DencoHappel MATRIX OP21C User manual

OPERATION MANUAL
Controls and Regulation
DencoHappel MATRIX®Control Panel with Display
Regulate efficiently, conserve resources

MATRIX control panel
2PR-2011-0110-GB • Subject to modifications • R9-03-2016
Table of contents
1 Overview of units and packaged content . . . . . . . . . . . . . . . . . . . . . 4
1.1 Using MATRIX control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Packaged content . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 About this Operation Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 Availability of the operation manual . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Scope of the operation manual . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Used symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Identification of safety instructions . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 Safety-conscious work procedures . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Proper use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Modifications and changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.5 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.6 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.7 Selection and qualification of personnel . . . . . . . . . . . . . . . . . . 11
4 Technical Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1 Product features and functions . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2 Models of MATRIX control panels . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Technical data and accessories . . . . . . . . . . . . . . . . . . . . . . . . . 14
5 Assembly and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.1 Planning of mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.2 Mounting MATRIX OP50x/51x control panels . . . . . . . . . . . . . . 17
5.3 Integration of MATRIX BSZ circuit board . . . . . . . . . . . . . . . . . . 19
5.4 Mounting MATRIX OP50x/51x control panels . . . . . . . . . . . . . . 22
5.5 Cable recommendations MATRIX.Net . . . . . . . . . . . . . . . . . . . . 23
5.6 Dismantling MATRIX OP50x/51x control panel . . . . . . . . . . . . . 23
6 Commissioning and testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.1 Factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.2 Setting Group Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6.3 MATRIX.Net termination setting . . . . . . . . . . . . . . . . . . . . . . . . 26
6.4 Closing MATRIX control panel . . . . . . . . . . . . . . . . . . . . . . . . . . 26
6.5 Testing operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7 Operating MATRIX control panel . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.1 Overview of the operating elements . . . . . . . . . . . . . . . . . . . . . 28
7.2 The menus in overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
7.3 Home and information screen . . . . . . . . . . . . . . . . . . . . . . . . . . 30

MATRIX control panel
PR-2011-0110-GB • Subject to modifications • R9-03-2016 3
7.4 Basic operation using the display . . . . . . . . . . . . . . . . . . . . . . . 34
7.5 “Setpoint room temperature” menu
(basic display 1 – alternatively to basic display 2) 38
7.6 “Setpoint supply-air temperature” menu (basic display 2 – alternati-
ve to basic display 1) 39
7.7 Settings for fan speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.8 “Fan mode” menu setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.9 Menu setting „Plant/fan“ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7.10 “Operating mode” menu setting . . . . . . . . . . . . . . . . . . . . . . . . . 43
7.11 “Controller mode” menu setting . . . . . . . . . . . . . . . . . . . . . . . . . 44
7.12 Menu "Secondary-air louvre" . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
7.13 Menu setting "Louvre angle offset " . . . . . . . . . . . . . . . . . . . . . . 45
7.14 Menu setting "MA damper position" . . . . . . . . . . . . . . . . . . . . . 46
7.15 Menu setting "Outside-air volume flow" . . . . . . . . . . . . . . . . . . . 46
7.16 “Outside air automatic” menu setting . . . . . . . . . . . . . . . . . . . . 46
7.17 “FOS Test” menu setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.18 “Fast ventilation” menu setting . . . . . . . . . . . . . . . . . . . . . . . . . 46
7.19 Menu values "Basic ventilation" . . . . . . . . . . . . . . . . . . . . . . . . 47
7.20 Menu room air flow (SWIRL-function) . . . . . . . . . . . . . . . . . . . . 47
7.21 Menu "additional menus" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
8 Maintenance, Cleaning and Troubleshooting . . . . . . . . . . . . . . . . . 82
8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.3 Operation messages and troubleshooting . . . . . . . . . . . . . . . . . 82
9 Menu Structure OP5xx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
10 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
11 Drilling Templates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
11.1 Unit version OPxxC (IP 20) . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
11.2 Unit version OPxxI (IP 54) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Copyright note
Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly prohi-
bited without express prior consent. Violations entail liability for any damages or other liability arising. All rights in
relation to patents, utility patents or design patents are reserved.

