Datakom DKM-430 User manual

DKM-430 User Manual Rev_02 Firmware V-1.8
DKM-430
MULTIPLE NETWORK
ANALYSER
DATAKOM DKM-430 is a precision instrument
allowing the measurement, recording and remote
monitoring of 10 3-phased or 30 single-phased feeders
(or any combination of these two). The number and
flexibility of current inputs allow the unit to be used in a
variety of applications like power distribution network
monitoring, ISO50001 energy efficiency or home and
factory automation.
The unit can be mounted on a DIN rail or backplane. It
can be easily adapted to existing panels.
Current inputs of the unit are designed for 0.1A output
current transformers (CTs). Different 0.1A rated CTs
are available at Datakom for sales.
Each CT can be assigned to any phase voltage and
any virtual analyzer. Inputs can be moved between
analyzers without modifying connections.
Independently adjustable current limits for each phase
provide pre-alarms and help to reduce energy failures.
All measurement values and program parameters may
be displayed on the graphic LCD screen.
The unit logs all fault conditions together with date and
time information. The internal real time clock is capable
of running 10 years without energy.
The astronomical relay function calculates sunrise and
sunset times precisely for daylight based applications.
Any fault or warning signal can be connected to digital
inputs of the unit. Input functions are selected from list.
Any function can be assigned to relay outputs of the
unit. Relays may be remotely operated through the
central monitoring program.
The isolated RS-485 MODBUS RTU data port is
unaffected by ground potential differences and allows
safe transmission of information to monitoring and
automation systems.
The optional internal GPRS modem allows remote
monitoring and control of the distribution panel without
the use of any additional module.
Parameter setting of the unit is made either manually or
through the USB port using the free PC program.
The unit records electrical parameters in its 1MB
internal memory with programmed period. Records are
read through Modbus.
Equivalent to 10 3-phase analyzers
True RMS measurements
0.5% measurement precision
Internal record memory: 1MB
Internal battery backed-up real time clock
Astronomical relay function
Isolated RS-485 serial port
MODBUS-RTU communication
Internal GPRS modem (optional)
2 programmable relay outputs
2 optically isolated programmable inputs
Active-reactive energy counters
USB port for programming
Free programming software
Graphic LCD, 128x64 pixels
Wide supply range:85-305VAC / 88-450VDC
DC supply version available
Wide operating temperature range
VOLTAGE INPUTS:
▪P-N and P-P voltages: V1-V2-V3-U12-U23-U31
▪Harmonics: Voltage inputs, 2-17 harmonics
EACH CT INPUT:
▪Current: In
▪Active/reactive/apparent powers: Pn-Qn-Sn
▪Power factor: COSn
▪Current harmonics 2-17
EACH VIRTUAL ANALYSER:
▪Total active/reactive/apparent power: ∑P-∑Q-∑S
▪Total power factor: ∑cos
▪Active and reactive counters: Pn-Qn
FEATURES
MEASUREMENTS
DESCRIPTION

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 2 -
Any unauthorized use or copying of the contents or any part of this document is prohibited.
This document describes minimum requirements and necessary steps for the successful installation of the
DKM-430 family units.
Follow carefully advices given in the document. These are often good practices for the installation which
reduce future issues.
For all technical queries please contact Datakom at below e-mail address:
If additional information to this manual is required, please contact the manufacturer directly at below e-mail
address: datakom@datakom.com.tr
Please provide following information in order to get answers to any question:
- Device model name (see the back panel of the unit),
- Complete serial number (see the back panel of the unit),
- Firmware version (read from the display screen),
- Measuring-circuit voltage and power supply voltage,
- Precise description of the query.
FILENAME
DESCRIPTION
500-Rainbow Installation
Rainbow Plus D-500 D-700 Installation Guide
500-Rainbow Usage
Rainbow Plus D-500 D-700 Usage Guide
500-Rainbow Scada Installation
Rainbow Scada Installation Guide
500-Rainbow Scada Usage
Rainbow Scada Usage Guide
QUERRIES
RELATED DOCUMENTS
ABOUT THIS DOCUMENT
COPYRIGHT NOTICE

