CliQ II DIN Rail Power
Supply
24 V 60 W 1
Phase
/ DRP024V060W1B
□
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (September 2021, Rev. 11)
Specifications
Input Ratings / Characteristics
Nominal Input Voltage 100-240 Vac
Input Voltage Range 85-264 Vac
Nominal Input Frequency 50-60 Hz
Input Frequency Range 47-63 Hz
DC Input Voltage Range* 120-375 Vdc
Input Current < 1.40 A @ 115 Vac, < 0.80 A @ 230 Vac
Efficiency at 100% Load > 90.0% @ 115 Vac & 230 Vac
Max Power Dissipation 0% load < 0.5 W @ 115 Vac & 230 Vac
100% load < 7.4 W @ 115 Vac & 230 Vac
Max Inrush Current (Cold Start) < 20 A @ 115 Vac, < 35 A @ 230 Vac
Leakage Current < 1 mA @ 240 Vac
*Safety approval according to IEC/EN/UL 60950-1 and IEC/EN/UL 62368-1.
Output Ratings / Characteristics**
Nominal Output Voltage 24 Vdc
Factory Set Point Tolerance 24 Vdc ± 2%
Output Voltage Adjustment Range 24-28 Vdc
Output Current 2.50 A (continuously operating at 24 V)
3.75 A (Power Boost for 5 seconds at 24 V, refer to the details
in the Functions section)
Output Power 60 W (continuously operating at 24 V)
90 W (Power Boost for 5 seconds at 24 V
, refer to the details in
the Functions section)
Line Regulation < 0.5% (@ 85-264 Vac input, 100% load)
Load Regulation < 1.0% (@ 85-264 Vac input, 0-100% load)
PARD*** (20 MHz) < 150 mVpp
Rise Time
< 100 ms @ nominal input (100% load)
Start-up Time < 2,000 ms @ nominal input (100% load)
Hold-up Time > 20 ms @ 115 Vac,
> 125 ms @ 230 Vac (100% load)
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264 Vac input, 0-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 50 Hz to 1 KHz)
Start-up with Capacitive Loads 8,000 µF Max
**For power de-rating from 50°C to 80°C, see power de-rating on page 3.
***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.