Datakom DKM-405 User manual

K30D01-EN - 1 - Version 1.5
http://www.datakom.com.tr
Tel: +90-216 466 84 60
Fax: +90-216 364 65 65
DKM-405 NETWORK ANALYSER
WITH TOTAL HARMONIC DISTORTION DISPLAY
INTRODUCTION
The DKM-405 is a low cost precision
instrument designed to display various AC
parameters in a 3-phase distribution panel.
The standard unit is designed for 230/400V
network. A different version is available for
120/208V systems.
The harmonic analysis is available for up to
31 harmonics. THD values of both voltage
and current inputs are available.
The optional digital input accepts both AC
and DC signals and has programmable
functions.
The optional relay output is programmable.
Relay function is selected through a list.
The unit fits into a standard 92x92mm panel
opening.
FEATURES
True RMS measurements
Total harmonic distortion display
Max demand display
Configurable relay output
Energy pulse output capability
Optically isolated, configurable digital input
Active-reactive power counters
Hour counter
Voltage transformer ratio for MV applications
Front panel programming
Reduced panel depth
Wide operating temperature range
Sealed front panel (IP54)
Plug-in connection system

K30D01-EN - 2 - Version 1.5
SAFETY NOTICE
Failure to follow below instructions will
result in death or serious injury
•
Electrical equipment should be installed only by qualified
specialist. No responsibility is assured by the
manufacturer or any of its subsidiaries for any
consequences resulting from the non-compliance to
these instructions.
•
Check the unit for cracks and damages due to
transportation. Do not install damaged equipment.
•Do not open the unit. There is no serviceable parts inside.
•
Fuses must be connected to the power supply and phase
voltage inputs, in close proximity of the unit.
•
Fuses must be of fast type (FF) with a maximum rating of
6A.
•
Disconnect all power before working on equipment.
•
When the unit is connected to the network do not touch
terminals.
•
Short circuit terminals of unused current transformers.
•
Any electrical parameter applied to the device must be in
the range specified in the user manual.
•
Do not try to clean the device with solvent or the like.
Only clean with a dry cloth.
•
Verify correct terminal connections before applying
power.
•
Only for front panel mounting.
Current Transformers must be used for current
measurement.
No direct connection allowed.

K30D01-EN - 3 - Version 1.5
TABLE OF CONTENTS
Section
1. INSTALLATION
1.1. FRONT / REAR PANELS
1.2. MECHANICAL INSTALLATIO
1.3. ELECTRICAL INSTALLATION
1.4. CONNECTION DIAGRAM
2. PUSHBUTTON FUNCTIONS
3. DISPLAY NAVIGATION
4. DEVICE CONFIGURATION
4.1. INTRODUCTION
4.2. RESETTING DEMAND VALUES
4.3. RESETTING ENERGY COUNTERS
4.4. RESETTING THE HOUR COUNTER
4.5. RESETTING ALARMS
4.6. SETTING THE DEFAULT SCREEN
4.7. SETTING THE CURRENT TRANSFORMER RATIO
4.8. SETTING THE VOLTAGE TRANSFORMER RATIO
4.9. SETTING HIGH AND LOW VOLTAGE LIMITS
4.10. SETTING HIGH AND LOW FREQUENCY LIMITS
4.11. SETTING THE OVERCURRENT LIMIT
4.12. SETTING HIGH AND LOW ACTIVE POWER LIMITS
4.13. SETTING HIGH AND LOW REACTIVE POWER LIMITS
4.14. SETTING HIGH AND LOW POWER FACTOR LIMITS
4.15. CONFIGURING THE DIGITAL INPUT
4.16. CONFIGURING THE RELAY OUTPUT
4.17. DISPLAYING THE FIRMWARE VERSION
4.18. CALIBRATION
4.19. LAMP TEST
5. TECHNICAL SPECIFICATIONS