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 3 -
REVISION
DATE
AUTHOR
DESCRIPTION
01
15.06.2015
MH
First edition
02
15.02.2017
ME
Modbus addresses updated
CAUTION: Potential risk of injury or death.
WARNING: Potential risk of malfunction or material damage.
ATTENTION: Useful hints for the understanding of device operation.
The D-500 family units are available in various options and peripheral features. Please use below information
for ordering the correct version:
DKM-430
-M
-T
-00
REVISION HISTORY
TERMINOLOGY
ORDERING CODES
Family Code
With Internal
GSM-GPRS
Modem
With Conformal
Coating
Variant
00: standard unit
01...99: customer
specific products

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 4 -
▪Electrical equipment should be installed only by qualified
specialist. No responsibility is assured by the manufacturer or
any of its subsidiaries for any consequences resulting from the
non-compliance to these instructions.
▪Check the unit for cracks and damages due to transportation. Do
not install damaged equipment.
▪Do not open the unit. There are no serviceable parts inside.
▪Fuses must be connected to the power supply and phase voltage
inputs, in close proximity of the unit.
▪Fuses must be of fast type (FF) with a maximum rating of 6A.
▪Disconnect all power before working on equipment.
▪When the unit is connected to the network do not touch
terminals.
▪Short circuit terminals of unused current transformers.
▪Any electrical parameter applied to the device must be in the
range specified in the user manual. Although the unit is designed
with a wide safety margin, over-range parameters may reduce
lifetime, alter operational precision or even damage the unit.
▪Do not try to clean the device with solvent or the like. Only clean
with a dump cloth.
▪Verify correct terminal connections before applying power.
▪Only for panel base mounting.
SAFETY NOTICE
Failure to follow below instructions
will result in death or serious injury
Current measurement is made with CTs provided together
with the module.
Do not apply direct connection, do not use 1A/5A current
transformers.

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 5 -
1. INSTALLATION INSTRUCTIONS
2. MOUNTING
2.1 DIMENSIONS
2.3 ELECTRICAL INSTALLATION
3. TERMINAL DESCRIPTIONS
3.1. BATTERY VOLTAGE INPUT
3.2. AC VOLTAGE INPUTS
3.3. AC CURRENT INPUTS
3.4. DIGITAL INPUTS
3.5. RELAY OUTPUTS
3.6. RS-485 PORT
3.7. USB DEVICE PORT
3.8. GSM MODEM (OPTIONAL)
4. CONNECTION DIAGRAM
5. TECHNICAL SPECIFICATIONS
6. DESCRIPTION OF CONTROLS
6.1. FRONT PANEL FUNCTIONALITY
6.2. PUSHBUTTON FUNCTIONS
6.3. LED FUNCTIONS
6.4. SCREEN SCROLLING
7. WAVEFORM DISPLAY & HARMONIC ANALYSIS
8. ASTRONOMIC RELAY FUNCTIONALITY
9. PROTECTIONS AND ALARMS
10. PROGRAMMING
10.1. ENTERING THE PROGRAMMING MODE
10.2. NAVIGATING BETWEEN MENUS
10.3. MODIFYING PARAMETER VALUE
10.4. PROGRAMMING MODE EXIT
TABLE OF CONTENTS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 6 -
11. PROGRAM PARAMETER LIST
11.1. CONTROLLER CONFIGURATION GROUP
11.2. ELECTRICAL PARAMETERS GROUP
11.3. CHANNEL CONFIGURATION
11.4. GSM MODEM PARAMETERS
11.5. DIGITAL INPUT PARAMETERS
11.6. DIGITAL OUTPUT PARAMETERS
11.7. USER INPUT SCREENS
11.8. DEMAND AND COUNTERS
11.9. USER SCREENS
11.10. DEVICE CALIBRATION
11.11. ADJUST DATE AND TIME
11.12. CHANGE PASSWORD
11.13. RETURN TO FACTORY SETTINGS
11.14. LOCATION SETUP
12. INTERNAL RECORD MEMORY
13. CENTRAL MONITORING OF UNITS
14. E-MAIL SENDING
15. SMS COMMANDS
16. MODBUS COMMUNICATIONS
16.1. PARAMETERS REQUIRED FOR RS-485 MODBUS OPERATION
16.2. DATA FORMATS
16.3. EXCHANGE BUFFER
16.4. DATE-TIME AND LOCATION ARRAY
16.5. COUNTERS ARRAY
16.6. COMMANDS ARRAY
16.7. MEASUREMENTS ARRAY
16.8. ANALYZER BLOCKS
16.9. DIGITAL INPUTS AND OUTPUTS
16.10. HARMONIC ANALYSIS
16.11. OSCILLOGRAPHIC RECORDS
16.12. DEVICE INFORMATION
16.13. ALARM INFORMATION
17. DECLARATION OF CONFORMITY
18. MAINTENANCE
19. DISPOSAL OF THE UNIT
20. ROHS COMPLIANCE
21. TROUBLESHOOTING GUIDE

