Dantherm KONTROLLELEKTRONIK FCB 773 User manual

U:\Manuals\FCB\FCB 773 -EN-.pdf
1/10 2009-02-05
Free Cooling Box FCB 773
Service manual

U:\Manuals\FCB\FCB 773 -EN-.pdf
2/10 2009-02-05
Introduction
Overview This is the service manual for the Free cooling box FCB 773 with air inlet in one of the
sides, optional which. It is equipped with a compact F5-filter and two economic high
flow axial fans.
Table of content Free Cooling Box FCB 773......................................................................... 1
Introduction ................................................................................................. 2
General information – Free Cooling Box FCB 773 ..................................... 3
Technical data ............................................................................................ 4
Dimensions ................................................................................................. 6
Flow illustration ........................................................................................... 7
Wiring diagram ........................................................................................... 8
Preventive maintenance ............................................................................. 9
Spare parts list.......................................................................................... 10
Contact In the table below you can see how to contact the manufacturer and sales offices.
Office Sweden Norway Denmark
Name Kontrollelektronik
Dantherm Air Handling AB
A/S Dantherm avd.
Kontrollelektronik
Dantherm Air Handling A/S
Address Virkesgatan 5 Postboks 147 /
Storgatan 29
Marienlystvej 65
SE-614 31 Söderköping
Sweden
NO-1851 Mysen
Norway
DK-7800 Skive
Denmark
Phone +46 (0)121 130 40 +47 69 89 37 67 +45 96 14 37 00
Fax +46 (0)121 133 70 +47 69 89 47 35 +45 96 14 38 20
Web kontrollelektronik.com www.dantherm.no www.dantherm-air-handling.com

U:\Manuals\FCB\FCB 773 -EN-.pdf
3/10 2009-02-05
General information – Free Cooling Box FCB 773
Introduction This section gives you the general information about the unit and this service manual.
Target group The target group of this service manual is the technicians who install and maintain the
unit.
Copyright Copying of this service manual, or part of it, is not allowed without written permission
from Kontrollelektronik Dantherm Air Handling AB.
Reservations The service manual is subject to changes without notice.
CE - Declaration of
Conformity
- FCB 773
Kontrollelektronik Dantherm Air Handling AB, Virkesgatan 5, SE-614 31 Söderköping
hereby declare that the unit are in conformity with the following directives:
2006/95/EG Low Voltage Directive including 93/68/EEC where required
86/336 EEC EMC Directive including 92/31/EEC and 93/68/EEC
89/392 EEC Machine Directive
The product is manufactured according to SS-EN 604 39-1
The product is manufactured with components which follow the application standards
for Low Voltage Directive and in case of norms for EMC in EU countries.
The product is controlled and tested before delivery according to the following:
Real test of built in functions with connected temperature sensors and
damper actuators.
Inspection of labeling and marking.
Ocular inspection of mounted materials and electrical connections.
Inspection that all parameter and settings are set to delivery position.
Recycling The unit is designed to last for many years. When the time comes for the unit to be
recycled, the unit should be recycled according to national rules and producers to
protect the environment.

U:\Manuals\FCB\FCB 773 -EN-.pdf
4/10 2009-02-05
Technical data
Free Cooling
Performance The table below shows the performance of the Free cooling unit:
Specification 48V DC 230V AC
Air flow 622 l/s (2240 m
3
/h) 622 l/s (2240 m
3
/h)
Free cooling capacity 746 W/°C 746 W/°C
Free cooling capacity at Δt=7°C 5,2 kW 5,2 kW
Power consumption 280 W 275 W
Sound pressure at 3m from shelter Approx. 40dBA Approx. 40dBA
External available pressure drop 50 Pa 50 Pa
Cabinet data Data of the cabinet are shown in the following table:
Specification Designation Value
Weight Controller included 25 kg
Metal sheet material Aluzinc AZ150 1,0-1,5 mm
Fan motor data Data of the fan motor is shown in the following table:
Specification 48V DC 230V AC
Voltage nominal 48V DC 230V AC
Current 5,2 A 1,12 A
Power consumption 278 W (@53V DC) 270 W
Speed 2600 rpm 1100 rpm
Continued overleaf

U:\Manuals\FCB\FCB 773 -EN-.pdf
5/10 2009-02-05
Technical data, continued
Filter data In the table below the data of the filter are specified:
Specification Compact filter
Type Compact filter
Removal efficiency F5
Dimensions 670 x 295 x 70
Total Area 4,3 m
2
Filter monitor setting 85 Pa (at 6V DC signal)
Controlling The table below show the components and types for controlling of the Free cooling unit:
Specification 48V DC 230V AC
Control unit BCT 48
(See separate manual)
Indoor temperature sensor RTT-1
Filter monitor JDW5

