Data Aire DAP III User manual

Data Aire DAPTM III
BACnet Integration Instructions
Data Aire, Inc.
230 West BlueRidge Avenue
Orange, California 92865
800-347-2473
714-921-6000
www.dataaire.com
Engineering Document Number 600-000-460
April 2009
Revision 2.0

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 2 of 13
Table of Contents
1Overview.....................................................................................................3
2Hardware Requirements and Installation............................................3
2.1 Required Network Card........................................................................3
2.1.1 The BACnet MS/TP protocol interface . ...................................................3
2.1.2 The BACnet IP protocol interface............................................................3
2.2 Network Card Installation ....................................................................4
2.2.1 For BACnet MS/TP interface ..................................................................4
2.2.2 For BACnet/IP interface .........................................................................5
2.3 Network Wiring .....................................................................................5
2.3.1 For RS-485 Multidrop network connection ...............................................5
2.3.2 For the Ethernet connection ...................................................................6
3Communication Port Setting...................................................................6
3.1 The RS-485 communication Port............................................................6
3.2 For BACnet/IP communication UDP port................................................6
4BACnet Object Definitions......................................................................7
4.1 Binary Value Objects............................................................................7
4.1.1 Readable fields................................................................................7
4.1.2 Object List .......................................................................................7
4.2 Analog Input Objects..........................................................................10
4.2.1 Readable fields..............................................................................10
4.2.2 Object List .....................................................................................10
4.3 Analog Value Objects.........................................................................10
4.3.1 Readable fields..............................................................................10
4.3.2 Object List .....................................................................................11
4.4 Multi-State Value Objects...................................................................13
4.4.1 Readable fields..............................................................................13
4.4.2 Object List .....................................................................................13
4.5 References..........................................................................................13

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 3 of 13
1 Overview
The DAP III control panel supports a BACnet communication with a BMS for the system
monitoring and control. This document describes all the requirements and configuration
steps to implement the interface with a DAP III panel using the BACnet MS/TP and
Bacnet IP protocol.
2 Hardware Requirements and Installation
2.1 Required Network Card
2.1.1 The BACnet MS/TP protocol interface requires a Data Aire RS-485 Multidrop
communication network card to be installed into the DAP III Display board.
The RS-485 Multidrop card part number is 160-400-383.
Figure 1: Data Aire RS-485 Multidrop Communications Network card
2.1.2 The BACnet IP protocol interface requires a Data Aire Ethernet network card to
be installed into the DAP III Display board. The Ethernet card part number is
160-400-385. This card is compliant with IEEE 802.3/802.3u 100BaseTX
Ethernet standard and auto-negotiation at 10Mbps/ 100 Mbps.
Figure 2: Data Aire Ethernet Communications Network card
BOARD CONNECTOR
RJ-45 CONNECTOR
END JUMPERTEST JUMPER
BOARD CONNECTOR

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 4 of 13
2.2 Network Card Installation
IMPORTANT NOTE: The DAP III panel supports one network connection at a
time therefore only one type of the network card can be
installed.
2.2.1 For BACnet MS/TP interface, plug an RS-485 Multidrop communication network
card to the Communication Header J1 of the DAP III Display board. Make sure
the End jumper is on “T” (Terminate) position if the installed unit is the last unit in
the communication loop. In some case, the End jumper may not be required,
check with the BMS manufacturer for the requirement of this End jumper. See
Figure 3 below for the DAP III Display board with an RS-485 Multidrop card
installed.
After installing the network card, go to Menu 6-1 – Unit & Network ID in Group
Menu 6 – Network to set the unit network ID number. Go to Menu 6-2 –Network
Protocol to configure or verify the network protocol. Menu 6-2 to 6-7 are locked
menus, refer to the DAP III Operation Manual for the procedure of how to unlock
these menus before enter values. It is recommended to reset the DAP III panel
after changing the network protocol or the unit ID number.
+
_
Figure 3: DAP III Display Board With an RS-485 Multidrop Network Card
Communication Header J1Tx and Rx LED
Shield RS-485 Communication Wirin
g
RS-485 Multidro
p
Communication

