate on
fan or filter.
• Use proper pan size. Always
use cookware appropriate
for the size of the surface
element.
18. TO REDUCE THE RISK OF
INJURY TO PERSONS IN THE
EVENT OF A RANGE TOP
GREASE FIRE, OBSERVE THE
FOLLOWING:
• SMOTHER FLAMES with a
close-fitting lid, cookie sheet,
or metal tray, then turn off
the burner. BE CAREFUL
TO PREVENT BURNS. If
the flames do not go out
immediately, EVACUATE
AND CALL THE FIRE
DEPARTMENT.
• NEVER PICK UP A FLAMING
PAN - You may be burned.
• DO NOT USE WATER,
including wet dishcloths
or towels - a violent steam
explosion will result.
• Use an extinguisher ONLY if:
• You know you have a Class
ABC extinguisher, and you
already know how to
operate it.
• The fire is small and
contained in the area where
it started.
• The fire department is
being called.
• You can fight the fire with
your back to an exit.
IMPORTANT SAFETY INSTRUCTIONS

2
Verifying the Package Contents
• Use and Care manual
• Anchoring Legs
Installation Planning
A qualified technician must complete the
installation of this appliance. Proper installation
is your responsibility.
Raised Vent System Specifications
Raised Vent
Model No.
For Use With For Use with Blower Duct Size
RV30 30” Cooktops CABP3, REMP3/16, ILB8/10 3 1/4”x10”, 8” & 10”
RV36 36” Cooktops CABP3, REMP3/16, ILB8/10 3 1/4”x10”, 8” & 10”
RV46 46” Cooktops CABP3, REMP3/16, ILB8/10 3 1/4”x10”, 8” & 10”
For detailed information on the remote blowers, refer to the Remote Blowers Installation Instructions.
WARNING:
Failure to disconnect power may
result in electrical shock or fire
hazard! If the electric service
provided does not meet the
product specifications, do not
proceed with the installation. Call
the selling dealer or a licensed
electrician.
Electrical Power Supply
Requirements
It is the owner’s responsibility to ensure that
the electrical connection of this appliance
is performed by a qualified electrician. The
electrical installation, including minimum supply
wire size and grounding, must be in accordance
with the National Electric code ANSI/NFPA 70-
1993* (or latest revision) and local codes and
ordinances.
*A copy of this standard may be obtained from:
National Fire Protection Association
1 Batterymarch Park
Quincy, Massachusetts 02269-9101
The correct 120VAC, 60Hz, 15A circuit must
be supplied for this appliance from a separate,
grounded, circuit that is protected by a properly
sized circuit breaker or time delay fuse.
Duct Planning
WARNINGS
1. To reduce the risk of fire and
to properly exhaust air, ducted
fans must be vented to outside.
Do not vent exhaust air into
spaces within walls, ceilings,
attics, crawl spaces or garages.
2. Improper installation,
adjustment, alteration, service,
or maintenance can cause
personal injury or property
damage.
3. To reduce the risk of fire,
use only ductwork materials
deemed acceptable by state,
municipal and local codes.
NOTES:
1. Best performance is achieved
by using round duct instead of
rectangular, especially when
elbows are required.
2. If multiple elbows are needed,
ensure that there is a minimum
of 24” of straight duct between
any two elbows.
3. Avoid “S” or “back to back”
configurations caused by
adjacent elbows.
4. Thermal breaks, such as a
short section of non-metallic
duct, should be used in areas
of extreme cold.
5. A back-draft damper at the duct
outlet may also be required.
6. Do not use flexible metal duct.
7. Do not use ductwork that is
smaller in cross-sectional area
than the recommended size
duct.
Stiffener Channel Location
RV Overall Dimensions
Front View
30” - RV30
36” - RV36
46” - RV46
COOKTOP
8”
26 11/16”
Top Cap
Vent Sleeve
(in raised positionb)
Countertop
Raised Vent
RV30/36/46
Vent Junction Box
120VAC, 15A, Grounded
Junction Box (not provided)
Support Leg
3 1/4” x 10” Duct
2 1/2”
1 13/16”
1/2”
2 1/4”
1/2”
2”
3”
1/4” min. of flat
3/4”