U:\Manuals\FCB\FCB 773 -EN-.pdf
6/10 2009-02-05
Dimensions
Illustration This drawing illustrates the dimensions of the Free cooling unit:
Side
Front

U:\Manuals\FCB\FCB 773 -EN-.pdf
7/10 2009-02-05
Flow illustration
Flow The picture below schematically shows the air flow.
Default inletAlternative inlet

U:\Manuals\FCB\FCB 773 -EN-.pdf
8/10 2009-02-05
Wiring diagram
+48
+48
-48
-48
Y1-2
Tc1
Tc2
RT
COM
FA1
FA2
PA1
+ Brown
- Blue
3
4
5
6
7
Brown
White
Blue
White
Green
+
-
Tc
0-10V
+
-
Tc
0-10V
1
2
6
5
Green
1
3
t
2
Fan alarm
output
Brown
White
BCT 48
0%
100%
Room termostat
Fans
Main supply
48VDC
BCT 48 090120
PA2
Violet
Power alarm
output
NC
NO
NO
NC
J2
J1
2
1
Violet
Green
White
Blue
7
4
3
2x1,5
7x1
2x0,5
1x4x0,5

U:\Manuals\FCB\FCB 773 -EN-.pdf
9/10 2009-02-05
Preventive maintenance
Introduction The unit needs preventive maintenance with specific intervals to avoid breakdown or
inefficient operation. It is important to notice that interval between maintenance can
vary depending on the specific environment.
Caution! Switch off all power to the unit before working on the unit!
Make sure that all work has been performed before switching on the power again.
Interval Kontrollelektronik Dantherm Air Handling AB recommends that intervals between
preventive maintenance do not exceed 1 year. It is also our recommendation that the
site and unit is examined closely during the first preventive maintenance to determine
whether the interval is too long. We recommend that preventive maintenance visits are
planned to occur in springtime.
Condition for
warranty The factory warranty is only valid if documented preventive maintenance has been
carried out with an interval of maximum 1 year. The documentation could be in form of
a written log.
Recommended
approach The recommended approach when performing a preventive maintenance visit is:
Step Action
1 Make sure that the power to the unit is safely switched off.
2 Remove the worn-out filter and clean the unit carefully.
3 Clean the dampers and check them regarding function and tightness.
4 Clean the fan and check its mounting.
5 Check and clean the air intake and exhaust accessories.
6 Insert the new filter carefully into the unit.
7 Close the unit and make sure that the service is completed correctly.
8 Turn on the power to the unit.
Function tests Fan and filter alarm function tests can be done by the following actions.
Function test Action
Filter Open the service door and put a plate of carton or similar on the
intake side of the filter, blocking a big part of the filter area. Close the
service door, run the free cooling unit and check that filter alarm is
given. Stop and remove the plate.
Fan Open the lid to the controlling unit and remove one of the cables
connected to the connector marked “Tc1” or “Tc2”. Close the lid, run
the free cooling unit and check that fan alarm is given. Restore the
controller.

U:\Manuals\FCB\FCB 773 -EN-.pdf
10/10 2009-02-05
Spare parts list
List Below are the complete list of spare parts with part numbers:
Spare part Type Part number
Compact filter F5, 670 x 295 x 70 mm 900-07633417
Fan 48V DC W1G250-HH67-52, 48 V DC 023-92184831
Fan 230V AC W2E250-HL06-01, 230V AC 023-92184844
Control Unit 48V DC BCT 48 500-24771619
Indoor temp. sensor RTT-1 889-350203
Filter monitor JDW5 021-422314
Contact In the table below you can see how to contact the manufacturer and sales offices.
Office Sweden Norway Denmark
Name Kontrollelektronik
Dantherm Air Handling AB
A/S Dantherm avd.
Kontrollelektronik
Dantherm Air Handling A/S
Address Virkesgatan 5 Postboks 147 /
Storgatan 29
Marienlystvej 65
SE-614 31 Söderköping
Sweden
NO-1851 Mysen
Norway
DK-7800 Skive
Denmark
Phone +46 (0)121 130 40 +47 69 89 37 67 +45 96 14 37 00
Fax +46 (0)121 133 70 +47 69 89 47 35 +45 96 14 38 20
Web kontrollelektronik.com www.dantherm.no www.dantherm-air-handling.com