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 5 of 13
2.2.2 For BACnet IP interface, connect an Ethernet Communications network card to
the Communication Header J1 of the DAP III Display board. See Figure 4 for the
DAP III Display board with an Ethernet card installed.
After installing the network card, go to menu 6-1 – Unit and Network ID in Group
menu 6 to set the unit network ID and to menu 6-2 –Network protocol to
configure the network protocol. Menu 6-2 to 6-7 are locked menus, refer to the
DAP III Operation Manual for the procedure of how to unlock these menus before
entering IP address. It is recommended to reset the DAP III panel after changing
the network protocol or the unit ID number.
Figure 4: DAP III Display Board With an Ethernet Communications Network Card
2.3 Network Wiring
2.3.1 For RS-485 Multidrop network connection, the 18 AWG or 22 AWG shielded,
twisted pair cable is recommended. The network wiring should be wired in the
multidrop fashion: The RS-485 devices are wired in parallel. The wiring should
start from the RS-485 port of the BMS Gateway module. See Figure 3 above for
the DAP III RS-485 network wiring terminations.
Communication Header
J1
RJ-45 Connector with Link
and Activity LED Ethernet Communication Card
Gateway
DAP III Display board of unit
#1 with RS-485 Multidrop card
(Supplied by Data Aire.)
DAP III Display Board of unit
#2 with RS-485 Multidrop card
(Supplied by Data Aire)
RS-485 Modbus Gateway
module (Supplied by BMS
Twisted-pair Multidrop connection to Gateway module Wiring to
next unit
BMS Computer

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 6 of 13
2.3.2 For the Ethernet connection, use the CAT-5 Ethernet cable. The DAP III panel
should be connected to the same network with the BMS by a network switch or a
network hub. Each unit requires having a dedicated IP address. Consult with
the building IT personnel or building network administrator on IP addressing.
3 Communication Port Setting
3.1 The RS-485 communication Port for BACnet MS/TP protocol is configured as
follow:
3.2 For BACnet IP communication UDP port setting, refer to the DAP III Operation
Manual for the procedure to enter an IP address and port setting to the DAP III.
The BACnet/IP UDP port (Listen port) in the DAP III is default to 47808.
Baud Rate 9600 (adjustable)
Word Length 8
Parity None
Stop Bits 1
Network switch or
hub (Supplied by
others)
DAP III Display board of unit
#1 with Ethernet card
(Supplied by Data Aire.)
DAP III Display board of unit
#2 with Ethernet card
(Supplied by Data Aire.)
Ethernet connection to BMS
BMS
computer

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 7 of 13
4 BACnet Object Definitions
4.1 Binary Value Objects
4.1.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value
4.1.2 Object List
Object Name Instance
No. BV Object Description Present-
Value
Writeable
Dehumidification 1 Unit is dehumidifying
No
Humidification 2 Unit is humidifying
No
Energy Saver 3 Energy Saver function is active
No
Cooling Held 4 Cooling is inhibited
No
Heating Held 5 Heating is inhibited
No
Humidification Held 6 Humidification is inhibited
No
Dehumidification Held 7 Dehumidification is inhibited
No
Reheat During Dehumidification 8 Reheat on during dehumidification
No
Water Under Floor 9 Water Under Floor detection alarm
No
No Air Flow 10 Loss of the air flow alarm
No
Dirty Filter 11 Filter clogged alarm
No
Humidifier Problem 12 Loss of the humidifier make-up water
pressure alarm No
Low Voltage Warning 13 DC power of the DAP III boards drops
below the required level No
Fire-Stat Trip 14 The return air temperature rises above
the Firestat temperature setting limit No
Compressor Short Cycle Warning 15 Compressor short cycle warning is active
No
Power Problem 16 Power reset or unit restart notification
No
Humidity Sensor Problem 17 Faulty Humidity sensor detected
No