Overview of units and packaged content MATRIX control panel
4PR-2011-0110-GB • Subject to modifications • R9-03-2016
1 Overview of units and packaged content
OP21C and OP31C OP30C and OP20C
OP44C OP50C
OP51C Optional: Unit cover OPD.C (not OP5xC)

MATRIX control panel Overview of units and packaged content
PR-2011-0110-GB • Subject to modifications • R9-03-2016 5
OP21I and OP31I OP30I
OP44I OP50I
OP51I Optional: Unit cover OPD.I (not OP5xI)

Overview of units and packaged content MATRIX control panel
6PR-2011-0110-GB • Subject to modifications • R9-03-2016
1.1 Using MATRIX control panels
In combination with the MATRIX controllers, the MATRIX control panels let you
specify setpoint values for the room air conditioning as well as the display of sta-
tus and error messages. The features are summarized as follows:
The assignment of...
– setpoints such as room or supply air temperature
– fan operating modes such as automatic operation
– operating modes of the unit, such as day-night operation
– switching times
– system parameters
The display of...
– actual values
– unit status
– error messages
1.2 Packaged contentMATRIX OPxxC control panel:
–Control panel for flush-mounted socket installation (protection type IP20)
consisting of a front panel and a mounting plate
–Operation manual – document comprising all relevant instructions
MATRIX OPxxl control panel:
–Control panel for surface mounting (protection type IP54)
consisting of a front panel and a mounting plate, including surface-mounted
socket with cable entry through membrane grommets
–Sensor type 903.454 (IP54), R=10 kOhm/25 °C
–Operation manual – document comprising all relevant instructions

MATRIX control panel
PR-2011-0110-GB • Subject to modifications • R9-03-2016 7
Fig. 1-1: DencoHappel product range

About this Operation Manual MATRIX control panel
8PR-2011-0110-GB • Subject to modifications • R9-03-2016
2 About this Operation Manual
2.1 Availability of the operation manual
The current operation manual provides important instructions on the safe and cor-
rect handling of the MATRIX control panel.
This operation manual applies to operators, building technicians, technical per-
sonnel or instructed persons as well as electricians.
Thisoperationmanualmustbeatalltimesavailableatthelocationofthe MATRIX
control panel. When working on the MATRIX equipment, observe all instructions
and precautions in the current operation manual.
2.2 Scope of the operation manual
This operation manual provides information about the following:
– Assembly/disassembly
– Installation
– Commissioning and testing
–Operation
– Maintenance and troubleshooting
2.3 Used symbols
The following symbols are used to highlight particular text sections in this opera-
tion manual:
– This symbol is used to indicate normal lists.
•This symbol indicates instructions to follow.
9The result of an action is indicated with this symbol.
NOTICE!
Additional information aboutusing the MATRIX control panels is specified here.

MATRIX control panel Safety
PR-2011-0110-GB • Subject to modifications • R9-03-2016 9
3 Safety
The MATRIX control panel is manufactured in accordance with the state-of-the-
art engineering standards and established technical safety codes and regula-
tions.
The MATRIX control panels are for use intended by the manufacturer. Ensure
proper and reliable operation of the unit before use. Observe all relevant safety
instructions and precautions in the operation manual. Use proper safety mea-
sures to prevent hazardous situations which, if not avoided, could result in death
or serious injury to the user or property damage-only accidents!
Have all faults repaired by an authorized specialist without delay!
3.1 Identification of safety instructions
The following symbols and notices are provided in appropriate places throughout
this document to designate the safety instructions.
3.2 Safety-conscious work procedures
Observe the following instructions when carrying out installation, adjustment or
repair work:
When carrying out work near low-voltage networks
When carrying out adjustment work on the MATRIX control panel
ELECTRICAL HAZARD!
This symbol indicates a risk of electric shock when working on the equipment.
RISK OF ELECTROSTATIC DISCHARGE!
This symbol precedes a warning on static-discharge damage to the MATRIX
control panels.
DAMAGE TO THE UNIT!
This section specifies procedures and precautions for preventing damage to
the MATRIX control panels.
PERSONAL INJURY!
This section specifies procedures and precautions for preventing personal
injury.
ELECTRICAL HAZARD!
Disconnect all electric power of the unit and ensure that the power cannot be
inadvertently switched on; earth, short-circuit, and block off all neighboring live
parts. Non-compliance can lead to death or serious injury.