K30D01-EN - 4 - Version 1.5
1. INSTALLATION
Before installation:
•Read the user manual carefully, determine the correct connection diagram.
•Remove all connectors and mounting brackets from the unit, then pass the unit through
the mounting opening.
•Put mounting brackets and tighten. Do not tighten too much, this can brake the
enclosure.
•Make electrical connections with plugs removed from sockets, then place plugs to their
sockets.
•Note that the power supply terminal is separated from measurement terminals.
Below conditions may damage the device:
•Incorrect connections.
•Incorrect power supply voltage.
•Voltage at measuring terminals beyond specified range.
•Current at measuring terminals beyond specified range.
•Connecting or removing data terminals when the unit is powered-up.
•Overload or short circuit at relay outputs
•Voltage applied to digital inputs over specified range.
•High voltage applied to communication port.
Current Transformers must be used for current
measurement.
No direct connection allowed.
Below conditions may cause abnormal operation:
•Power supply voltage below minimum acceptable level.
•Power supply frequency out of specified limits
•Phase order of voltage inputs not correct.
•Current transformers not matching related phases.
•Current transformer polarity incorrect.

K30D01-EN - 5 - Version 1.5
1.1 FRONT / REAR PANELS
1.2 MECHANICAL INSTALLATION
Panel Cutout Required Panel Depth

K30D01-EN - 6 - Version 1.5
1.3 ELECTRICAL INSTALLATION
Do not install the unit close to high electromagnetic noise
emitting devices like contactors, high current busbars,
switchmode power supplies and the like.
Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and data communication quality.
•ALWAYS remove plug connectors when inserting wires with a screwdriver.
•Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
•Fuses must be of fast type (FF) with a maximum rating of 6A.
•Use cables of appropriate temperature range.
•Use adequate cable section, at least 0.75mm
2
(AWG18).
•For current transformer inputs, use at least 1.5mm
2
section (AWG15) cable.
•The current transformer cable length should not exceed 1.5 meters. If longer
cable is used, increase the cable section proportionally.
•Follow national rules for electrical installation.
•Current transformers must have 5A output.
Current Transformers must be used for current
measurement.
No direct connection allowed.

K30D01-EN - 7 - Version 1.5
1.4 CONNECTION DIAGRAM

K30D01-EN - 8 - Version 1.5
2. PUSHBUTTON FUNCTIONS
Three buttons on the front panel provide access to configuration and measurement
screens.
BUTTON FUNCTION
Selects display context
•THD display
•Minimum values display
•Maximum values display
•Demand display
•If all leds are off then actual measurements
display.
HELD PRESSED FOR 5 SEC:
resets min-max values and displays minimum phase-
to-neutral voltages.
Upper screen
or
Increase related value (configuration mode)
Lower screen
or
Decrease related value (configuration mode)
HELD PRESSED TOGETHER FOR 2 SEC:
Enters configuration mode.
IF NO BUTTON PRESSED FOR 5 MINUTES:
returns to the main display screen

K30D01-EN - 9 - Version 1.5
3. DISPLAY NAVIGATION
The button will select the display context and buttons will navigate between
possible values of this context.
Phase indication leds will reflect the phase displayed on the screen.
Phase status leds will turn-on if the related phase voltage is above 70 volts.
Relay led will turn-on when the relay output is active.
Kilo leds will turn on if the displayed value is in kA/kV/kW/kVA/kVAr.
Sigma led will turn on when displaying total values.
V / Hz leds will turn-on when the displayed value is in volts or hertz.
Display of currents: If the CT ratio is below 200/5 then currents will be displayed with
0.1A precision. If the CT ratio is between 200/5 and 2000/5 then currents are displayed
with 1A precision. If the CT ratio is above 2000/5 then currents are displayed with 0.01 kA
precision and the “k” led will turn on.
Display of voltages: If the VT ratio is above 100.0/1 then voltages will be displayed with
0.1kV precision. If the VT ratio is between 100.0/1 and 20.0/1 then voltages will be
displayed with 0.01kV precision. In both cases the “k” led will turn on. If the VT ratio is
below 20.0/1 then voltages are directly displayed with 1V precision.
Display of kW, kVA, kVAr: If the product CTxVT is below 1000 then the values will be
displayed with 0.1k precision. Otherwise they will be displayed with 1k precision.
Display of kWh, kVArh, Hours: Values are displayed with a precision of 0.1 k (or hour).