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 8 of 13
Object Name Instance
No. BV Object Description Present-
Value
Writeable
Temperature Sensor Problem 18 Faulty Return Air temperature sensor
detected No
Maintenance Due 19 The blower runtime has elapsed the
scheduled maintenance hours No
High Pressure / Internal
Overload: Compressor 1 20 Compressor #1 high pressure switch or
compressor internal overload relay trips No
Low Pressure C1 21 Compressor #1 low pressure switch
opens No
High Pressure C2/ Internal
Overload: Compressor 2 22 Compressor #2 high pressure switch or
compressor internal overload relay trips No
Low Pressure C2 23 Compressor #2 low pressure switch
opens No
Smoke Detector
(Optional) 24 Smoke Detected, unit shutdown. An
optional smoke detector required No
No Water Flow
(Optional) 25 Loss of water on calling for cooling, An
optional Water Flow switch required. No
Discharge Air Sensor Problem
(Optional) 26 Faulty Discharge Air temperature sensor
detected. An optional temperature
required
No
High Temperature Warning 27 The Return Air temperature rises above
the high temperature alarm limit setting No
Low Temperature Warning 28 The Return Air temperature drops below
the low temperature alarm limit setting No
High Humidity Warning 29 The Relative humidity rises above the
high humidity alarm limit setting No
Low Humidity Warning 30 The Relative humidity drops below the
low humidity alarm limit setting No
Fan Motor Overload
(Optional) 31 The optional fan motor overload trips. No
Local Alarm 1 (Optional) 32 The optional alarm input 1 is
programmed to Local alarm #1: See tag
inside door and the alarm signal is active
No
Local Alarm 2 (Optional) 33 The optional alarm input 2 is
programmed to Local alarm #2: See tag
inside door and the alarm signal is active
No
Local Alarm 3 (Optional) 34 The optional alarm input 3 is
programmed to Local alarm #3: See tag
inside door and the alarm signal is active
No
Local Alarm 4 (Optional) 35 The optional alarm input 4 is
programmed to Local alarm #4: See tag
inside door and the alarm signal is active
No
Standby Pump On
(Optional) 36 The optional alarm input is programmed
to Standby pump on: Check primary
pump and the alarm signal is active
No
UPS Power On
(Optional) 37 The optional alarm input is programmed
to UPS power on: Check main power
supply and the alarm signal is active
No
Custom Alarm 1
(Optional) 38 The optional alarm input 1 is
programmed to Custom alarm #1 and the
alarm signal is active
No

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 9 of 13
Object Name Instance
No. BV Object Description Present-
Value
Writeable
Custom Alarm 2
(Optional) 39 The optional alarm input 2 is
programmed to Custom alarm #2 and the
alarm signal is active
No
Custom Alarm 3
(Optional) 40 The optional alarm input 3 is
programmed to Custom alarm #3 and the
alarm signal is active
No
Custom Alarm 4
(Optional) 41 The optional alarm input 4 is
programmed to Custom alarm #4 and the
alarm signal is active
No
Humidification Inhibited
(optional) 42 The optional inputs are programmed to
Humidification inhibited and the input
signal is active
No
Reheat Inhibited
(Optional) 43 The optional inputs are programmed to
Reheat inhibited and the input signal is
active
No
Reheat And Humid. Inhibited
(Optional) 44 The optional inputs are programmed to
Reheat and Humidification inhibited and
the input signal is active
No
Low Discharge Air Temperature
Alarm
(Optional)
45 The Discharge Air temperature drops
below the low discharge temperature
setting limit. An optional Discharge Air
temperature sensor required
No
Manual Override 46 Manual override switches are on; unit
operates in the manual control mode. No
High Condensate water level
(Optional) 47 High condensate water level switch of
the optional condensate pump closes.
This is a standard alarm on ceiling units.
No
Unit In Standby, All Functions
Held Off Alarm (Optional) 48 The optional alarm input 1 is
programmed to Unit in standby, all
functions held off and the alarm signal is
active. Unit is put to standby mode.
No
Cooling Inhibit 1001 The Cooling stages will be inhibited
when this point is on. Yes-
Enumerated
(0,1)
Heating Inhibit 1002 The Heating stages will be inhibited
when this point is on Yes-
Enumerated
(0,1)
Humidification Inhibit 1003 The Humidification function will be
inhibited if this point is on Yes-
Enumerated
(0,1)
Dehumidification Inhibit 1004 The dehumidification function will be
inhibited if this point is on. Yes-
Enumerated
(0,1)
Blower Inhibit 1005 The blower(s) will stop if this point is
on. In a normal circumstance, this point
should be off at all time
Yes-
Enumerated
(0,1)