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 7 -
Before installation:
▪Read the user manual carefully, determine the correct connection diagram.
▪Install to the panel base or DIN rail. In order to install to panel base, pull mounting tabs at corners.
▪Make electrical connections with plugs removed from sockets, then place plugs to their sockets.
▪Be sure that adequate cooling is provided.
▪Be sure that the temperature of the environment will not exceed the maximum operating temperature in any
case.
▪Be sure that the unit is not subject to water spill.
Below conditions may damage the device:
▪Incorrect connections.
▪Incorrect power supply voltage.
▪Voltage at measuring terminals beyond specified range.
▪Voltage applied to digital inputs over specified range.
▪Current at measuring terminals beyond specified range.
▪Overload or short circuit at relay outputs
▪Connecting or removing data terminals when the unit is powered-up.
▪High voltage applied to communication ports.
▪Ground potential differences at non-isolated communication ports.
▪Excessive vibration, direct installation on vibrating parts.
Below conditions may cause abnormal operation:
▪Power supply voltage below minimum acceptable level.
▪Power supply frequency out of specified limits
▪Phase order of voltage inputs not correct.
▪Current transformers not matching related phases.
▪Current transformer polarity incorrect.
▪Missing grounding.
Current measurement is made with CTs provided together
with the module.
Do not apply direct connection, do not use 1A/5A current
transformers.
1. INSTALLATION INSTRUCTIONS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 8 -
Dimensions: 158x90x60mm (6.22”x3.55”x2.36”)
Installation: Panel base or DIN rail
Weight: 350g (0.77 lb)
Although the unit is protected against electromagnetic disturbance, excessive disturbance
can affect the operation, measurement precision and data communication quality.
▪ALWAYS remove plug connectors when inserting wires with a screwdriver.
▪Fuses must be connected to the power supply and phase voltage inputs, in close
proximity of the unit.
▪Fuses must be of fast type (FF) with a maximum rating of 6A.
▪Use cables of appropriate temperature range.
▪Use adequate cable section, at least 0.75mm2 (AWG18).
▪Follow national rules for electrical installation.
▪Current transformers must have 0.1A output.
2.1. DIMENSIONS
Current measurement is made with CTs provided together with
the module.
Do not apply direct connection, do not use 1A/5A current
transformers.
Do not install the unit close to high electromagnetic
noise emitting devices like contactors, high current
busbars, switchmode power supplies and the like.
2.2. ELECTRICAL INSTALLATION
2. MOUNTING

