
DD3922077
Rev 03
16 April 2020
NPN-410X/ZPN-1000 Series Wall-Mount Substructure Quick Guide Page 1 of 1
201 Daktronics Drive
Brookings, SD 57006-5128
www.daktronics.com/support
800.325.8766
The standard NPN-410X/ZPN-1000 display
substructure is vertical aluminum tubing
with mounting pass-through holes and
shims for attachment to a wall or
equivalent structure. The panels are
self-drilled into the vertical tubes at four
points per panel. The tubes must be
vertically level, or plumb, on the face
and sides, horizontally level on the
top/bottom across multiple tubes,
vertically at along each tube, and
horizontally at across multiple tubes.
Tubes come in two different types
(panel-to-panel tubes and narrow
tubes for the far-left and far-right edges
of the display face) in nine different
sizes ranging from one panel high to
a maximum of nine panels high. Refer
to Figure 1. Each panel height has two
mounting pass-through holes.
1. Attach 3/4" plywood to the wall before substructure attachment if the
holes in the tubes do not line up with studs on the wall. Other wall
materials such as concrete should not require the 3/4" plywood, but
refer to the contract-specic Shop Drawing for verication.
2. Check the wall for atness and levelness with a laser level (or a level
and string if a laser level is not available). Refer to Figure 2.
Figure 2: Marked Tube Positions Figure 3: Attach Tube
1: Mounting pass-through hole
2: Additional mounting pass-through
hole for seismic-affected regions
1
2
a. A three-plane laser level is preferred. Set the Z-plane a set distance
from the wall. Mark the tube positions and make note of the high
and low points of the wall along the tube screw position.
Figure 1: Tube Type
b. A string level can be used if a laser level is unavailable. Mark the
tube positions and install all vertical tubes. Mount each tube to
the wall with one screw and secure a string line taut across all
vertical tubes. It is recommended to run two string lines per vertical
tube. This method will show the highest point of the wall. Shim all
remaining tubes to touch the string line.
3. Fill the required hole(s) in the tubes. Refer to Figure 3. In
seismic-affected regions, two holes per panel height must be lled. In
all other regions, only one hole per panel height is required. Refer to the
contract-specic Shop Drawing for details on how many holes to ll.
4. Attach the tube (center tube rst)
and use a large level to ensure the
side of the tube is level. Refer to
Figure 4. Tubes will recess 1/4" from
both the top and bottom of the
display. Refer to Figure 5.
Ensure the tube is positioned
vertically within 1/4" of the
specications on the Shop Drawing.
Start the tube mounting hardware
through the tube into the wall, but do
not tighten down.
Figure 5: Tube on Panel (Top View)
5. Add shims on the started hardware
between the tube and the wall and
use a level to ensure the tube
remains plumb to the wall and at
over the entire length of the tube.
Refer to Figure 6. If the appropriate
amount of shims is not used, the wall
anchors can bow.
Note: The shims on the left and
right tubes should be
oriented so the
tail/tag sticks out behind
the display and out of
sight when the display
is fully installed. Refer to
Figure 7.
6. Repeat Steps 1-5 to attach the remaining tubes to the right and left
of the center tube. Level each tube separately. Refer to Figure 8 and
Figure 9. Place shims between the wall and the tube until the tube is
plumb. Each individual tube should be level within 1/4" from the lowest
to highest point along the entire vertical length of the display tube(s).
Figure 4: Verify Plumb First Tube
Figure 6: Verify
Plumbness
Figure 7: Shim
Orientation
Figure 8: Check Plumbness Figure 9: Check Plumbness
7. Check the atness at the top and bottom of the tubes (Figure 10),
along the height of the tubes (Figure 11), and diagonally across the
tubes (Figure 12), measuring across three tubes at a time, to ensure
it does not exceed the max out of at of 1/16" and there is no rocking.
Each individual tube should be level within 1/4" from the lowest to
highest point along the entire vertical length of the display tube(s). If
the tube does not meet the level with a gap greater than 1/4" or if there
is rocking, add shims to the affected tubes to bring them into spec.
Figure 10: Check
Flatness
Figure 11: Check
Flatness
Figure 12: Check
Flatness
8. Re-level any individual vertical tube
that was adjusted but do not remove
the shims that were added to make
the tube faces at to each other.
Repeat this step, incrementing one
tube to the right or left so all tubes in
the display are plumb, level to each
other, and at to each other. After
this has been veried, tighten down
the tube hardware to the wall.
9. Repeat Steps 1-8 if additional rows of
tubes are required. Space the tubes
approximately 1/2" apart vertically.
Refer to Figure 13. Tighten down the hardware and quality check the
plumbness and atness.
After the tube hardware is tightened down and the tubes are level and
at, begin panel installation. Refer to the appropriate Installation & Service
Quick Guide: NPN-4100 (DD3830324), NPN-4101 (DD4133945), NPN-4102
(DD4174150), or ZPN-1000 (DD4175845).
Figure 13: Install Second Row