
12
PQC Series Active Power Filter
Chapter 3 : Installation and Wiring
The APF is applicable to many applications and can meet the particular installation requirements of
industrial sites, power distribution rooms and IT data centers. According to different work conditions
and environment requirements, the fixed-type module can be installed in a customized cabinet or
standard cabinet, and exible conguration and on-site capacity expansion can be realized based on
the current and subsequent capacity requirements.
3.1 Pre-installation Conrmation
Since the installation environment varies for different users, please be sure to read this
Manual carefully before installation. All installation, assembly and start-up work must be
carried out by the qualified professional personnel. If the work is to be carried out by the
customer, it shall be under the supervision of the qualied professional personnel. When a
forklift or similar lifting equipment is used to handle the device, make sure the lifting capacity
is sufcient. Please refer to Table 2-2 for the APF weight.
3.2 Installation Environment
1. The APF device can only be installed indoors. Do not install the device for outdoor use.
Be sure to consider the IP21 protection degree of the device while installing. For a higher
protection degree requirement, please contact the distributor.
2. The APF device shall not be installed in a place close to dust sources or subject to heavy
environmental pollution. Because the conductive dust will damage the device, make sure
the installation place is free of conductive dust.
3. Make sure the transport route and placement location are firm and big enough to
accommodate the APF system cabinet and forklift.
4. Since some noise can be generated during the operation of the APF, please take the noise
effects into account when choosing the installation position.
5. Keep the installation area clean. Please note that wiring routes must be hermetic to
prevent possible damage from rodents.
6. Make sure enough space is left in the installation place for future maintenance. For the
purpose of ventilation, avoid installing the APF against the wall. A space of 1500mm shall
be left in front of the device for front operation, maintenance and wiring.
7. Since some heat can be generated during the operation of the APF, please make sure the
cooling system of the installation environment is sufcient for heat dissipation, so that the
ambient temperature will not exceed the normal working temperature of the device.
8. The device is equipped with cooling fans, and is designed with air inlet in the front and air
outlet at the back; thus, it is recommended to leave at least a 500mm space both at the
front and the back for ventilation purpose. Figure 3-1 and Figure 3-2 illustrate the air inlet