Datakom DPR-350 Series User manual

DPR-350 User Manual Ver_01 Firmware V-1.0
DPR-350 is a state of the art network analyzer and
protection relay in 96x96 standard panel dimensions.
Thanks to its low depth, it provides space economy.
The DPR-350 features dual current measurement
circuits. It is both a precise analyzer and a protection
relay. Protection curves can be selected among IEC,
ANSI, UK and US standards. Multiple protection curves
can be activated simultaneously.
Multiple measurements can be viewed on the 128x64
pixel graphic display of the device.
The unit records every electrical parameter to its built-in
1MB (16MB optional) memory at the desired sampling
rate. The records can be read via Modbus.
Through its RS-485 port, the unit can connect to various
Scada systems and can be remotely monitored.
Parameter configuration is done via USB port.
The unit offers 4 digital inputs, 2 relay outputs, and 3
analog outputs as standard. Analog outputs can be used
to receive desired measurements in the form of 4-20mA
signals, or to drive a visual fault mechanism.
• IEC Standard / Very / Extreme Inverse
• UK Long Term Inverse,
• IEEE Medium / Very / Extreme Inverse
• US Normal Inverse, Short Time Inverse
• USB 2.0 PC connection
• RS-485 (isolated) 2400-115200 baud
• Modbus RTU
• IEC60870-5-103 communication protocol
• 35x event records with time stamp.
• 15.000 periodic records with time stamp.
• Adjustable sampling rate.
• 1MB total record memory.
• Phase voltages: V1-V2-V3-U12-U23-U31
• Phase currents: I1-I2-I3-Ineutral
• Active power: P1-P2-P3-∑P
• Reactive power: Q1-Q2-Q3-∑Q
• Apparent power: S1-S2-S3-∑S
• Power factor: cos1-cos2-cos3-∑cos
• Frequency: F
• Negative sequence currents and voltages
• Zero sequence currents and voltages
• T32Q value
DPR 350
NETWORK ANALYZER &
PROTECTION RELAY
• 128x64 pixels graphic displays
• % 0.5 accuracy OG analyzer features
• 4 quadrant energy counters
• Multiple protection curves
• 1MB records memory
• Self-test, internal failure monitoring
• Cold reclosure
• Configurable optically isolated digital inputs
• Configurable relay outputs
• Configurable analog outputs
• 2 independent configuration sets
• English menus
• Setup parameters on the device
• 3-level password protection
• Connection via USB or RS-485
• Free PC configuration software
• Manual open/close from front panel and
Scada
• Software update via USB
• Wide supply voltage range: 19-150VDC
• IP65 protection with optional gasket
• Low panel depth
• EN60255 Electrical Relays
• EN61010 Safety Requirements
• EN61326 Electromagnetic Compatibility
• EN60068 Environmental Conditions
• EN60529 Protection Levels
ANSI CODE
DESCRIPTION
50,51
Overcurrent
46
Negative Sequence Overcurrent
67
Directional Overcurrent
50BF
Breaker Failure
79
Reclosure
DESCRIPTION
PROTECTION CURVES
COMMUNICATIONS
RECORD MEMORY
ANALYZER MEASUREMENTS
FEATURES
STANDARDS
PROTECTION FUNCTIONS

DPR-350 User Manual Ver_01 Firmware V-1.0
Any unauthorized use or copying of the contents or any part of this document is prohibited. This applies in
particular to trademarks, model denominations, part numbers and drawings.
This document describes the minimum requirements and necessary steps for the successful installation
of the DPR-350 family units.
Follow the advice given in the document carefully. These are often good practices for the installation of
the units which reduce future issues.
For all technical queries please contact Datakom at the e-mail address below:
technical.support@datakom.com.tr
If additional information to this manual is required, please contact the manufacturer directly at the e-mail
address below: technical.support@datakom.com.tr
Please provide the following information in order to receive answers to any question:
- Device model name (see the back panel of the unit),
- Complete serial number (see the back panel of the unit),
- Firmware version (read from the display screen),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the query.
REVISION
DATE
AUTHOR
DESCRIPTION
01
07.02.2017
AY
First Edition
COPYRIGHT NOTICE
ABOUT THIS DOCUMENT
QUERRIES
REVISION HISTORY

