manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Danfoss
  6. •
  7. Controllers
  8. •
  9. Danfoss 324166 Owner's manual

Danfoss 324166 Owner's manual

www.danfoss.com DKCD 5/2002
Temperature setting
Set room temperature on the thermostat dial. On
the right-hand side of the thermostat is a func-
tion switch with 3 possible settings:
Sun
:The room temperature will be as set on the
thermostat.
Clock
: Used only if the zone regulator is en-
gaged.The temperature will be as set on the
room thermostat, but in accordance with the
consumption pattern entered.
The consumption pattern in the zone regulator
can be overridden by moving the switch to sun or
moon.
Moon
:The room temperature will be as set on
the thermostat - minus 5°C.
Limitation of the setting range
Behind the button for temperature setting are two
lock-pins.These can be placed in the setting
knob as shown in fig. 4 if the thermostat setting
range is to be narrowed.
Putting into operation
Each room thermostat has a unique ID number
preventing conflicts with other thermostats.
A single room thermostat is capable of regulating
several heating outputs, provided these outputs
are assigned to the thermostat.
Assigning thermostats to output(s)
-The installation cable between room thermostat
and CFM (fig. 2) must be connected in assigning
each thermostat to the respective output(s).
-IntheLED array the firstavailable output will
flash. The LED in the CFR will also flash. Out-
puts already assigned will not be lit (fig. 2). By
pressing OK the thermostat will be assigned to
that output. If the room thermostat is to be as-
signed under another lit output, scroll to the out-
put bymeans of the +/- keys,then press OK.
-When the installation cable is removed, the red
LED behind the front panel (fig. 4) will flash for at
least 4 minutes.See “Test of room thermostat”
Removal of assigned thermostat
-It is not necessary to have the installation
cable in place when removing an assigned ther-
mostat. Once a thermostat has been removed, it
may be reassigned to another output.
-Removal of room thermostat is done by pressing
OK for 5 seconds, then the entire LED array will
be lit. Scroll to the specific room thermostat to
be removed with the +/- button,and press OK for
5 seconds. The thermostat has now been re-
moved.
Test of room thermostat
If a defect in a room thermostat is suspected, the
following test may be carried out:
- Set the thermostat to the highest temperature.
- Move the function switch on the side of the
room thermostat to a new position.
- If the LED behind the front panel (fig. 4)
flashes quickly for 4 minutes, the room thermo-
stat is OK.
Battery change
If the battery is getting low, the LED will flash 6
times every 6 seconds. See fig. 4.
Master regulator CFM
This regulator governs the individual heat cir-
cuits via wireless communication with the asso-
ciated room thermostats. Connection of 8 heat
circuits is enabled.
If more heat circuits are required, connect one
or max. two slave regulators CFS, each with
connection for 8 circuits.This allows max.24
heat circuits to be governed.
The master/slave is to be fitted immediately
above the distributor pipe on the wall or in a dis-
tribution cabinet. Easy access to plugs and ter-
minals should be ensured.See instruction draw-
ing on the opposite page.
If two slave regulators are connected, move the
jumper in “slave 2” to position 2.See instruction
drawing.
The connection cable for the slave regulator is 1
m.Cable lengths of up to 100 m are enabled
(available from your electrical items wholesaler)
Alarm
There are 2 options with respect to alarms given
by the master regulator:
-Integral acoustic signal can be selected by
moving the jumper marked “buzzer” from OFF
to ON.See installation drawing.
-External alarm generator can be connected to
the output marked .
Technical data
Max.ambient temperature 60°C.
Enclosure IP40
Zone regulator CFZ
The zone regulator governs a maximum of 6
heat zones.For each heat zone, individual tim-
ing programmes can be connected.For reading
and operating convenience, it is recommended
to place the regulator at eye height.
The connection cable is 5 m.Cable lengths up
to 100 m are permitted (available from your
electrical items supplier).
Troubleshooting
Appearance Problem Reason/cause Solution Comments
CFM controller out-
put array blinks
specifically from a
row and column(s)
Alarm symbol in
zone controller,
CFZ flashes
Acoustic alarm
buzzes (provided
jumper is set to
“ON”)
Master or slave
controller row(s)
and entire columns
lit on master output
array
Constant light in
LED array
LED on back of
room thermostat
does not blink dur-
ing test mode
All output LEDs are
unresponsive
CFM controller out-
put array blinks rap-
idly 3 times specifi-
cally from a row
and column(s)
Lack or ex-
cessive heat
to floor heat-
ing system
Room tem-
perature is
below 6oC
(43oF)
No heat
No heat
Lack or ex-
cessive heat
to floor heat-
ing system
No heat
None
Distance between room and
master is too far.