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 10 of 13
4.2 Analog Input Objects
4.2.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Units
4.2.2 Object List
Object Name Instance
No. AI Object Name Present-
Value
Writeable
Return Air Temperature 1 Current Return Air temperature
No
Relative Humidity 2 Current Relative humidity
No
Discharge Air Temperature 3 Current Discharge Air temperature. This
temperature is only available when an
optional Discharge Air sensor is installed
No
Chilled Water Temperature
(Optional) 4 Chilled Water temperature. This
temperature is only available when an
optional Chilled water sensor is installed.
No
Analog Input 1 Sensor
(Optional) 5 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 1
No
Analog Input 2 Sensor
(Optional) 6 An optional analog sensor such as
temperature transmitter must be installed
and programmed into analog module
input 2.
No
Analog Input 3 Sensor
(Optional) 7 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 3
No
Analog Input 4 Sensor
(Optional) 8 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 4
No
4.3 Analog Value Objects
4.3.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Units

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 11 of 13
4.3.2 Object List
Object Name Instance
No. AV Object Description Present-
Value
Writeable
Cooling Stages On 1 Cooling stages are currently on (0-5).
This point only applies to DX unit No
Heating Stages On 2 Heating stages are currently on (0-4)
No
Chilled Water Valve Open
Percentage 3 Chilled Water valve open percentage
(0-100%). This point only applies to
chilled water unit.
No
Humidifier Valve
(Optional) 4 Humidifier valve open percentage (0-
100). This point only applies to unit
that has an optional modulating
humidifier
No
High Temperature In The Last
24Hrs. 5 Maximum value of the Return Air
temperature in the last 24 hours No
Low Temperature In The last 24Hrs. 6 Minimum value of the Return Air
temperature in the last 24 hours No
High Humidity In The last 24Hrs. 7 Maximum value of the Relative
humidity in the last 24 hours No
Low Humidity In The Last 24Hrs. 8 Minimum value of the Relative
humidity in the last 24 hours No
Cooling Utilization 9 Cooling Utilization of the last hour
(0-100 percent). This applies to DX
unit only
No
Heating Utilization 10 Heating utilization of the last hour
(0-100 percent) No
Chilled Water Utilization 11 Chilled Water valve utilization of the
last hour (0-100 percent). This
applies to unit with Chilled water
unit only
No
Humidifier Utilization 12 Humidifier utilization of the last hour
(0-100 percent) No
Compressor 1 Runtime 13 The total runtime of the compressor
#1 (Hour) No
Compressor 2 Runtime 14 The total runtime of the compressor
#2 (Hour) No
Compressor 3 Runtime 15 The total runtime of the compressor
#3 (Hour) No
Compressor 4 Runtime 16 The total runtime of the compressor
#4 (Hour) No
Heat Stage 1 Runtime 17 The total runtime of the heating stage
#1 (Hour) No
Heat Stage 2 Runtime 18 The total runtime of the heating stage
#2 (Hour) No
Heat Stage 3 Runtime 19 The total runtime of the heating stage
#3 (Hour) No
Humidifier Runtime 20 The total runtime of the humidifier
(Hour) No