DPR-350 User Manual Ver_01 Firmware V-1.0
FILENAME
DESCRIPTION
Rainbow Installation
Rainbow Plus Installation Guide
Rainbow Usage
Rainbow Plus Usage Guide
CAUTION: Potential risk of injury or death.
WARNING: Potential risk of malfunction or material damage.
ATTENTION: Useful hints for the understanding of device operation.
The DPR-350 family units are available in various options and peripheral features. Please use below
information for ordering the correct version.
DPR-350
-DC
-T
-00
RELATED DOCUMENTS
TERMINOLOGY
ORDERING CODES
Family Code
Supply Voltage
AC: 100-265VAC
DC: 24-110VDC
With Conformal
Coating
Variant
00: Standard Unit
01...99: customer
specific products

DPR-350 User Manual Ver_01 Firmware V-1.0
SPARE PARTS
Screw type bracket
Stock Code=J10P01 (per unit)
Self-Retaining type bracket
Stock Code=K16P01 (per unit)
Sealing Gasket, Stock Code= J63P01

DPR-350 User Manual Ver_01 Firmware V-1.0
▪Electrical equipment should only be installed by a qualified
specialist. No responsibility is assured by the manufacturer or
any of its subsidiaries for any consequences resulting from the
non-compliance to these instructions.
▪Check the unit for cracks and damages due to transportation.
Do not install damaged equipment.
▪Do not open the unit. There are no serviceable parts inside.
▪Fuses must be connected to the power supply and phase
voltage inputs, in close proximity of the unit.
▪Fuses must be of fast type (C-type) with a maximum rating of
6A.
▪Disconnect all power before working on the equipment.
▪When the unit is connected to the network, do not touch the
terminals.
▪Short circuit terminals of unused current transformers.
▪Any electrical parameter applied to the device must be in the
range specified in the user manual. Although the unit is
designed with a wide safety margin, over-range parameters may
reduce lifetime, alter operation precision or even damage the
unit.
▪Do not try to clean the device with solvent or the like. Only
clean with a damp cloth.
▪Verify correct terminal connections before applying power.
▪Only for front panel mounting.
SAFETY NOTICE
Failure to follow below instructions will result in death
or serious injury.
Current Transformers must be used for current
measurement. No direct connection allowed.

DPR-350 User Manual Ver_01 Firmware V-1.0
1. INSTALLATION INSTRUCTIONS
2. MOUNTING
2.1. DIMENSIONS
2.2. MECHANICAL INSTALLATION
2.3. SEALING GASKET
2.4. ELECTRICAL INSTALLATION
3. TERMINAL TECHNICAL SPECIFICATIONS
3.1. SUPPLY VOLTAGE INPUT
3.2. AC VOLTAGE INPUTS
3.3. AC CURRENT INPUTS
3.4. DIGITAL INPUTS
3.5. RELAY OUTPUTS
3.6. RS-485 PORT
3.7. USB PORT
4. TOPOLOGIES
4.1. TOPOLOGY SELECTION
4.2. 3 PHASE, 4 WIRE, STAR
4.3. 3 PHASE, 3 WIRE, DELTA
4.4. 3 PHASE, 4 WIRE, DELTA
4.5. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L2)
4.6. 3 PHASE, 3 WIRE, DELTA, 2 CT (L1-L3)
4.7. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L2)
4.8. 2 PHASE, 3 WIRE, DELTA, 2 CTs (L1-L3)
4.9. 1 PHASE, 2 WIRE
5. CONNECTION DIAGRAM
6. TECHNICAL SPECIFICATIONS
7. TERMINAL DESCRIPTIONS
8. DESCRIPTION OF CONTROLS
8.1. FRONT PANEL FUNCTIONALITY
8.2. PUSHBUTTON FUNCTIONS
8.3. MEASURED PARAMETERS
9. DISPLAY SYMBOLS
9.1. AUTOMATIC DISPLAY SCROLL
10. PROTECTION FUNCTIONS
10.1. GENERAL FEATURES
10.2. TIME CALCULATION FOR CURVES
10.3. OVERCURRENT PROTECTION (ANSI 50/51)
10.4. NEGATIVE SEQUENCE OVERCURRENT PROTECTION (ANSI 46)
10.5. DIRECTIONAL OVERCURRENT PROTECTION (ANSI 67)
10.6. BREAKER FAILURE ANSI 50BF)
10.7. AUTOMATIC RECLOSURE (ANSI 79)
10.8. COLD LOAD PICKUP (CLPU 50/51)
11. MIMIC DIAGRAM
12. ASTRONOMIC TIMER RELAY FUNCTION
13. USER SCREEN CONFIGURATION
14. COUNTERS
15. DEMAND VALUES
TABLE OF CONTENTS