Degradation of signal due to
reinforced concrete or foil
faced insulation between
floors.
External antenna mounted
close to metal parts or wires.
Master control is placed in
metal enclosure.
Interference from electronic
equipment using the same
frequency, 433.92Mhz (i.e.
baby monitors, portable or
wireless headphones)
Low battery
Problem in heating system
or signal to thermostat
Blown fuse in master/slave
Loose wire connection be-
tween master and slave con-
troller
Defective zone actuator
Lack of heated fluid to sys-
tem
Faulty battery
Bad contacts between bat-
tery and thermostat
Defective room thermostat
Improper wiring
Master controller is defective
Normal operation during test
of room thermostat
Reposition thermostat in
room until signal is clear.
Reposition external an-
tenna, however if signal is
still unclear move external
antenna to the
same floor as
thermostat(s)
Reposition room thermo-
stat and run test mode
Mount external antenna if
not already installed.
Eliminate interfering elec-
tronic equipment
Replace battery and test
thermostat
Check heating supply to
the system and the circu-
lator pump
Check master control,
CFM, is properly wired.
First check actuators for
proper wiring then re-
place fuse in
master/slave controller,
1.25A
Check wire and connec-
tion between master and
slave
Replace zone actuator
Check heating supply to
the system and the circu-
lator pump
Replace battery/
Adjust connection in ther-
mostat to ensure better
contact to battery
Replace room thermostat
Check wiring of power to
CFM
Replace master control-
ler.
If signal is
continuosly
poor contact
Danfoss
Max. load for
CFM 6W,
max. Load
for CFS 3W
Installation and operation Wireless floorheating controller and room thermostat, type CF
www.danfoss.com DKCD 5/2002
CFR CFZ
CFM
CFS
CFS 24 T 1.25A
+T 0.5A
CFS 230 F 4A
+T 0.5A
CFM 24 T 1.25A
CFM 230 F 4A
1
2
3
4
5
www.danfoss.com DKCD 5/2002
GB Typical wiring diagram (Europe)
D Typischer Schaltplan
DK Typisk el-diagram
S Elanslutning
FIN Kytkentäkaaviomalli
Typical wiring diagram
(Applies to the USA & Canada)
Pump: 115V, 1 phase,
60 Hz, 3A max.
T 1.25 A protects outputs
T 0.5 A protects controller
L1
L2
L1
L2
FCC ID: PGBTYPE-CFR , CAN 3934104209
This device complies with Part 15 of the FCC Rules and with
RSS-210 of Industry Canada and with RSS-210 of Industry
Canada:
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2)This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications to this unit not expressly
approved by the party responsible for compliance could void
the user’s authority to operate the equipment.
F Diagramme (Europe)
NL Aansluitschema (Europa)
PL Przykład schematu połączeń (Europa)
CZ Typické schéma zapojení (Evropa)
GB If the regulator is fitted in a metal cabinet or where a wall, a concrete
floor or other structural components attenuate the transmission signal from the
room thermostats to such an extent that a faulty alarm is triggered, an external
antenna, order no.088H0093, must be used.
D Wird der Regler in einem Metallschrank oder an einem Ort montiert,
an dem die Dämpfung des Signals von den Raumthermostaten durch Wände,
Betondecken oder andere Gebäudeteile zu Fehlalarmen führt, so ist eine ex-
terne Antenne, Bestellnr.088H0093, einzusetzen.
DK Hvis regulatoren monteres i et metalskab eller hvor væg, betondæk
eller andre bygningsdele dæmper sendesignalet fra rumtermostaterne så
meget, at der op står fejlalarm, skal der anvendes en ekstern antenne, best.nr.
088H0093.
S Om regulatorn monteras i ett metallskåp, eller där väggar, betonggolv
eller andra byggnadsdelar dämpar sändarsignalen från rumstermostaten så
mycket att larmet löser ut, ska man använda en extern antenn, best.nr
088H0093.
FIN Jos ohjain asennetaan metallikoteloon tai paikkaan, jossa seinä,
betonilattia tai muut rakennusosat vaimentavat huonetermostaattien
lähettämää viestiä niin paljon, että järjestelmä antaa vikahälytyksen, on
käytettävä ulkopuolista antennia, tuotenumero 088H0093.
F En cas d’installation du régulateur dans une armoire métallique ou
bien à tout autre endroit où un mur, une plate-forme en béton ou d’autres
éléments de construction atténuent le signal émis par les thermostats
d’ambiance au point de déclencher une fausse alarme, il convient d’utiliser un
capteur externe, n° de code 088H0093.
NL Als de regelaar in een metalen behuizing wordt gemonteerd of op
plaatsen waar een wand, beton of andere delen van een gebouw het
zendsignaal van de ruimtethermostaten dusdanig dempt dat er foutalarmen
ontstaan, moet er een externe antenne, best.nr.088H0093, worden gebruikt.
PL Jeżeli regulator znajduje się w metalowej obudowie lub betonowe
ściany i stropy osłabiają sygnał wysyłany przez termostaty pokojowe, należy
zastosować zewnetrzną antenę (numer katalogowy 088H0093)
CZ Pokud je regulátor namontován v kovové skříni nebo na místě, kde
dochází ke snížení kvality signálu /stěna, betonový strop nebo jiné části
budovy/ je třeba instalovat přídavnou anténu, obj. č. 0088H0093.

