Warning
Please read this instruction carefully before use.
Switch off the power before wiring.
The display panel of TP04 series is waterproof. But please prevent grease, corrosive liquids and sharp objects from
contacting the TP04 series.
The TP04 series require 24VDC input power. DO NOT connect input AC power supply to any of the RS-485
communication port; otherwise serious damage may occur. Check all the wiring again before switching on the
power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after
the power is switched off.
Make sure the groud terminal is correctly grounded in order to prevent electromagnetic interference.
Please use the fixed support accessory which is packed together with the product provided by Delta. DO NOT
tighten the screws out of the normal torque specifications; otherwise serious damage may occur.
Introduction
Model Explanation
Thank you for choosing Delta TP Series. TP04G-AS2 has the features of high resolution 128×64 dots and is
able to display 8×4 Chinese character. It provides multilingual display and two built-in communication ports, one
is for RS-232/RS-422 and the other is for RS-485. RS-232 and RS-485 can be used simultaneously. Besides, it
also supports built-in RTC, communication/alarm LED indicators. The user can purchase program copy card
(optional) to copy settings and programs quickly and save download time. Regarding the editing software, there
are various objects and images for the user’s requirements.
Product Outline
RS- 485/ RS4 22 LED In dica tor
Arr ow Keys
En ter Key
Fu ncti on Ke ys
Dis play ing A rea
Es cape / E xit Ke y
Sh ift Key
Panel Function Explanation
Panel component Explanation
Alarm LED indicator
(RED)
Status 1: When power is on, LED will start to blink slowly
Status 2: When there is an abnormal situation, LED will blink quickly along with an alarm sound.
RS-232 LED
indicator (yellow) LED will blink when transmits program and comm unicates via RS-232.
RS-485/RS-
indicator (green) LED will blink when communicates via RS-485/RS-422.
Displaying area Liquid Crystal Module display area. It is used to display current program status.
Escape/Exit key It is used to cancel an incorrect input, or to exit a programming step.
Shift key It is used to select function keys F0 ~ F9 and other keys for special function.
Arrow keys
UP/Pg Up: It is used to increase the value or move up one page.
Pg Dn/DOWN: It is used to decrease the value or move down one page.
Left: This key is left direction key and it can be used to select the position of the value.
Right: This key is right direction key and it can be used to select the position of the value.
Enter key It is used to input a value or accept a programming command.
Function keys
F0/F5: It is used to be constant 0 (F0) and 5 (Shift+F0) when it is in the system menu, the user
can use it to define functions separately when they are in user page.
F1/F6: It is used to be constant 1 (F1) and 6 (Shift+F1) when it is in the system menu, the user
can use it to define functions separately when they are in user page.
F2/F7: It is used to be constant 2 (F2) and 7 (Shift+F2) when it is in the system menu, the user
can use it to define functions separately when they are in user page.
ENGLISH
Panel component Explanation
Function keys
F3/F8: It is used to be constant 3 (F3) and 8 (Shift+F3) when it is in the system menu, the user
can use it to define functions separately when they are in user page.
F4/F9: It is used to be constant 4 (F4) and 9 (Shift+F4) when it is in the system menu, the user
can use it to define functions separately when they are in user page.
Back Panel
BATTERY
SWITCH OR
RS-485/422
5 PIN terminal/Wire gauge: 12-24 AWG/Torque: 4.5 lb.-inch
Dimension
Front panel (unit: mm [inch]) Right side diagram (unit: mm [inch])
97.00
[3.82]
147.00 [5.79]
85.00
[3.35]
Mounting dimension (unit: mm [inch]) Vertical view (unit: mm)
Thickness Range 0.5~9mm
135~136.5[5.31~5.37]
85
[3.35]
Installation
Please insert TP04 series to the opening hole of panel and tighten the screws. However, if a firm mounting
TP04 series to the panel is needed, please use the mounting fixed support accessory which is packed together
with TP04 series, then insert the fixed support in the back and tighten the screws.
If the fixed support is not installed well, Delta will not guarantee the waterproof function. The screw torque
should be 4-5(kg-cm). DO NOT exceed this specification when tightening the screws; otherwise TP04 series
may be damaged.
Notes: The flat surface should be a UL Type 4 "Indoor Use Only" enclosure or equivalent (IP65/NEMA4). Please refer to
the figures below.
Thi ckne ss: 0.5 ~9.0m m
Pl ease le ave su ffic ient sp ace (m ore th an 50mm )
ar ound t he un it for hea t dis sipa tion .