DPR-350 User Manual Ver_01 Firmware V-1.0
16. MIN-MAX VALUES
17. DISPLAYING EVENT LOGS
18. PROTECTIONS & ALARMS
19. PROGRAMMING
19.1. ENTERING PROGRAM MODE
19.2. NAVIGATING BETWEEN MENUS
19.3. MODIFYING PARAMETER VALUE
19.4. EXITING PROGRAM MODE
20. PROGRAM PARAMETER LIST
20.1. CONTROLLER CONFIGURATION GROUP
20.2. ELECTRICAL PARAMETERS GROUP
20.3. INPUT PARAMETERS
20.4. OUTPUT PARAMETERS
20.5. ANALOG OUTPUTS
20.6. INPUT & DISPLAY STRINGS
20.7. RESETTING THE COUNTERS
20.8. USER SCREEN CONFIGURATION
20.9. MODIFYING THE SERIAL NUMBER
20.10. CALIBRATION
20.11. DATE & TIME SETTINGS
20.12. CHANGING THE PASSWORD
20.13. RETURN TO FACTORY PRESET
20.14. LOCATION SETTINGS
20.15. OVERCURRENT PROTECTION (ANSI 50/51)
20.16. NEGATIVE SEQUENCE OVERCURRENT PROTECTION (ANSI 46)
20.17. BREAKER FAILURE (ANSI 50BF )
20.18. AUTO RECLOSURE ( ANSI 79 )
20.19. COLD LOAD PICKUP
20.20. SAFE EXIT
21. INTERNAL RECORDS MEMORY
22. MODBUS COMMUNICATIONS
22.1. REQUIRED PARAMETERS FOR RS-485 MODBUS COMMUNICATION
22.2. DATA FORMATS
22.3. DATA READING
22.4. DATA WRITING
22.5. CRC CALCULATION
22.6. INTERNAL RECORD STORAGE STRUCTURE
22.7. COMMANDS
22.8. REAL TIME CLOCK (RTC)
22.9. COUNTERS
22.10. MEASUREMENTS
22.11. FUNCTION ALARM INFORMATION
22.12. DEMAND-MIN-MAX
23. DECLARATION OF CONFORMITY
24. MAINTENANCE
25. DISPOSAL OF THE UNIT
26. ROHS COMPLIANCE