3
Higher volumes of air exhausted by the vent
system result in better overall removal of smoke
and fumes from the kitchen. Longer duct runs
and greater numbers of duct transitions reduce
air volume, therefore it is extremely important
to keep duct runs as short and straight as
possible. When longer runs or multiple turns
are unavoidable, and inline blower may be used
to assist the remote blower.
To ensure that your installation meets this
requirement, add the actual straight length of
duct to the equivalent straight length of all duct
fittings to determine the total equivalent straight
length of duct. (Refer to the table above, which
shows various common duct fittings with their
equivalent straight lengths for various common
duct sizes). If this total equivalent straight
length is less than or equal to the maximum
limits specified, then the installation is proper.
Consider the duct size that corresponds to the
majority of the duct used in the installation.
Sample problem:
Given a remote system installation having 25
feet of 31¼” x 10” rectangular duct, one (1) 90-
degree 3 1¼” x 10” elbow, and one (1) 31¼” x
10” to 8” round transition, would this installation
be proper?
Solution:
1. Add the total length of straight duct:
25’ (of 31¼” x 10”) = 25’.
3 1/4" x 10" 90° Elbow 3 1/4" x 10" 45° Elbow 3 1/4" x 10" Wall Cap 3 1/4" x 10"
90° Flat Elbow
Transistion
3 1/4" x 10" to Round
45° Elbow - Round Duct 90° Transistion
3 1/4" x 10" to 8" Round
90° Elbow - Round Duct
15 Feet 7 Feet 2 Feet 20 Feet
6" Diameter - 4 Feet
7" Diameter - 4 Feet
8" Diameter - 4 Feet
10" Diameter - 4 Feet
6" Diameter - 6 Feet
7" Diameter - 5 Feet
8" Diameter - 3 Feet
10" Diameter - 2 Feet
25 Feet 6" Diameter - 12 Feet
7" Diameter - 10 Feet
8" Diameter - 7 Feet
10" Diameter - 5 Feet
Model
#
Duct
Size
Maximum Equivalent Straight Lengths
CABP3 REMP3 REMP16 ILB10 & REMP16 ILB8 & REMP3
RV
8” 60’ 60’ - - 60’
10” 50’ 50’ - - 50’
3 1/4”x10” 50’ 50’ - - 50’
8. Do not rely on duct tape alone
to seal duct joints. Use sheet
metal screws as require to
support the duct weight.
9. The vent hood and cooking
appliance(s) must be
removable if service is
required.
10. Be certain that the ductwork
does not interfere with floor
joists or wall studs.
11. It is important to keep a
minimum number of turns in
the duct run, and to keep the
run as short as possible.
12. Do not restrict the air flow
by reducing the duct cross-
sectional areas when making
hard joints or squeezing
through a tight area.
13. With concrete slab
construction, "box-in" the
ductwork to prevent it from
collapsing when the wet
concrete is poured. Also allow
room for electrical conduit.
14. Cross-drafts or air currents
caused by adjacent open
windows or doors, HVAC
outlets, ceiling fans, and
recessed ceiling lights reduce
vent efficiency.
2. Using Table above, determine the
equivalent straight length of all duct
fittings: 90-degree 3 1¼” x 10” elbow
= 15’. 31¼” x 10” to 8” round transition
= 4’.
3. Add (1) and (2) to determine the
total equivalent straight length of the
complete duct system: 25’ + 15’ + 4’
= 44’ total equivalent straight duct
length.
4. For the remote system with 31¼” x
10” duct, the maximum allowable total
equivalent straight length of duct is 50
feet. Thus, this proposed installation is
proper.
After determining that your proposed ductwork
meets the maximum duct length requirement,
proceed with the location planning.
3 1/4” x 10” to 8” DIA.
ROUND TRANSITION
REMOTE BLOWER
90˚ ELBOW
3 1/4” x 10”
Run duct under floor (between joists) to nearest
wall and up to roof-mounted Remote Blower
.
RV30/RV36/RV46 with REMP3 Remote Blower,
Island Installation
WALL CAP
12” MIN.
CABINET
BLOWER
3 1/4” x 10”
90˚ ELBOW
Run duct directly through rear
wall to outside wall cap.
RV30/RV36/RV46 with CABP3 Cabinet Blower,
Direct Connection
NOTE:
The ILB8 & ILB10 Inline Blowers
are only approved as a boost
assist to the REMP3 and REMP16
Remote Blowers and the CABP3
Cabinet Blower.

