Installation and start up instructions
Stator Earth Fault Relay RMC-142D
uni-line
4189340158C (UK)
•
Earth fault protection: iE>> and iE>
•
Built-in filter for 3rd harmonic
•
LED indication of fault condition
•
Timer controlled tripping
•
LED indication for activated relay
•
35 mm DIN rail or base mounting
Page 2 of 2 Tel. (+45) 9614 9614 •Fax:(+45) 9614 9615 E-mail: deif@deif.com
Mounted current module
Scaling
1
(for adaption of the unit
to the measurin
g
current
)
Contact remains locked
in alarm position even though
the input returns to normal.
Latch circuit is reset by
disconnecting the supply voltage.
Distributor’s ID No.
Filled in by distributor
when customizing the unit.
Measuring current
corr. to 100% on scale
Supply voltage
Relay coupling
Shown is relay B as a
normally de-energised
relay, relay C as a
normally energised relay
with latch circuit
Type designation DEIF’s order ack. No.
To be stated when contacting DEIF
Highest voltage
in relation to earth.
Installation category
(E.g. time delay(s),
special calibration)
1. Description
This stator earth fault relay type RMC-142D forms part of a complete DEIF series (the
uni-line) of relays for protection and control of generators.
2. Label
The relay is provided with a label with the following data:
Note: The relay is provided with a 200 ms power-up relay, ensuring correct
function of the relay on connection of the auxiliary voltage. Normally
energised contacts (”NE”) are not activated (contact does not open/close)
until 200 ms after connection of the auxiliary voltage. Likewise, the relay is
provided with a 200 ms power-down circuit, ensuring supervision and
maintenance of any set point exceeding for 200 ms after disconnection of
the auxiliary voltage.
3. Mounting instructions
The RMC-142D is designed
for panel mounting, being
mounted on a 35 mm DIN
rail, or by means of two 4-
mm screws.
Weight: Approx. 0.600 kg
Installation and start up instructions RMC-142D
4189340158C (UK)
The design of the relay makes mounting of it close to other uni-line units possible,
however make sure there are min. 50 mm between the top and bottom of this relay and
other relays/units.
The DIN rail must always be placed horizontally when several relays are mounted on
the same rail.
4. Connection diagram
A 2A fuse may protect the auxiliary supply connection.
The relay is protected against ESD (electrostatic electricity), and further special
protection against this during the mounting of the relay is not necessary.
5. Start up instructions
5.1 Setting and indication
Setting of LED/relay
Earth current set point:
(10…110%) of In
Time delay: (0-T1)
0…1/0…5/0…10 s
IE>> Yellow LED is lit when the set point has
been exceeded, but the output contact
has not yet been activated.
The contact is activated and the red
LED is lit after the timer has expired.
Earth current set point:
(2…20%) of In
Time delay: (0-T2)
0…20/0…60/0…120 s
IE> Yellow LED is lit when the set point has
been exceeded, but the output contact
has not yet been activated.
The contact is activated and the red
LED is lit after the timer has expired.
At the factory the time delays are set according to the order specifications.
Page 4 of 4 Tel. (+45) 9614 9614 •Fax:(+45) 9614 9615 E-mail: deif@deif.com
Normally the settings of the RMC-142D are selected to ensure optimum protection of
the voltage source (generator, transformer, line), however without causing unwanted
disconnections.
Unwanted disconnections may occur in installations based on 3 or 4 CTs with the
secondary windings coupled in parallel. In connection with a short circuit between 2
phases, the short circuit current arising thereby may get so high that a differential
signal occurs because of the different saturation characteristics of the applied CTs.
In order to avoid this, the disconnection limit must be selected with due consideration
of the characteristics of the applied CTs. Alternatively a cable transformer must be
applied instead of 3 (4) current transformers.
RMC-142D is provided with a special filter suppressing the harmonic currents. This
filter suppresses the 3rd harmonic 18db (8 times), so that the latter does not influence
the measurings. However, in certain cases the 3rd harmonic is so high that the
disconnection limit must be set accordingly.
If shortest possible time delay is selected (50 ms), unwanted disconnection may occur
during synchronisation caused by a pulse signal which may be transmitted in
connection with the switching on of the voltage source and unbalance of the applied
CTs (saturation).
In order to avoid this, connection of the auxiliary voltage to the relay in connection with
the switching on of the voltage source is recommended.
The built-in power-up circuit (200 ms) will then ensure that the relay is not activated
until 200 ms after switching on the voltage source.
6. Technical specifications
Frequency range: 40…50/60…70Hz
Max. input current: 4 x In, continuously,
20 x Infor 10 s (max. 75A)
80 x Infor 1 s (max. 300A)
Load: Max. 0.3VA per phase
Relay contact: 2 changeover switches
Contact rating: 250V-8A-2000A (AC), 24V-8A-200W (DC)
Response time: <50 ms
Galv. separation: Between input, output and aux. supply: 3250V-50Hz-1 min.
Consumption: (Aux. supply) 3.5VA/2W

This manual suits for next models

1

Other Deif Relay manuals

Deif MVR-200 Series User manual

Deif

Deif MVR-200 Series User manual

Deif MDR-2 User manual

Deif

Deif MDR-2 User manual

Popular Relay manuals by other brands

ADEMCO 4204 - Ademco/ Relay Module installation instructions

ADEMCO

ADEMCO 4204 - Ademco/ Relay Module installation instructions

HK Instruments DPI Series installation instructions

HK Instruments

HK Instruments DPI Series installation instructions

macromatic CAP Series installation instructions

macromatic

macromatic CAP Series installation instructions

Siemens SIRIUS 3RA2811 Original operating instructions

Siemens

Siemens SIRIUS 3RA2811 Original operating instructions

Vega SI-12 user manual

Vega

Vega SI-12 user manual

FANOX SIA-F Series Installation & commissioning guide

FANOX

FANOX SIA-F Series Installation & commissioning guide

macromatic PMP Series installation instructions

macromatic

macromatic PMP Series installation instructions

BECKWITH ELECTRIC SYNCROCLOSER M-0188A Instruction book

BECKWITH ELECTRIC

BECKWITH ELECTRIC SYNCROCLOSER M-0188A Instruction book

ZIEHL STW1K operating manual

ZIEHL

ZIEHL STW1K operating manual

Emirel W 04N quick start guide

Emirel

Emirel W 04N quick start guide

Siemens 3TK2856 Original operating instructions

Siemens

Siemens 3TK2856 Original operating instructions

Leviton EZ-Max Plus Programming guide

Leviton

Leviton EZ-Max Plus Programming guide

Rockwell Automation Allen-Bradley 193-T1D P Series Installation instruction

Rockwell Automation

Rockwell Automation Allen-Bradley 193-T1D P Series Installation instruction

ZIEHL MS220VA operating manual

ZIEHL

ZIEHL MS220VA operating manual

Eaton ZEB Series manual

Eaton

Eaton ZEB Series manual

Moeller EASY 412-DC Series Training guide

Moeller

Moeller EASY 412-DC Series Training guide

Taco SR501-HC-4 instruction sheet

Taco

Taco SR501-HC-4 instruction sheet

Siemens 3RB22 Commissioning instructions

Siemens

Siemens 3RB22 Commissioning instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.