BE- IT2698 1/4 ITOE0236-en
Technical Information
OEtroCom-2, OEtroCom-3, OEtroCom-Easy
Control panels
Remplace, remove or add an electronic PCB
Troubleshooting
JS N° ITOE0236-en 29/09/2020
1. Make a PCB autodetection
Autodetection allows the identification of the electronic PCBs which are on the appliance and
the correct operation of the system.
Perform an autodetection in the following cases:
- Replacing an electronic PCB on a device
- Removing or adding a PCB to a device
- Cascade: replacing, removing or adding an electronic PCB on one of the devices.
- One of the following error codes appears: H02.02, H02.03, H02.36, H02.37, H02.45,
H02.46,…
2. On OEtroCom-2 control panel
1. If an error code is displayed: clear the error by pressing the RESET key,
2. Press the 2 right-hand keys to access the Installer Menu,
3. Enter the code 0012
4. If more than one electronic PCB is displayed: select the main PCB:
- EHC-…
- CU-GH-…
- CU-OH-…
- EEC…
5. Validate
6. Select autodetection parameter AD (at the end of the parameter list) and confirm .
- The autodetection is carried out,
- The main screen is displayed again when the automatic detection is complete.
- The mounted electronic PCBs are visible in the different menus.