4
WARNINGS:
1. To reduce the risk of personal
injury caused by reaching
over a hot appliance, cabinet
storage space located directly
above the cooktop should be
avoided.
2. Do not store combustible
materials or items adversely
affected by heat in cabinet
areas above the appliance.
3. Follow the instructions
regarding minimum safe
clearances and installation
location. Failure to do so may
result in a fire or safety hazard.
NOTE:
When installing the cooktop and
vent into a laminated (Formica®,
etc.) or synthetic (Corian®, etc.)
countertop, follow the countertop
manufacturer’s instructions
regarding the minimum corner
radius, use of heat reflective tape,
reinforcement of corners, etc.
Plan the installation so that all required minimum
clearances between the cooktop, overhead
cabinets and adjacent vertical walls are
provided. Refer to the cooktop/range installation
instructions for the minimum dimensions specific
to the particular appliance being installed.
The DACOR Raised Vent System is designed
to remove the contaminants and by-products
that result when cooking with gas or electric
appliances. The vent system consists of the vent
intake along with a remote blower and a inline
blower if needed. The raised vent downdraft
systems are compatible for use with select
DACOR cooktops and ranges, therefore, these
instructions offer specific guidelines for mounting
the raised vents behind DACOR cooktops and
ranges.
t=max. backsplash thickness
25"
B
C
A
D
Combustible
Rear Wall
Cutout and Overall Dimensions
(CER304, CER365, ETT304, ETT365, SGM466, SGM464EM)
Countertop Preparation
Below Countertop Preparation
The raised vent intake, blower (in cabinet
mounted models only), and cooktop are
designed for installation into standard U.S.
made base cabinets. Before making the
countertop cutout, make certain that the cooktop
and vent system will clear the cabinet walls,
backsplash, and any wall studs along the back
wall within the cabinet.
Dacor
Model No.
Cutout
“A”
Cutout
“B”
Cutout
“C”
Cutout
“D”
Dimension
“t”, max.
Overall
Width
CER304 19 7/8” 28 1/2” 27 1/2” 2 3/8” 3/4” 30”
CER365 19 7/8” 34 1/2” 33 1/2” 2 3/8” 3/4” 36”
ETT304 19 7/8” 28 1/2” 27 1/2” 2 3/8” 3/4” 30”
ETT365 19 7/8” 34 1/2” 33 1/2” 2 3/8” 3/4” 36”
SGM304 22 1/4” 27 1/2” - - 3/4” 30”
SGM364 22 1/4” 33 3/4” - - 3/4” 36”
SGM365 22 1/4” 33 3/4” - - 3/4” 36”
SGM466 19 7/8” 19 7/8” 43 1/2” 2 3/8” 3/4” 46”
SGM464EM 19 7/8” 19 7/8” 43 1/2” 2 3/8” 3/4” 46”
NOTES:
1. If there is a backsplash with a
curved base at the countertop
level, then the clearance
behind the vent will be
reduced. Keep this in mind to
avoid interference.
2. If your cabinet differs from
the standard 24” deep, 36”
high cabinets shown in Figure
4, then adjust your cutout
locations accordingly to
prevent interference.
3. If a drawer or shelf is being
installed below a gas cooktop,
be certain to avoid interference
with the gas supply line and
the drawer or shelf.
4. For installation with gas
cooktops, a 90-degree elbow
must be connected to the
cooktop gas inlet to avoid
interference with the Raised
Vent plenum front.
Locate the house junction box adjacent to the
vent junction box found at the lower right of the
vent plenum.
t=max. backsplash thickness
25"
B
A
Combustible
Rear Wall
Cutout and Overall Dimensions
(SGM304, SGM364, SGM365)
Finished
Countertop
11/16" (17mm) to 3 11/16" (94mm)
to right of centerline
3 1/2" x 10 1/4"
(89mm x 260mm)
Optional
8"
(203mm)
30 13/16"
(783mm)
Rear edge of
cooktop/vent
cutout
plumbed down
Down Duct Cutout Dimensions
RV with CABP3 Blower
NOTE:
Access from the front of the
cabinet to the underside of the
cooktop, the vent system, and the
junction box must be provided
for inspection and service. Any
drawers or shelves placed below
the cooktop and in front of the
vent must be easy to remove for
access to the cooktop, vent and
junction box.
For installation of the raised vent system,
provide an opening in the countertop as shown
in the Countertop Preparation section. Position
the cutout so all required minimum clearances
are met. Make certain that the minimum flat
countertop area meets or exceeds the combined
overall width and overall depth, as shown.
NOTE:
Verify that the raised vent and
blower being installed are a
matched pair before beginning the
installation.