Other Danfoss Controllers manuals

Danfoss AK-CC55 User manual

Danfoss

Danfoss AK-CC55 User manual

Danfoss VLT AutomationDrive FC 300 Guide

Danfoss

Danfoss VLT AutomationDrive FC 300 Guide

Danfoss EKC 202A User manual

Danfoss

Danfoss EKC 202A User manual

Danfoss VLT Option Panel User manual

Danfoss

Danfoss VLT Option Panel User manual

Danfoss EKC 319A User manual

Danfoss

Danfoss EKC 319A User manual

Danfoss AK-SM 800 User manual

Danfoss

Danfoss AK-SM 800 User manual

Danfoss FC 300 Guide

Danfoss

Danfoss FC 300 Guide

Danfoss AFP Series User manual

Danfoss

Danfoss AFP Series User manual

Danfoss ECL 2000 User manual

Danfoss

Danfoss ECL 2000 User manual

Danfoss ADAP-KOOL Drive User manual

Danfoss

Danfoss ADAP-KOOL Drive User manual

Danfoss vlt soft starter mcd 500 User manual

Danfoss

Danfoss vlt soft starter mcd 500 User manual

Danfoss AK-CC55 User manual

Danfoss

Danfoss AK-CC55 User manual

Danfoss MCX15B2 User manual

Danfoss

Danfoss MCX15B2 User manual

Danfoss AME 55QM User manual

Danfoss

Danfoss AME 55QM User manual

Danfoss ECL Comfort 210 User manual

Danfoss

Danfoss ECL Comfort 210 User manual

Danfoss VLT HVAC Drive FC 102 Operating instructions

Danfoss

Danfoss VLT HVAC Drive FC 102 Operating instructions

Danfoss VLT FC Series Spare Brake IGBT User manual

Danfoss

Danfoss VLT FC Series Spare Brake IGBT User manual

Danfoss AVT/VG User manual

Danfoss

Danfoss AVT/VG User manual

Danfoss EKC 347 User manual

Danfoss

Danfoss EKC 347 User manual

Danfoss EvoFlat WSS User manual

Danfoss

Danfoss EvoFlat WSS User manual

Danfoss ADAP-KOOL AK-PC 651 User manual

Danfoss

Danfoss ADAP-KOOL AK-PC 651 User manual

Danfoss ERC 112D User manual

Danfoss

Danfoss ERC 112D User manual

Danfoss ICAD 600A User manual

Danfoss

Danfoss ICAD 600A User manual

Danfoss FT1555-BM User manual

Danfoss

Danfoss FT1555-BM User manual

Popular Controllers manuals by other brands

Hypercom Thales Specification sheet

Hypercom

Hypercom Thales Specification sheet

Crestron CNECI-4A Operation guide

Crestron

Crestron CNECI-4A Operation guide

Abus WINTECTO One Fitting and operating instructions

Abus

Abus WINTECTO One Fitting and operating instructions

Kapego XS PRO user manual

Kapego

Kapego XS PRO user manual

Buspro HDL SB-DN-HVAC user manual

Buspro

Buspro HDL SB-DN-HVAC user manual

Interphase 4538 Hardware reference manual

Interphase

Interphase 4538 Hardware reference manual

PPI Neuro 102EX user manual

PPI

PPI Neuro 102EX user manual

NovaStar VX4 user manual

NovaStar

NovaStar VX4 user manual

GARDASOFT CC320 user manual

GARDASOFT

GARDASOFT CC320 user manual

Infineon Technologies ICE2PCS Series Design guide

Infineon Technologies

Infineon Technologies ICE2PCS Series Design guide

iseg CC23 user manual

iseg

iseg CC23 user manual

Horizont turbomax AN800 instruction manual

Horizont

Horizont turbomax AN800 instruction manual

Rice Lake 820i installation manual

Rice Lake

Rice Lake 820i installation manual

Victron energy Cerbo GX manual

Victron energy

Victron energy Cerbo GX manual

Siemens SIMATIC S7 operating instructions

Siemens

Siemens SIMATIC S7 operating instructions

Siemens SIRIUS 3RW44 user manual

Siemens

Siemens SIRIUS 3RW44 user manual

Raven AccuBoom installation manual

Raven

Raven AccuBoom installation manual

Symondo Box Installation and operating instruction

Symondo

Symondo Box Installation and operating instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.