K30D01-EN - 10 - Version 1.5
4. DEVICE CONFIGURATION
4.1. INTRODUCTION
In order to offer the maximum flexibility to the user, the unit has several configurable
parameters.
•Device Configuration
Default display configuration
•Measurement Configurations
Resetting Demand Values
Clearing Counters
Resetting Alarms
Setting the CT ratio
Setting the VT ratio
Setting alarm limits
•Input / Output Configuration
Input Configuration
Relay Configuration
•Device Calibration
In order to enter the configuration menu,
hold both MENU buttons pressed for 2 seconds.
In order to exit the configuration menu,
hold both MENU buttons pressed for 2 seconds.
If no button is pressed, the unit will automatically
close the configuration menu after 1 minute.
Parameter values are increased / decreased with
MENU buttons. Holding the button pressed will
increase / decrease with larger steps.
Pressing the SET button will save the current
parameter and display the next parameter.
Holding the SET button pressed for 2 seconds will
display the previous parameter.

K30D01-EN - 11 - Version 1.5
4.2. RESETTING DEMAND VALUES
SET
MENU
MENU
PGM
dEnd
CLR
0
Parameter value:
0: No action
1: Reset Demand values
Setting this parameter to 1 will reset demand
values.
The parameter value is not stored into
memory and reads always 0.
4.3. RESETTING ENERGY COUNTERS
SET
MENU
MENU
PGM
eNGy
cLr
0
Parameter value:
0: No action
1: Reset kWh and kVArh counters
Setting this parameter to 1 will reset
powermeter counters.
The parameter value is not stored into
memory and reads always 0.

K30D01-EN - 12 - Version 1.5
4.4. RESETTING THE HOUR COUNTER
SET
MENU
MENU
PGM
hovr
cLr
0
Parameter value:
0: No action
1: Reset hour counter
Setting this parameter to 1 will reset the
hour counter.
The parameter value is not stored into
memory and reads always 0.
4.5. RESETTING ALARMS
SET
MENU
MENU
PGM
ALAR
CLR
0
Parameter value:
0: No action
1: Reset alarms
Setting this parameter to 1 will reset
existing alarms.
The parameter value is not stored into
memory and reads always 0.

K30D01-EN - 13 - Version 1.5
4.6. SETTING THE DEFAULT SCREEN
SET
MENU
MENU
PGM
disp
seL
0
This parameter selects the default screen
that the unit returns 5 minutes after any key
is pressed.
Setting this parameter to 0 will cancel the
default screen.
Param.
value
Upper
displays
Lower display
0 no change no change
1 Voltages L-N Frequency
2 Voltages L-L Frequency
3 Voltages L-L Voltage L1-N
4 Currents Total current
5 Currents Frequency
6 Currents Voltage L1-N
7 Phase kW Total kW
8 Phase kW Frequency
9 Phase kW Voltage L1-N
10 Phase kVAr Total kVAr
11 Phase kVAr Frequency
12 Phase kVAr Voltage L1-N
13 Phase kVA Total kVA
14 Phase kVA Frequency
15 Phase kVA Voltage L1-N
16 Phase cosø Average cosø
17 Phase cosø Frequency
18 Phase cosø Voltage L1-N
19 - kWh counter
20 - kVArh counter
21 - hour counter

K30D01-EN - 14 - Version 1.5
4.7. SETTING THE CURRENT TRANSFORMER RATIO
SET
MENU
MENU
PGM
cvrr
trF
500
This parameter sets the primary rating of
current transformers.
Current transformer secondary rating
should be 1 Amps.
The factory set default value is 500/5A.
Acceptable values are 5/5A to 5000/5A.
4.8. SETTING THE VOLTAGE TRANSFORMER RATIO
SET
MENU
MENU
PGM
voLt
trF
10
This parameter sets the ratio of voltage
transformers.
All voltage and power measurements will
be displayed after multiplication with this
parameter.
The factory set default value is 1.0
Acceptable values are 0.1 to 200.0