Safety MATRIX control panel
10 PR-2011-0110-GB • Subject to modifications • R9-03-2016
For all kinds of work:
•Observe all assembly instructions for the MATRIX control panels.
•Fluctuations and imbalances in the supply voltage may not exceed the
tolerance limits specified in the technical data, otherwise functional failures
and limit states cannot be excluded.
3.3 Proper use
The MATRIX control panel is specifically designed for controlling air treatment
units manufactured by DencoHappel and depending on the equipment version,
regulating other units within a building automation system.
According to the hardware version, the MATRIX control panel is used:
– to assign setpoints for room temperature
– to assign setpoints for supply air temperature
– to select fan speed
– to assign operating mode (e.g. normal, economy mode)
– to assign controller operating mode (changing between heating and cooling)
– to set mixed-air or recirculating-air mode
– to perform regulation of remote building automation system, e.g. damper or
lighting control.
The MATRIX control panels are shipped in two protection types which protect the
unit against external effects:
Protection IP20
residential area – In protection type IP20 according to DIN EN 60529 for residential areas.
May only be used indoors; in this case - ensure that the unit is protected
against dust and other substances.
Protection IP54
industrial area – In protection type IP54 according to DIN EN 60529 for industrial areas.
The casing is dust-proof and protected against splash water.
Proper use also stipulates the observance of the current operation manual as well
as the inspection and maintenance intervals specified by DencoHappel.
Improper use Any use other than that described above is considered improper. The manufac-
turer/supplier is not liable for any damages arising from improper use. The user
alone bears the risk.
RISK OF ELECTROSTATIC DISCHARGE!
While carrying out adjustment work on the MATRIX control panel make sure
that you discharge yourself statically before manipulating PC boards and
installing electrical components.

MATRIX control panel Safety
PR-2011-0110-GB • Subject to modifications • R9-03-2016 11
3.4 Modifications and changes
It is not allowed to modify, add components, or convert the MATRIX control panel
in any way.
Any conversions or modifications as well as tampering with the unit or misappli-
cation of the MATRIX control panel will invalidate the CE conformity and void war-
ranty.
3.5 Spare parts
Only original DencoHappel spare parts are allowed, since DencoHappel is not lia-
ble if third-party spare parts are used.
3.6 Disposal
Equipment and operating supply materials must be disposed of according to the
material type in a safe and environmentally friendly manner.
3.7 Selection and qualification of personnel
Every person authorized to work on the MATRIX control panel must have read
theentireoperationmanual and understood it completely – especiallythechapter
on safety. Pleaseread this document fully before commencing any work, and not
while performing a task.
Electrical connections may only be carried out by qualified licensed staff or other
individuals with proper professional training and experience in the following ar-
eas:
– Regulations concerning health and safety in the workplace
– Accident prevention regulations
– Directives and recognized codes of practice
All skilled staff must be able to assess the entrusted work and be able to recog-
nize and avoid all associated dangers.
PERSONAL INJURY!
The MATRIX control panel may not be operated:
– in explosion risk areas
– in rooms with conductive dust
– in rooms with strong electromagnetic fields
– in rooms with aggressive atmosphere that attacks plastics, for instance.
... in protection type IP20 it may not be operated:
– in humid rooms
– in rooms with dust-laden air
... in protection type IP54 it may not be operated:
– in wet areas
– in areas with high dust content