5
Blower Installation
WARNING:
Do not slide the CABP3 blower
over or beyond the mounting
stop on the blower mounting
groove. To do so may prevent
the vent sleeve from raising and/
or lowering due to interference
between the blower and the vent
drive arm assembly.
Connecting the Exhaust Duct
NOTE:
Use duct tape to seal the
connection between the blower
outlet and duct. Support the duct
weight as necessary to ensure
sealed joints.
For the side or bottom knockouts use the sup-
plied transition (ATD2). For the rear knockout
attach a 3 1/4" x 10" duct.
Electrical Connection
WARNINGS:
1. Ensure that the power supply
is disconnected before
proceeding.
2. Verify that the power supply
matches the ratings found on
the appliance data plate before
proceeding.
3. The complete appliance must
be properly grounded at all
times when electrical power is
applied.
4. Do not ground the appliance
with the neutral (white) house
supply wire. A separate
ground wire must be utilized.
5. If aluminum house supply
wiring is used, splice the
appliance copper wires to the
aluminum house wiring with
special connectors designed
and agency-certified for this
purpose. Follow the connector
manufacturer’s recommended
procedure carefully. Improper
connection can result in a fire
hazard.
N1
L1
N2
BLK
WHT
120VAC, 60Hz, 15A
Supply power from
dedicated circuit breaker
GRN
WHT
L2
BLK
BLK
WHT
Gnd
GRN
Gnd
GRN
RV
L2
N2
Gnd
GRN
WHT
BLK
L2
N2
Gnd
GRN
WHT
BLK
GRN
WHT
BLK
ILB
REMP OR CABP3
J-BOX
Wiring of RV with ILB and REMP or CABP3
Installing the Raised Vent
Loosely attach the support legs to the left and
right sides of the plenum using the hex nuts
provided. Place the vent into the rear of the
countertop cutout. Adjust the support leg height
so that the end caps are gently resting on the
counter, then tighten the hex nuts. Secure the
support legs to the cabinet floor with the screws
provided.
For the cabinet blower application, place the
adhesive-backed foam tape provided with the
cabinet blower onto the left and right vertical
blower flanges. Slide the blower outlet into the
exhaust duct, while making sure that the lower
blower flange slides into the blower mounting
groove on the vent. Use duct tape to seal the
connection between the blower outlet and the
duct. Support the duct weight as necessary to
ensure sealed joints.
For downdraft vents utilizing the remote blowers,
locate the AREM found in the RV carton. Attach
the adhesive-backed foam tape provided with
the blower to the left and right vertical blower
cover flanges. Attach the Remote Blower Cover
(AREM) to the large opening in the front of the
vent. The vent is now ready to be ducted for a
remote blower installation.
NOTE:
For both the cabinet and remote
systems, the vent must be
installed in a vertical orientation.
Do not mount the vent on a slant
or angle.
6. Failure to complete electrical
connections properly may
result in a damaged or non-
functional system. Follow the
wiring diagrams carefully to
ensure a proper installation.
Both vent systems require a properly grounded,
120 VAC, 60 Hz., 15 Amp electrical service.
Max. full line load is 8 amps. Always use a
dedicated circuit. Do not use same circuit that
cooktop is using.
Make all electrical connections between the vent
and blowers, then connect power to the vent as
per the wiring diagrams shown on pages 5 and
6. Use wire nuts provided and electrical tape to
secure all wiring connections at the blowers.