DPR-350 User Manual Ver_01 Firmware V-1.0
Before installation:
▪Read the user manual carefully, determine the correct connection diagram.
▪Remove all connectors and mounting brackets from the unit, then pass the unit through the
mounting opening.
▪Put mounting brackets on and tighten. Do not tighten too much, this may break the enclosure.
▪Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
▪Be sure that adequate cooling is provided.
▪Be sure that the temperature of the environment will not exceed the maximum operating
temperature in any case.
▪Be sure that no water will contact the device.
Below conditions may damage the device:
▪Incorrect connections.
▪Incorrect power supply voltage.
▪Voltage at measuring terminals beyond specified range.
▪Voltage applied to digital inputs over specified range.
▪Current at measuring terminals beyond specified range.
▪Overload or short circuit at relay outputs.
▪Connecting or removing data terminals while the unit is powered up.
▪High voltage applied to communication ports.
▪Ground potential differences at non-isolated communication ports.
▪Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
▪Power supply voltage below minimum acceptable level.
▪Frequency outside specified limits.
▪Phase order fault.
▪Faulty current transformer input.
▪Incorrect current transformer polarity.
▪Incomplete grounding.
1. INSTALLATION INSTRUCTIONS
Current transformers must be used for current
measurement.
No direct connection allowed.

DPR-350 User Manual Ver_01 Firmware V-1.0
Dimensions: 102x102x53mm (4.0”x4.0”x2.0”)
Installation: Panel mounted, rear retaining plastic brackets.
Weight: 200g (0.44 lb)
Panel Cutout Required Panel Depth
2. MOUNTING
2.1. DIMENSIONS
2.2. MECHANICAL INSTALLATION
The unit is designed for panel mounting. The user
should not be able to access parts of the unit other
than the front panel during normal operation.

DPR-350 User Manual Ver_01 Firmware V-1.0
Mount the unit on a flat, vertical surface. Before mounting, remove the mounting brackets and connectors
from the unit, then pass the unit through the mounting opening.
Place and tighten mounting brackets.
Two different types of brackets are provided:
Screw type bracket
Self-retaining type bracket
Installation of screw type bracket
Installation of self-retaining type bracket
Do not tighten too much, this may break the unit.

DPR-350 User Manual Ver_01 Firmware V-1.0
The rubber gasket (sold separately) provides a watertight means of mounting the module to the panel.
With the gasket, IEC 60529-IP65 protection is provided. A short definition of IP protection levels is given
below:
1st Digit
0 Not protected
1 Protected against solid foreign objects of 50 mm diameter and greater
2 Protected against solid foreign objects of 12.5 mm diameter and greater
3 Protected against solid foreign objects of 2.5 mm diameter and greater
4 Protected against solid foreign objects of 1.0 mm diameter and greater
5 Protected from the amount of dust that would interfere with normal operation
6 Dust tight
2nd Digit
0 Not protected
1 Protected against vertically falling water drops
2 Protected against vertically falling water drops when enclosure is tilted up to 15 °
3 Protected against water sprayed at an angle up to 60 ° on either side of the vertical
4 Protected against water splashed against the component from any direction
5 Protected against water projected in jets from any direction
6 Protected against water projected in powerful jets from any direction
7 Protected against temporary immersion in water
8 Protected against continuous immersion in water, or as specified by user
2.3. SEALING GASKET
Module
Gasket
Panel

DPR-350 User Manual Ver_01 Firmware V-1.0
Although the unit is protected against electromagnetic disturbance, excessive
disturbance can affect the operation, measurement precision and data communication
quality.
▪ALWAYS remove plug connectors when inserting wires with a screwdriver.
▪Fuses must be connected to the power supply and phase voltage inputs, in
close proximity to the unit.
▪Fuses must be of fast type (C-type) with a maximum rating of 6A.
▪Use cables of appropriate temperature range.
▪Use adequate cable section, at least 0.75mm2 (AWG18).
▪Follow national rules for electrical installation.
▪Current transformers must have 1A or 5A output.
▪For current transformer inputs, use at least 1.5mm2section (AWG15) cable.
▪The current transformer cable length should not exceed 1.5 meters. If a
longer cable is used, increase the cable section proportionally.
2.4. ELECTRICAL INSTALLATION
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switchmode power supplies, etc.
Current transformers must be used for current
measurement.
No direct connection allowed.
For the correct storage of event records, adjust the
real time clock through the programming menu.