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 9 -
Supply voltage:
AC SUPPLY VERSIONS: 85-305VAC, 45-65Hz, 88-450VDC
DC SUPPLY VERSIONS: 19-150VDC
Reverse voltage:
Non polarized inputs, works in both polarizations.
Maximum input power:
6W
Typical operating current:
250mA @ 12VDC. (all options passive, digital outputs open)
125mA @ 24VDC. (all options passive, digital outputs open)
Maximum operating
current:
30mA @ 230VAC. (all features active, digital outputs open)
60mA @ 110VDC. (all features active, digital outputs open)
Measurement method:
True RMS
Sampling rate:
2048 Hz
Harmonic analysis:
up to 17th harmonic
Input voltage range:
5 to 300 VAC (phase-neutral)
Measurement range:
0 to 330VAC ph-N (0 to 570VAC ph-ph)
Input impedance:
4.5M-ohms
Display resolution:
0.1VDC
Accuracy:
0.5% + 1 digit @ 230VAC ph-N (±2VAC ph-N)
0.5% + 1 digit @ 400VAC ph-ph (±3VAC ph-ph)
Frequency range:
45 to 65 Hz
Frequency display
resolution:
0.01 Hz
Frequency accuracy:
0.2% + 1 digit (±0.1 Hz @ 50Hz)
3.1. BATTERY VOLTAGE INPUT
3. TERMINAL DESCRIPTIONS
3.2. AC VOLTAGE INPUTS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 10 -
Measurement method:
True RMS
Sampling rate:
2048 Hz
Harmonic analysis:
up to 17th harmonic
CT secondary rating:
100mA
Measurement range:
5/0.1 to 5000/0.1A minimum
Input impedance:
1 ohm
Burden:
10 mW
Maximum continuous
current:
500mA
Measurement range:
0.5 to 120mAA
Display resolution:
0.1A
Accuracy:
0.5% + 1 digit @ 100mA
SELECTING THE CT ACCURACY CLASS:
The CT accuracy class should be selected in accordance with the required measurement precision. The
accuracy class of the Datakom controller is 0.5%. Thus 0.5% class CTs are advised for the best result.
3.3. AC CURRENT INPUTS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 11 -
CONNECTING CTs:
Be sure of connecting each CT to the related phase input with the correct polarity. Mixing CTs between
phases will cause faulty power and pf readings.
Many combinations of incorrect CTs connections are possible, so check both order of CTs and their polarity.
Reactive power measurement is affected by incorrect CTs connection in similar way as active power
measurement.
CORRECT CT CONNECTIONS
Let’s suppose that the network is loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
100.0
0.0
100
1.00
Phase L3
100.0
0.0
100
1.00
Total
300.0
0.0
300
1.00

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 12 -
EFFECT OF POLARITY REVERSAL
The network is still loaded with 100 kW On each phase. The load Power Factor (PF) is 1.
PF in phase L2 will show -1,00 due to reverse CT polarity. The result is that total network power displayed by
the controller is 100 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-100.0
0.0
100
-1.00
Phase L3
100.0
0.0
100
1.00
Total
100.0
0.0
300
0.33
EFFECT OF PHASE SWAPPING
The network is still loaded with 100 kW on each phase. The load Power Factor (PF) is 1.
PF in phases L2 and L3 will show -0,50 due to phase shift between voltages and currents which is caused by
CT swapping. The result is that total network power displayed by controller is 0 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-50.0
86.6
100
-0.50
Phase L3
-50.0
-86.6
100
-0.50
Total
0.0
0.0
300
0.0

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 13 -
Number of inputs:
2 inputs, all configurable
Input type:
Opto-isolated digital input
Function selection:
from list
Contact type:
Normally open or normally closed (programmable)
Minimum pulse duration:
250ms
Active level:
85-305VAC
Isolation:
1000VAC, 1 minute
Noise filtering:
yes
Structure:
Relay output, normally open contact. One terminal is internally
connected to the common terminal for both relays.
Max switching current:
5A @250VAC
Max switching voltage:
250VAC
Max switching power:
1250VA
Structure:
RS-485, isolated.
Connection:
3 wires (A-B-GND). Half duplex.
Baud rate:
2400-115200 bauds, selectable
Data type:
8 bit data, no parity, 1 bit stop
Termination:
External 120 ohms required
Common mode voltage:
-0.5 VDC to +7VDC, internally clamped by transient suppressors.
Max distance:
1200m @ 9600 bauds (with 120 ohms balanced cable)
200m @ 115200 bauds (with 120 ohms balanced cable)
Isolation:
1000VAC, 1 minute
The RS-485 port features MODBUS-RTU protocol. Multiple modules (up to 128) can be paralleled on the
same RS-485 bus for data transfer to automation or building management systems.
The RS-485 port provides also a good solution for distant PC connection where RainbowPlus program will
enable programming, control and monitoring.
3.5. RELAY OUTPUTS
3.6. RS-485 PORT
3.4. DIGITAL INPUTS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 14 -
Description:
USB 2.0, not isolated, HID mode
Data rate:
Full Speed 1.5/12 Mbits/s, auto detecting
Connector:
USB-B (printer connector)
Cable length:
Max 6m
Functionality:
Modbus, FAT32 for firmware upgrade (boot loader mode only)
The USB-Device port is designed to connect the module to a PC. Using the RainbowPlus software,
programming, control of the genset and monitoring of measured parameters are achieved.
The RainbowPlus software can be downloaded from www.datakom.com.tr website.
The connector on the module is of USB-B type. Thus A to B type USB cable should be used. This is the
same cable used for USB printers.
For more details about programming, control and monitoring please refer to RainbowPlus user manual.
If USB connector provides also power supply to the
unit. During computer connection additional supply
is not required.
3.7. USB PORT
USB
Connector
USB A to B
Cable