Technical Description MATRIX control panel
12 PR-2011-0110-GB • Subject to modifications • R9-03-2016
4 Technical Description
4.1 Product features and functions
The MATRIX control panels are designed to control DencoHappel air treatment
units and are available in two types:
– Series OPxxC (Comfort) for normal environment (IP20) and
– Series OPxxI (Industry) for commercial/industrial environment (IP54).
Both series of control panels enable communication between the user and the
MATRIX control system.
OP5xx The OP5xx MATRIX control panels are equipped with MATRIX.Net bus, through
which communication with air treatment units is performed.
Display of OP5xx The MATRIX control panels with display enable a menu structure as plain text
from where users can directly access numerous functions of the DencoHappel
units. The menus are adapted dynamically according to the configuration of the
unit. Thus, menus are also available for access to remote systems such as
damper or lighting controls (only through MATRIX.LON).
NOTICE!
For further information about the MATRIX.Net refer to the operation manual of
the relevant air treatment unit.

MATRIX control panel Technical Description
PR-2011-0110-GB • Subject to modifications • R9-03-2016 13
4.2 Models of MATRIX control panels
Type
Equipment features
Setpoint assign-
ment Operating modes/control modes Unit connection Status display Other
Setting fan speed
Setting room tem-
perature
Normal and
economy mode
Circulating air or
outside-air mode
Heating only
Cooling only
Control of second-
ary louvre
Using
MATRIX.Net
Through parallel
wiring
Through LED
Through display
Integrated room
temperature sen-
sor
Integrated
clock timer
Network
interface
OP20C 99 9999
OP21C 999 9999
OP30C 99 9 999
OP31C 999 9 999
OP44C 9 99999 9 9 9 9
OP50C Menu guided through digital display; automatic
adjustment of menus to the unit equipment 9999
OP51C Menu guided through digital display; automatic
adjustment of menus to the unit equipment 99999
OP71C Menu guided through digital display; automatic
adjustment of menus to the unit equipment 9999
OP21I 999 99 9
OP30I 999 9
OP44I 9 999 99 9 9
OP50I Menu guided through digital display; automatic
adjustment of menus to the unit equipment 99 9
OP51I Menu guided through digital display; automatic
adjustment of menus to the unit equipment 9999
OP71I Menu guided through digital display; automatic
adjustment of menus to the unit equipment 9999

Technical Description MATRIX control panel
14 PR-2011-0110-GB • Subject to modifications • R9-03-2016
4.3 Technical data and accessories
Type series OPxxC (Comfort) OPxxI (Industry)
Area of application Comfort area Industrial area
Ambient conditions
Allowed ambient temperature 0 °C to 45 °C
Allowed storage temperature -10 °C to 65 °C
Allowed relative humidity 15% to 75% no condensation
Electromagnetic compatibility
Electromagnetic interference
(EMI) according to DIN EN 55022/DIN EN 61000
Electromagnetic interference
shielding (EMS) according to DIN EN 61000
Mechanical data
External dimensions (W/H/D) 83 x 135 x 30 mm 83 x 135 x 55 mm
Fixation directly on the wall or socket for flush
mounting on the wall
Weight 184 g 248 g
Casing material N185 Noryl UL 94 V-0
Casing front panel similar to RAL 9016 (traffic white) similar to RAL 7035 (light grey)
Casing rear section (if necessary
surface-mounted socket) similar to RAL 9016 (traffic white) similar to RAL 7016 (anthracite)
Pushbutton similar to RAL 7074 (telegrey 4) similar to RAL 7016 (anthracite)
Protection type (according to DIN
40050) IP20 IP54
Application position installed vertically installed vertically
Cable entry point from behind from behind via 3 membrane grommets
M16
Electrical data
Supply voltage Through power supply of the unit
Temperature sensor integrated room temperature sensor type 903.454
supplied loose
30 mm
135 mm
83 mm
83 mm 55 mm
135 mm

MATRIX control panel Technical Description
PR-2011-0110-GB • Subject to modifications • R9-03-2016 15
4.3.1 Accessory Items
Accessories OPxxI Sensor type 903.454
Mechanical data
External dimensions (W/H/D) 50 x 65 x 44 mm
Allowed ambient temperature -35 °C to 90 °C
Fixation on the wall
Weight 60 g
Casing color similar to RAL 9016 (traffic white)
Application position arbitrary
Protection type (according to DIN
40050) IP54
Electrical data
Resistance 10 kOhm/25 °C
Voltage U < 12 V AC/DC