K30D01-EN - 15 - Version 1.5
4.9. SETTING HIGH AND LOW VOLTAGE LIMITS
SET
MENU
MENU
PGM
voLt
higH
0
This parameter sets the high limit for high
voltage alarm.
Only phase to neutral voltages are
monitored and generate alarms.
If the parameter is set to 0 then no high
voltage alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 12’000volts
SET
MENU
MENU
PGM
voLt
Lo
0
This parameter sets the low limit for low
voltage alarm.
Only phase to neutral voltages are
monitored and generate alarms.
If the parameter is set to 0 then no low
voltage alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 12’000volts

K30D01-EN - 16 - Version 1.5
4.10. SETTING HIGH AND LOW FREQUENCY LIMITS
SET
MENU
MENU
PGM
frq
high
0
This parameter sets the high limit for high
frequency alarm.
If the parameter is set to 0 then no high
frequency alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 400Hz.
SET
MENU
MENU
PGM
FRQ
Lo
0
This parameter sets the low limit for low
frequency alarm.
If the parameter is set to 0 then no low
frequency alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 400Hz.

K30D01-EN - 17 - Version 1.5
4.11. SETTING THE OVERCURRENT LIMIT
SET
MENU
MENU
PGM
Cvrr
high
0
This parameter sets the high limit for
overcurrent alarm.
If the parameter is set to 0 then no
overcurrent alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 5000Amps.

K30D01-EN - 18 - Version 1.5
4.12. SETTING HIGH AND LOW ACTIVE POWER LIMITS
SET
MENU
MENU
PGM
Act
high
0
This parameter sets the high limit for
excess active power alarm.
If the parameter is set to 0 then no excess
active power alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 6500kW.
SET
MENU
MENU
PGM
Act
Lo
0
This parameter sets the low limit for low
active power alarm.
If the parameter is set to 0 then no low
active power alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 6500kW.

K30D01-EN - 19 - Version 1.5
4.13. SETTING HIGH AND LOW REACTIVE POWER LIMITS
SET
MENU
MENU
PGM
rAct
high
0
This parameter sets the high limit for
excess reactive power alarm.
If the parameter is set to 0 then no excess
reactive power alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 6500kVAr.
SET
MENU
MENU
PGM
rAct
Lo
0
This parameter sets the low limit for low
reactive power alarm.
If the parameter is set to 0 then no low
reactive power alarm will occur.
The factory set default value is 0
Acceptable values are 0 to 6500kVAr.

K30D01-EN - 20 - Version 1.5
4.14. SETTING HIGH AND LOW POWER FACTOR LIMITS
SET
MENU
MENU
PGM
coS
high
0000
This parameter sets the high limit for high
cosø alarm.
If the parameter is set to 0.000 then no high
cosø alarm will occur.
The factory set default value is 0.000
Acceptable values are 0.000 to 1.000
SET
MENU
MENU
PGM
coS
Lo
0000
This parameter sets the low limit for low
cosø alarm.
If the parameter is set to 0.000 then no low
cosø alarm will occur.
The factory set default value is 0.000
Acceptable values are 0.000 to 1.000
Table of contents
Other Datakom Measuring Instrument manuals

Datakom
Datakom DKM-409-PRO-AT User manual

Datakom
Datakom DKM-409 User manual

Datakom
Datakom DKM-407 User manual

Datakom
Datakom DKM-407 User manual

Datakom
Datakom DKM-409 User manual

Datakom
Datakom DPR-165 User manual

Datakom
Datakom DKM-409 PRO AT User manual

Datakom
Datakom DSD-080 User manual

Datakom
Datakom DKM-250 User manual

Datakom
Datakom DPR-350 Series User manual