Specifications
Function Specifications
Item TP04G-AS2
Screen type STN-LCD
Display color Monochromatic
Backlight The back-light automatic turn off time is 1 ~ 99 minutes (0 = DO NOT turn off)
(The back-light life is about 50 thousand hours at 25°C)
Resolution 128x64 dots
Display range (W) x (H) = 72 x 40 (unit: mm); 3.00” (diagonal preferred)
Contrast adjustment 10 levels of adjustment
Language/Font
ASCII: (Code page 850) Alphanumeric (including European characters)
Taiwan: (Big 5 codes) Traditional Chinese Fonts
China: (GB2324-80 codes) Simplified Chinese Fonts
5×8 dots 25 characters×8 rows
8×8 dots 16 characters×8 rows
8×12 dots 16 characters×5 rows
text
8×16 dots 16 characters×4 rows
Font Size ASCII: 5×8, 8×8, 8×12, 8×16
Alarm LED indicator (RED)
1. Power on indication (Blink for three times); 2. Communication error alarm;
3. Special indication by user programming.
RS-232 LED indicator
(yellow) It will blink when transmitting program and communicating by using RS-232.
Display
screen
RS-485/RS-422
LED indicator (green) It will blink when communicating by using RS-485/RS-422.
Program memory 256KB flash mem ory
RAM of system 32K Byte
Serial communication port
RS-232 (COM1)
Unsynchronized transmission method: RS-232;
Data length: 7 or 8 bits, Stop bits: 1 or 2 bits; Parity: None/Odd/Even;
Transmission speed: 9,600 bps ~ 115,200 bps; RS-232: 9 PIN D-SUB male.
Extension communication
port RS-422 (COM1)
RS-485 (COM2)
Unsynchronized transmission method: RS-485 / RS-422; Data length: 7 or 8 bits;
Stop bits: 1 or 2 bits; Parity: None/Odd/Even; Transmission speed: 9,600 bps ~
115,200 bps; RS-422: 9 PIN D-SUB male; RS-485: 5 PIN removal terminal.
Extension interface 1. Update firmware version. 2. The slot for program copy card.
Battery cover 3V DC battery for HMI
External
interface
5 PIN removal terminal Include 24V DC input and RS-485 communication input
Electrical Specifications
Specifications TP04G-AS2
Communication interface COM1: RS-232/RS422; COM2: RS-485.
Waterproof class of front panel IP65/NEMA4
Operating tem perature for hardware
0 ~ 50°C; 20 ~ 90% RH (non-condensing)
Storage temperature for hardware -20 ~ 60°C
Vibration 5Hz
≦
f
<
9Hz = Continuous: 1.75mm/Occasional: 3.5mm
9Hz
≦
f
≦
150Hz = Continuous: 0.5g/Occasional: 1.0g
Shock 15g peak, 11ms duration, half-sine, three shocks in each direction per axis,
on 3 mutually perpendicular axes (total of 18 shocks)
Radiated emission CISPR11, Class A
Electrostatic discharge immunity EN61000-4-2
Radiated immunity EN61000-4-3
Electrical fast transient EN61000-4-4
Weight/dimensions 0.24kg; 147×97×35.5mm (Width(W)×Height(H)×Deep(D))
Cooling method Natural air cooling
Password Function
1. If the user forgot the password, the password can be cleared by using the following code: 8888. This
universal code will clear the password and all TP04 series internal programs. The TP04 series will be reset to
the factory settings by using this code also. Please pay close attention when using it.
2. The password can be the alphabet from A to Z or the number from 0 to 9. But it must use the function keys F0
~ F9 to input the password characters. Please refer to the following table.
F0/F5: Scrolls in a loop as follows 0→5→A→B→C→D→E→F→0
F1/F6: Scrolls in a loop as follows 1→6→G→H→I→J→K→1
F2/F7: Scrolls in a loop as follows 2→7→L→M→N→O→P→2
F3/F8: Scrolls in a loop as follows 3→8→Q→R→S→T→U→V→3
F4/F9: Scrolls in a loop as follows 4→9→W→X→Y→Z→4
Hardware Operation
When the user wants to startup TP04 series, a 24V DC power is needed. After applying 24V DC power to
TP04 series, it will enter into the startup display and then enter the user-designed program. Pressing Esc key
and holding on for 5 seconds can return to system menu. There are five selections in the system menu and
are described below.
Selections Explanation
Download program
Use the connection cable (DVPACAB530) to connect the TP04 serial communication port RS-
a PC. Then use the TPEditor software to download an application program to TP04.
Upload program Use the connection cable (DVPACAB530) to connect the TP04 serial communication port RS-
a PC. Then use the TPEditor software to upload an application program from TP04.
Copy program
Transfer a program between two TP04 units.
