IOM 1281-2 • CENTRIFUGAL WATER CHILLERS 10 www.DaikinApplied.com
Water Piping
All evaporators and condensers have OGS-type grooved water
connections (adhering to Standard AVVWA C606) or optional
matching mechanical connections. Be sure that water inlet
markings. PVC/CPVC piping should not be used.
CAUTION
Polyolester Oil, commonly known as POE oil is a synthetic
oil used in many refrigeration systems, and may be present
in this Daikin Applied product. POE oil, if ever in contact with
PVC/ CPVC, will coat the inside wall of PVC/CPVC pipe
causing environmental stress fractures. Although there is
no PVC/ CPVC piping in this product, please keep this in
mind when selecting piping materials for your application, as
system failure and property damage could result.
CAUTION
connections:
1. Remove the solid-state temperature sensor,
switches from the wells to prevent damage to those
components.
2. Properly ground the unit or severe damage to the
MicroTech®unit controller can occur.
NOTE:
performed on a vessel shell or tube sheet.
The water heads can be interchanged (end for end) so that
the water connections can be made at either end of the unit.
If this is done, use new head gaskets and relocate the control
sensors.
Field installed water piping to the chiller must include:
• air vents at the high points.
• a cleanable water strainer upstream of the evaporator
and condenser inlet connections.
•
condenser. Flow switches, thermal dispersion switches,
or Delta-P switches can be used. Note that thermal
series with the ones already provided. Connect additional
discussed on page 68.
• water pressure gauge connection taps and gauges at the
inlet and outlet connections of both vessels for measuring
water pressure drop.
•
chiller must be capable of draining the water from the
evaporator or condenser without draining the complete
system.
• Piping must be supported to eliminate weight and strain
• Chilled water piping must be adequately insulated.
• thermometers at the inlet and outlet connections of both
vessels.
CAUTION
When common piping is used for both building heating and
cooling modes, care must be taken to provide that water
this hot can damage controls or cause the relief valve to
discharge refrigerant.
a shell and tube evaporator with carbon steel shell and
the wetted surfaces of the heat exchangers must be clean
and non-corrosive to the standard materials of construction.
Daikin Applied makes no warranty as to the compatibility
standard materials of construction is in question, a professional
corrosion consultant should administer the proper testing and
evaluate compatibility.
Water Quality Guidelines
The water quality provided by the owner/occupant/operator/
user to a chiller system should minimize corrosion, scale
of HVAC equipment without creating a hazard to operating
personnel or the environment. Strainers must be used to
protect the chiller systems from water-borne debris. Daikin
Applied will not be responsible for any water-borne debris
damage or water side damage to the chiller heat exchangers
due to improperly treated water.
during initial chiller installation/commissioning and maintained
on a continuous basis by water treatment professionals (see
Limited Product Warranty)
CAUTION
The improper use of detergents, chemicals, and additives
performance and potentially lead to repair costs not covered
by warranty. Any decision to use these products is at the
discretion of the owner/occupant/operator/user and as such
they assume full liability/responsibility for any damage that
may occur due to their use.