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 15 -
The optional internal GSM modem offers the advantage of being internally powered and is fully compatible
with the unit. It does not require any special setup.
The 1800/1900 MHz magnetic antenna together with its 2 meter cable is supplied with the internal modem
option. The antenna is intended to be placed outside of the genset panel for the best signal reception.
The module requires a GPRS enabled SIM card for full functionality. Voice-only type SIM cards will usually
not function properly.
Please refer to GSM Modem Configuration Guide for more details.
Description:
Quad-band GSM/GPRS 850/900/1800/1900MHz module.
GPRS multi-slot class 12/10
GPRS mobile station class B
Compliant to GSM phase 2/2+.
–Class 4 (2 W @850/ 900 MHz)
–Class 1 (1 W @ 1800/1900MHz)
Functionality:
Web Client, SMTP, Modbus TCP/IP (client), SMS, e-mail
Operating temp range:
-40°C to +85 °C
Data speed:
max. 85.6 kbps (download), 85.6 kbps (upload)
SIM card type:
external SIM 3V/1.8V, GPRS enabled
Antenna:
Quad band, magnetic, with 2m cable
Module certificates:
CE, FCC, ROHS, GCF, REACH
3.8. GSM MODEM (OPTIONAL)
SIM Card slot
SIM Card extraction tab
Antenna connector
Communication
indicator

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 16 -
4. CONNECTION DIAGRAM

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 17 -
Supply Input:
85 - 305VAC, 50/60Hz,
88 - 450VDC
Optional 19-150VDC
Measurement Inputs:
Voltage: 7 - 300 V AC (P-N)
14 - 520 V AC (P-P)
Current: 0.001 –0.12 A AC
Frequency: 45 - 65 Hz
Accuracy:
Voltage: 0.5% + 1 digit
Current: 0.5% + 1 digit
Frequency: 0.5% + 1 digit
Power (kW,kVAr): 1.0% + 2 digit
Cos: 0.5% + 1 digit
Measurement Range:
CT range: 5A to 6500A
VT range: 1.0/1 to 5000.0/1
kW range: 1.0 kW to 5000 MW
Power Consumption: < 6 VA
Loading:
Voltage Input: < 0.02VA per phase
Current Input: < 0.02VA per phase
Relay Outputs: 5A @ 250V AC
Digital Inputs:
Active level: 85 –305VAC
Min pulse: 250ms.
Isolation: 1000V AC, 1 minute
Serial Port:
Signal type: RS-485
Protocol: Modbus RTU
Data Rate: 2400-115200b adjustable
İsolation: 1000V AC, 1 minute
Operating Temp. Range: -20°C to +70 °C (-4°F to 158°F)
Max Relative Humidity: 95%, non-condensing
Case Material: Flame retardant, ROHS compliant, high temp. ABS/PC (UL94-V0)
Installation: DIN rail or backpanel
Dimensions: 158x90x60mm (WxHxD)
Weight: 350 gr
AB Directives:
2006/95/EC (LVD)
2004/108/EC (EMC)
Reference Standards:
EN 61010 (safety)
EN 61326 (EMC)
5. TECHNICAL SPECIFICATIONS

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 18 -
BUTTON
FUNCTION
Selects previous display screen in the same display group.
Selects previous display group.
Selects next display group.
Selects next display screen in the same display group.
When held pressed for 5 seconds, enters PROGRAMMING mode.
6.2. PUSHBUTTON FUNCTIONS
6.1. FRONT PANEL FUNCTIONALITY
6. DESCRIPTION OF CONTROLS
Energy and
communication
indicators
Graphic LCD
screen
Next screen in
the same group.
Previous
display group
Next display
group
Previous
screen in the
same group.
Fault condition
indicators