1: transmit programs. 2: receive programs
When transmit programs and data between two TP04 units. Set one TP04 to “Receive Program”
mode and the other TP04 to “Transmit Program” mode. Please use twisted pair wires to conne
two units via the RS-485 ports.
TP04 settings
There are 9 items that used to modify TP04 system settings:
1. Communication protocol: Setting the address of TP04, the control port of PLC, and the
communication string for either RS-232 or RS-485.
2. Contrast: Adjust the contrast of LCM display screen.
3. Back-light: adjust the automatic turn off time of LCM. Setting range is 00 ~ 99 minutes. If set to
00, the LCM Back-light will not turn off.
4. Date and Time: It is used to set the TP04 built-in RTC including year, month, day, hour, minute,
second and week. Also the internal battery capacity display is shown here.
5. Buzzer: Used to set the buzzer sound, normal mode or quiet mode.
6. Language Setting: Used to set the displayed language. English, Traditional Chinese, Simplified
Chinese or user defined language.
7. Password setting: Used to set, enable, and disable the password function. If the password
function is enabled, it will require the user to input a password before entering any system menu.
The factory password is 1234.
8. Startup display: Used to select the TP04 startup display. User can select “user defined”
file that designed by TPEditor and download to TP04.
9. Comm. indicator: The user can determine if the RS-232 and RS-
485 LEDs will blink or not during
communication.
PLC connection
There are three m ethods to connect to PLC:
1. Using TP04 serial communication port (COM1) RS-232: set 8-pin DIP switch to RS-485 mode
and connect the cable (DVPACAB215 or DVPACAB230) to program communication I/O
RS-232C of PLC.
2. Using extension communication port (COM2): set 8-pin DIP switch to RS-
5-pin removal terminal of extension communication port to RS-485 of PLC with twisted pair.
3. Using extension communication port (COM2): set 8-pin DIP switch to RS-422 mo
four pins (6, 7, 8, 9) of 9 PIN D-SUB male to RS-422 of PLC with 4-wire cable.
Execution
Execute the internal program that download from TPEditor or transm itted from other TP04 units.
When program is in execution, the user can return to system menu by pressing Escape/Exit (Esc)
key for 5 seconds.
Communication Connection
TP04G may connect to a PC by using connection able DVPACAB515
TO P C (RS-2 32) TO TP0 2 / 04G
9 P IN D-S UB femal e
Rx 2
GND 5 5 GND
PC C OM Port
9 P IN D-S UB fe male
3 Tx
2 Rx
TP0 2 / 04G COM P ort
Tx 3
TP04G may connect to a DVP-PLC by using connection cable DVPACAB215/DVPACAB230/
DVPACAB2A30
1. DVPACAB215/DVPACAB230
1
13
14
1
5
6
9
25 P IN D- SUB
9 PIN D-S U B
TO P LC
MI NI DI N TER MI N AL
TO P LC
MIN I DIN TE RMIN AL
PC / T P CO M Po rt PLC C OM1 Por t
Tx 2
GND 7
8 PIN M INI DIN9 PIN D- SUB fe male
PC /T P COM Port P LC COM 1 Port
Rx 2
GND 5
6
8
20
4
5
1
4
6
7
8
1,2 5 V
5 Tx
The Pin definition of 9 PIN D-SUB
1. RS-232
3 T x
5 GN D
RS -23 2 9 P IN D-S UB mal e
TP 02 / 04G C OM Po rt
2 R x
2. RS-422
8 Tx +
RS -422 9 P IN D-S UB ma le
9 Tx -
TP 02 / 04G C OM Po rt
7 Rx -
6 Rx +
3. DVPACAB630 (RS-422)
8 PI N MIN I DIN
9 PI N D- SUB f emal e
TP 02 / 04G CO M Port M IT SU BI S HI F X-P L C
1
2
x -
Tx - 9 1 R x -
Switch between RS-422/RS-485 (by using 8-PIN DIP switch)
8-PIN DIP switch RS-485 RS-422
SW1 ~ SW4 On Off
SW5 ~ SW8 Off On
Battery Life and Precision of Calendar
Timer
Battery Life
Temperature (°C)