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 12 of 13
Object Name Instance
No. AV Object Description Present-
Value
Writeable
Blower Runtime 21 The total runtime of the blower
motor(s) (Hour) No
Condenser Runtime 22 The total runtime of the condenser.
This will be available when the
optional Relay module is installed
No
Dehumidification Runtime 23 The total runtime of dehumidification
No
Energy Saver Runtime
(Optional) 24 The total runtime of the energy saver
chilled water valve. This applies to
the DX unit with energy saver
cooling only.
No
Chilled Water Runtime 25 The total runtime of the chilled water
valve. This point applies to chilled
water unit only
No
Analog Output 1
(Optional) 37 Optional analog output 1 Value No
Analog Output 2
(Optional) 38 Optional analog output 2 Value No
Fire stat Temperature Limit 1001 Fire stat temperature limit setting
(100-150F) – Default 100 F Yes-Real
value
High Humidity Limit 1002 High humidity alarm Limit setting
(10-90%). Default: 60 % Yes- Real
value
High Temperature Limit 1003 High temperature alarm Limit setting
(50-90F). Default: 80 F Yes- Real
value
Humidity Deadband 1004 Humidity deadband (0-15%).
Default: 3% Yes- Real
value
Low Discharge Air Temperature
Limit (optional) 1005 Low Discharge Air temperature
alarm Limit setting (45-61F). This
requires an optional Discharge Air
temperature sensor. Default: 52 F
Yes- Real
value
Low Humidity Limit 1006 Low humidity alarm limit setting
(10-90%). Default: 40% Yes- Real
value
Low Temperature Limit 1007 Low Return Air temperature alarm
Limit setting (50-90F). Default: 60F Yes- Real
value
Chilled Water Available Limit
(Optional) 1008 Chilled Water available setpoint (40-
60F). Default: 50 F. This applies to
unit that has an energy saver or
auxiliary chilled water coil.
Yes- Real
value
Humidity Setpoint 1009 Humidity setpoint (30-70%).
Default: 50% Yes- Real
value
Unit Start Delay 1010 Unit start time delay setting (5-600
seconds). Default: 5 seconds Yes- Real
value
Temperature Deadband 1011 Temperature deadband (1-5F).
Default: 2F Yes- Real
value
Temperature Setpoint 1012 Temperature setpoint (65-85F).
Default: 72F Yes-Real
value
Fan Speed Control
(Optional) 1013 Optional fan speed control setting
(85-100%). Default: 100%. This
option requires an Analog module.
Yes- Real
value

Data Aire, Inc. DAPTM III BACnet Integration Instructions
Engineering Document - 600-000-460 Page 13 of 13
4.4 Multi-State Value Objects
4.4.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Number-of-states
4.4.2 Object List
Object Name Instance
# MSV Object Description Present-
value
Writeable
Person To Contact
(Optional) 13 Information of the person to contact
on the alarm event. This requires a
factory-preprogrammed message.
No
Reset Mode Warning 14 Loss of power or Unit restart warning
message No
Water Under Floor Alarm Action 17 Water under floor alarm action
setting, menu 4-9 of the DAP III
panel. This can be set to unit
shutdown or compressor lock-out
No
No Water Flow Alarm Action
(optional) 18 No water flow alarm action setting,
menu 4-10 of the DAP III panel. This
can be set to compressor lock-out or
none. This requires an optional water
flow sensor.
No
Energy saver Lockout Time
(optional) 19 Energy saver lockout time delay once
the DX cooling comes on. This is set
on menu 3-8 of the DAP III panel.
Energy saver option required
No
Auto flush Timer
(Optional) 1001 Auto flush Timer setting. This setting
only applies when an optional
Infrared humidifier is used.
Yes-
Unsigned
value
Unit on/off Control 1002 This point controls the unit on/off.
The default setting value is 1; unit is
ON. Changing the setting value to 2
will turn the unit OFF. Default =1
(ON).
Yes-
Unsigned
value
4.5 References
ANSI/ASHRAE Standard 135-2001, BACnet - A Data Communication Protocol
for Building Automation and Control Networks
Other manuals for DAP III
2
Table of contents
Other Data Aire Control Panel manuals
Popular Control Panel manuals by other brands

Motorline professional
Motorline professional MC50 User& installer's manual

Aritech
Aritech 1X-F Series Quick installation guide

JCM Technologies
JCM Technologies INTEGRA user manual

Eminent
Eminent e-Domotica e-Centre 2 manual

Johnson Controls
Johnson Controls S1-TTSCC01 User's information manual

OERTLI
OERTLI OEtroCom-2 technical information