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 19 -
POWER: Turns on as long as energy is supplied to the unit.
COMM: Flashes when the RS-485 Modbus communication is active.
ALARM: Turns on in case of high level alarm (trip condition).
UYARI: Turns on in case of warning.
The unit performs a detailed set of AC measurements. Displaying these parameters are organized under
PARAMETER GROUPS and subgroups.
Switching between parameter groups are made with and buttons.
Each depression of the button switches the screen to the next parameter group. After the last group, the
first group is displayed again.
Each depression of the button switches the screen to the previous parameter group. After the first
group, the last group is displayed again.
Switching within the same group is performed with and buttons.
Each depression of the button switches the screen to the next display in the same group. After the last
display, the first display comes again.
Each depression of the button switches the screen to the previous display in the same group. After the
first display, the last display comes again.
The list of parameter groups are below:
Channel Measurement Screens: Voltage, current, kW, kVA, kVAr, pf and reactive ratio of each input
channel.
Channel Counter Screens: Instantaneous current, demand current, demand power, active and reactive
energy counters of each input channel.
Main busbar voltages and frequency: Phase-neutral, phase-phase and average voltages of the main
busbar in different screens.
GSM Modem Parameters: Signal level, counters, connection status, IP addresses, etc...
Status Group: Various information as date-time, firmware version, identity, configuration, etc...
User Screens: Screens in this group are configured by the user.
Oscilloscope Screen: In this group, waveforms of currents and voltages may be visualized as an
oscilloscope. All phase-neutral and phase-phase voltages and each current input are avalable. Thanks to
this feature, waveform distorsions and harmonic components are displayed in graphichal form.
Harmonic Analysis Result Tables: In this group, THDs of currents and voltages are displayed with 0.1%
precision. All phase-neutral and phase-phase voltages and each current input are avalable.
6.3. LED FUNCTIONS
6.4. SCREEN SCROLLING

DKM-430 User Manual Rev_02 Firmware V-1.8
K92D01-EN - 20 -
The unit features waveform display together with a precision harmonic analyzer for both voltages and
currents. Both phase to neutral and phase to phase voltages are available for analysis, thus 36 channels in
total are possible.
Available channels are:
Main busbar volts: V1, V2, V3, U12, U23, U31
Currents: I1, I2, I3,….,I29,I30
Scopemeter Display
The waveform display memory is of 100 samples length and 13 bit resolution, with a sampling rate of 2048
s/s. Thus one cycle of a a 50Hz signal is represented with 41 points. The vertical scale is automatically
adjusted in order to avoid clipping of the signal.
The waveform is displayed on the device screen, and with more resolution on PC screen through the
RainbowPlus program.
The display memory is also available in the Modbus register area for third party applications. For more
details please check chapter “MODBUS Communications”.
The waveform display is updated twice a second. All channels may be scrolled using buttons.
7. WAVEFORM DISPLAY & HARMONIC ANALYSIS
Table of contents
Other Datakom Measuring Instrument manuals

Datakom
Datakom DPR-165 User manual

Datakom
Datakom DPR-350 Series User manual

Datakom
Datakom DKM-411 User manual

Datakom
Datakom DV-0101 User manual

Datakom
Datakom DKM-260 User manual

Datakom
Datakom DKM-409 PRO AT User manual

Datakom
Datakom DKM-407 User manual

Datakom
Datakom DKM-411 User manual

Datakom
Datakom DKM-409 User manual

Datakom
Datakom DKM-405 User manual
Popular Measuring Instrument manuals by other brands

Amprobe
Amprobe UDM45 user manual

Bms Bulut Makina
Bms Bulut Makina BULUMOUNT-3 Operational manual

Pilot Communications
Pilot Communications EGO700 Installation & operation manual

Vaisala
Vaisala M212551EN-B quick guide

Swan Electronics
Swan Electronics SWR-1 Instruction manuals

BEKA
BEKA BA418CF-F Installation & maintenance instructions