DPR-350 User Manual Ver_01 Firmware V-1.0
Power Supply Voltage:
AC SUPPLY TYPES: 100-265VAC(±%15), 50-60Hz (±%10), 88-
400VDC
DC SUPPLY TYPES: 24-110VDC (±%20)
Reverse Voltage:
Directionless inputs, operates with both polarities.
Maximum Input Power:
15 VA
Isolation:
3500VAC/1minute from all other terminals.
Measurement Method:
True RMS
Sampling Rate:
8192 Hz
Input Voltage Range:
0 - 300 VAC (phase-neutral)
Measurement Range:
7 - 330VAC Ph-N (14 to 520VAC Ph-Ph)
Input Impedance:
4.5M-ohm
Display Resolution:
0.1VAC
Accuracy:
0.5% + 1 digit @ 230VAC Ph-N (±2VAC Ph-N)
0.5% + 1 digit @ 400VAC Ph-Ph (±3VAC Ph-Ph)
Withstanding:
1300V-AC continuous
Frequency Range:
30 to 100 Hz
Frequency Display
Resolution:
0.01 Hz
Frequency Accuracy:
0.5% + 1 digit
3. TERMINAL TECHNICAL SPECIFICATIONS
3.1. SUPPLY VOLTAGE INPUT
Power supply input must be fused. (6A type C).
3.2. AC VOLTAGE INPUTS
Supply Input
Connector

DPR-350 User Manual Ver_01 Firmware V-1.0
Structure:
Isolated, integrated current transformers
Measurement Method:
True RMS
Sampling Rate:
8192 Hz
CT Secondary Rating:
5A
CT Range:
5/5 - 25000/5A minimum
Input Impedance:
15 milliohms
Burden:
0.375W @ 5A
Maximum Current:
6A continuous
Measurement Range:
0.001 to 6A AC
Display Resolution:
0.1A
Accuracy:
0.5% + 1 digit
Isolation:
1000VAC/1minute from all other terminals.
Withstanding:
100A-AC 1 second
SELECTING THE CT RATING AND CABLE SECTION:
The load on a CT must be kept minimum in order to
minimize phase shift effect of the current transformer.
Phase shift in a CT will cause erroneous power and
power factor readings, although the amp readings are
correct.
It is advised CT rating to be selected following this table
for the best measurement accuracy.
SELECTING THE CT ACCURACY CLASS:
The CT accuracy class should be selected in accordance
with the required measurement precision. The accuracy
class of the controller is 0.5%. Thus 0.5% class CTs are
advised for the best result.
CONNECTING THE CTs:
Be sure to connect each CT to the related phase input with the correct polarity. Mixing CTs between
phases will cause faulty power and power factor readings.
Many combinations of incorrect CT connections are possible, so check both the order of the CTs and
their polarity. Reactive power measurement is affected by incorrect CT connections in a similar was as
active power measurement.
3.3. AC CURRENT INPUTS

DPR-350 User Manual Ver_01 Firmware V-1.0
CORRECT CT CONNECTIONS
Suppose that each phase of the utility mains are loaded with 100 kW. The power factor (PF) for the load
is as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
100.0
0.0
100
1.00
Phase L3
100.0
0.0
100
1.00
Total
300.0
0.0
300
1.00
EFFECT OF POLARITY REVERSAL
The utility mains is still loaded with 100 kW on each phase. The load power factor (PF) on Phase L2 will
show -1.00 due to reverse CT polarity.
As a result, total load power displayed will be 100 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-100.0
0.0
100
-1.00
Phase L3
100.0
0.0
100
1.00
Total
100.0
0.0
300
0.33