6
N1
L1
N2
L2
N2
Gnd
BLK
WHT
120VAC, 60Hz, 15A
Supply power from
dedicated circuit breaker
GRN
WHT
L2
BLK
BLK
WHT
Gnd
GRN
Gnd
GRN
GRN
WHT
BLK
RV
REMP OR CABP3
N1
L1
N2
BLK
WHT
120VAC, 60Hz, 15A
Supply power from
dedicated circuit breaker
GRN
WHT
L2
BLK
BLK
WHT
Gnd
GRN
Gnd
GRN
RV
L2
N2
Gnd
GRN
WHT
BLK
L2
N2
Gnd
GRN
WHT
BLK
GRN
WHT
BLK
ILB
REMP OR CABP3
J-BOX
Wiring of RV with REMP or CABP3
Wiring of RV with ILB and REMP or CABP3

7
Cooktop Installation
Set the cooktop into the countertop opening so
that the back edge of the cooktop overlaps the
leading edge of the vent. (Refer back to page 4.)
Follow the cooktop manufacturer’s installation
instructions regarding securing the cooktop to
the countertop and completing the electrical
and/or gas connection.
NOTE:
Do not use a hardening
compound or caulking to
permanently seal the cooktop and
vent into place, as the units must
be easily removed for service. If
such a hardening compound is
used, removal of the units will be
at the customer’s expense.
Verifying Operation
Please read the accompanying Use & Care
Manual carefully. Important safety, service and
warranty information is contained within this
manual.
WARNINGS:
1. If the vent system is not
operational after completion of
the installation, do not attempt
to repair it. See the Problem
Solving section of the Use
& Care Manual, then call a
qualified service technician if
the
system is still not functional.
2. Always disconnect the
appliances from the electrical
power when servicing them.
3. Install the two (2) grease filters
and the grill prior to operating
the vent. Refer to the Use
& Care Manual for instructions
regarding filter and grill
installation.
4. Ensure that the top cap on
the vent intake does not
catch on the back edge of the
cooktop when the intake is
lowered. If interference does
occur, adjust the position
of the cooktop by moving
it against the front edge of
the countertop cutout, then
re-secure the cooktop to the
countertop. Also, ensure that
the vent support legs have
been properly secured to the
cabinet base using the screws
provided in the instructions
envelope. Failure to eliminate
interference may result in
permanent damage to the
vent.

8
NOTES:

9
NOTES:

10
NOTES:

Web Site: www.dacor.com
For a Dealer/Service: (800) 772-7778
Corporate Phone: (800) 793-0093
Other manuals for RV30
4
This manual suits for next models
2
Table of contents
Other Dacor Fan manuals
Popular Fan manuals by other brands

Nailor
Nailor Engeneered Comfort 39MU Series Installation and operation manual

inVENTer
inVENTer iV-Twin+ installation instructions

Daikin
Daikin F-Series instruction manual

Savo
Savo RH-9709-W instruction manual

Inline
Inline 40161 user manual

Minka Group
Minka Group minkaAire CRISTAFANO F900L-BCW Instruction manual warranty certificate