-20 0 20 60
Life (Year) 1.972
Precision of Calendar Timer
1. At 0°C/32°F, less than -117 seconds error per month.
2. At 25°C/77°F, less than 52 seconds error per month.
3. At 55°C/131°F, less than -132 seconds error per month.
注意事項
請在使用之前,詳細閱讀本使用說明書。
實施配線,務必關閉電源。
本機顯示操作 板防水,但對油污或具腐蝕性之液體不具防護作用,避免以尖銳之物品刮傷 板使用時請注
意。
本機輸入電源為直流
24V
,不可連接於
RS-485
通訊口信號端,否則可能造成嚴重的損壞,因此請在上電之前
再次確認電源配線。
輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。請勿在上電時觸摸任何端子。
本體上之接地端子
務必正確的接地,可提高產品抗雜訊能力。
利用原廠包裝附件之固定架,鎖緊 板固定螺絲時,請勿太緊以免造成機殼損壞。
產品簡介
型號說明
謝謝您採用台達終端顯示器系列產品。
TP04G-AS2
,解析度
128*64
,最大可顯示
8*4
個中文字,支援多國
文字顯示。
建兩個通訊口
(RS-232
及
RS-485/RS-422
,可同時使用
)
。
建萬年曆、通訊
/
警告指示
LED
。
可外接程式複製單元,快速移植程式,節省程式下載時間。
建多種物件圖形可供使用者選用。
產品外觀及各部介紹
LC M
顯示區
數值鍵及功能鍵
輸入鍵
警示指示燈
RS -4 85
指示燈
複合功能鍵
面版功能說明
面板元件
說明
警示指示燈
(
紅燈
)
狀態一:當啟動電源時,指示燈慢慢開始閃爍。
狀態二:當異常狀態 生,指示燈會重覆持續亮一秒並 出警報聲。
RS-232
指示燈
(
黃燈
)
傳送程式及使用
RS-232
通訊時持續閃爍。
RS-485/RS-422
指示燈
(
綠燈
)
使用
RS-485/RS-422
通訊時持續閃爍。
LCM
顯示區
液晶顯示模組,顯示目前程式狀態。
退出
/
取消鍵
進入系統選單或輸入值錯誤時可按此鍵,刪除文字敘述等。
命令操作鍵
UP/Pg Up
:此鍵為向上方向鍵,可作為數值遞增輸入或換至上頁等操作。
Pg Dn/DOWN
:此鍵為向下方向鍵,可作為數值遞減輸入或換至下頁等操作。
Left
:此鍵為左方向鍵,可作為選擇數值位置操作。
Right
:此鍵為右方向鍵。可作為選擇數值位置操作。
複合功能鍵
此鍵是搭配功能鍵
F0 ~ F9
及其他按鍵作為特殊功能的使用。
輸入鍵
當輸入值確認正確無誤時,即可按下此鍵。
功能鍵
F0/F5
:在系統選單操作時可作為
0 (F0)
或
5 (Shift+F0)
的常數輸入鍵,在使用者頁面時可
由使用者定義其個別功能。
F1/F6
:在系統選單操作時可作為
1 (F1)
或
6 (Shift+F1)
的常數輸入鍵,在使用者頁面時可
由使用者定義其個別功能。
繁體中文
面板元件
說明
功能鍵
F2/F7
:在系統選單操作時可作為
2 (F2)
或
7 (Shift+F2)
的常數輸入鍵,在使用者頁面時可
由使用者定義其個別功能。
F3/F8
:在系統選單操作時可作為
3 (F3)
或
8 (Shift+F3)
的常數輸入鍵,在使用者頁面時可
由使用者定義其個別功能。
F4/F9
:在系統選單操作時可作為
4 (F4)
或
9 (Shift+F4)
的常數輸入鍵,在使用者頁面時可
由使用者定義其個別功能。
背面介紹
BATTERY
SWITCH OR
RS-485/422
5 PIN
端子座
/
線徑:
12-24 AWG /
扭力:
4.5 lb.-inch
外觀尺寸
正面圖
(
單位:
mm
,
[ ]
:
inch)
右側圖
(
單位:
mm
,
[ ]
:
inch)
97.00
[3.82]
147.00 [5.79]
85.00
[3.35]
嵌入開孔尺寸
(
單位:
mm
,
[ ]
:
inch)
俯視圖
(
單位:
mm)
135~136.5[5.31~5.37]
85
[3.35]
0.5~ 9mm
厚度:
安裝方法
人機介面安裝於控制盤的方法,請直接將人機由盤面的正面直接放入即可
(
嵌入式
)
,若要固定更牢固,可再利用
原廠包裝附件之固定架,嵌入後蓋直接四端凹槽處固定,並上、下平均鎖緊面板固定螺絲即可,如下圖為正確安
裝:(
固定螺絲時請以扭力:
4-5 (kg-cm)
鎖緊,請勿超過此範圍以免破壞面板)
注意:該安裝的平 必須是要適用
Type 4
室內使用或相等條件的配電盤外殼。
嵌入 式
隔板 厚度:
0.5~9 .0mm