DPR-350 User Manual Ver_01 Firmware V-1.0
EFFECT OF PHASE SWAPPING
The utility mains is still loaded with 100 kW on each phase. PF in phases L2 and L3 will show -0.50 due
to phase shift between voltages and currents which is caused by CT swapping. As a result, the total
power displayed will be 0 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-50.0
86.6
100
-0.50
Phase L3
-50.0
-86.6
100
-0.50
Total
0.0
0.0
300
0.0
Number of Inputs:
4 inputs, all configurable.
Input Type:
Optically isolated, digital input
Function Selection:
From list
Contact Type:
Normally open or normally closed (programmable)
Minimum Sensing
Duration:
250ms
Active Signal Level:
40-135V-DC or 30-265V-AC
Isolation:
1000VAC, 1 minute
Noise Filtering:
Var
Structure:
Relay output, normally open contact, single common terminal free
contact output.
Max. Switching Current:
5A @250VAC
Max. Switching Voltage:
250VAC
Max. Switching Power:
1250VA
3.4. DIGITAL INPUTS
3.5. RELAY OUTPUTS

DPR-350 User Manual Ver_01 Firmware V-1.0
Structure:
RS-485, isolated.
Connection:
3 wires (A-B-GND). Half duplex.
Baud rate:
2400-115200 baud, adjustable.
Data type:
8 bit data, no parity, 1 bit stop
Termination
External 120 ohms required.
Common mode voltage:
-0.5 VDC ... +7VDC, internally clamped by transient suppressors.
Max. Distance:
1200m @ 9600 baud (with 120 ohm balanced cable)
200m @ 115200 baud (with 120 ohm balanced cable)
Isolation:
500VAC, 1 minute
The RS-485 port supports MODBUS-RTU protocol. Multiple modules may be paralleled on the same RS-
485 line in order to provide data transfer to automation or building management systems.
The RS-485 port provides an effective solution for distant PC connection to enable programming and
monitoring via SCADA software.
RS-485 LINE STRUCTURE
Up to 32 controllers can be connected in parallel on a single RS-485 line. A repeater is required in order
to connect more controllers.
A B A B A BA B
120R 120R
The line must be terminated by 120 ohms on each end.
The cable shield must be grounded at one end only.
3.6. RS-485 PORT
The Modbus register list is available at Datakom
technical support.
There is no termination resistor in the controller.
120 ohm termination resistors must be installed at
each end of the line.
Cihaz içinde sonlandırma direnci yoktur.
Haberleşme hattının her ucuna 120 ohm sonlandırma
direnci takılmalıdır.

DPR-350 User Manual Ver_01 Firmware V-1.0
Description:
USB 2.0, non-isolated, HID mode
Data transfer rate:
1.5/12 Mbit/s, auto detecting
Connector:
Mini-USB (camera cable)
Cable length:
Max. 6 meters
Function:
Modbus RTU
The USB port is designed to provide PC connection with the controller. Programming and monitoring can
be done via RainbowPlus program.
The RainbowPlus program is available for free on www.datakom.com.tr.
The connector type is Mini-USB. The cable type is the commonly available camera cable.
Please refer to the RainbowPlus user manual for more detailed information about monitoring,
programming, and control.
3.7. USB PORT
Mini-USB
Connector
Mini USB
Cable

DPR-350 User Manual Ver_01 Firmware V-1.0
Topologies are selected from program parameters.
Mains grid topologies are shown in the picture below.
4. TOPOLOGIES
4.1. TOPOLOGY SELECTION
Configuration
Screen
Topology
Selection
Electrical
Parameters

DPR-350 User Manual Ver_01 Firmware V-1.0
4.2. 3 PHASE, 4 WIRE, STAR
4.3. 3 PHASE, 3 WIRE, DELTA
This manual suits for next models
1
Table of contents
Other Datakom Measuring Instrument manuals

Datakom
Datakom DKM-409 PRO AT User manual

Datakom
Datakom DKM-409-PRO-AT User manual

Datakom
Datakom DKM-409 User manual

Datakom
Datakom DV-0101 User manual

Datakom
Datakom DKM-405 User manual

Datakom
Datakom DKM-407 User manual

Datakom
Datakom DKM-250 User manual

Datakom
Datakom DKM-411 Instructions for use

Datakom
Datakom DKM-409 User manual

Datakom
Datakom DKM-260 User manual