Assembly and Installation MATRIX control panel
16 PR-2011-0110-GB • Subject to modifications • R9-03-2016
5 Assembly and Installation
5.1 Planning of mounting
Mounting MATRIX-
control panels/
room temperature sensor
* recommended
installation height = 1.5 m
ELECTRICAL HAZARD!
The electrical installation and (dis)assembly of the MATRIX control panel may
only be carried out by qualified electricians in compliance with the given oper-
ation manual and current VDE regulations.
•Before drilling, ensure that the drilling area is free from electrical cables and
pipes.
•Only indoor mounting of the MATRIX control panel is allowed.
•Do not connect the MATRIX control panel to an external voltage.
NOTE!
The installation site of the MATRIX control panel or room temperature sensor
is crucial for the precise measurement of room temperature.
Therefore the MATRIX control panels or sensors must:
– notbe fitted nexttodoors,windows,passages etc.,since intensemovement
of air can cause incorrect measurements,
– not be fitted on hot or cold walls (e.g. chimney, outside wall),
as wall temperature can cause incorrect measurements.
– not be fitted behind curtains or net curtains, since the insulating layers of air
can cause incorrect measurements,
– not befitted adjacent to unit discharge grilles as discharge temperature can
cause incorrect measurements
– not be fitted below cold surfaces like windows, since descending cold air
flow can cause incorrect measurements.

MATRIX control panel Assembly and Installation
PR-2011-0110-GB • Subject to modifications • R9-03-2016 17
5.2 Mounting MATRIX OP50x/51x control panels
5.2.1 Mounting MATRIX OP5xC (IP20) control panel
The casing of the MATRIX OP5xC (IP20) control panel is designed for on-wall
and flush-mounted sockets.
•Useascrewdrivertoreleasethefrontpanel(1)fromthe
mounting plate (2) on the bottom side of the MATRIX
control panel.
NOTICE!
Use the drilling template for the wall mounting of the MATRIX control panels
(see "Drilling Templates" on page 102).
Make sure that the mounting plate is not deformed during installation.
NOTICE!
When mounting the MATRIX control panels in a flush-mounted socket, espe-
cially hollow-wall socket, ensure that nothing can impede the correct measure-
mentof the room temperature.Toavoiddraught,provideappropriateinsulation
of the flush-mounted socket, if necessary.
If the controlpanel is mounted into a flush-mountedsocket, edges of themount-
ing plate may remain visible, which depends on the used socket and the way it
is mounted. If necessary, use paint, wall paper, orsimilar means to prepare the
installation surface.
It also possible to hide the visible edges of the mounting plate by using a wall-
lamp socket with a vertical mounting dimension (screw clearance) of 60 mm.
When tightening the fixing screws the mounting plate must belevel, flush-fitting
and is not deformed by tightening the screws.
1
2

Assembly and Installation MATRIX control panel
18 PR-2011-0110-GB • Subject to modifications • R9-03-2016
•Route the wires through the opening (1) in the mount-
ing plate (2) of the MATRIX control panel.
•Securethe mountingplateoftheMATRIXcontrolpanel
on the wall or flush-mounted socket.
5.2.2 Mounting MATRIX OP5xl (IP54) control panel
The casing of the OP5xI is suitable for installation on the wall. The wires are
routed through three membrane grommets from below.
•Useascrewdrivertoreleasethefrontpanel(1)fromthe
mounting plate (2) on the bottom side of the MATRIX
control panel.
Ensure that the mounting plate is not deformed.
•If required, unscrew the mounting screws from the
mounting plate (3) on the surface-mounted socket (1).
•Lift the mounting plate (3) away from the surface-
mounted socket (1).
•Adhere a gasket (2) on the bottom part of the mounting
plate (3).
1
2
1
2
2
1
3

MATRIX control panel Assembly and Installation
PR-2011-0110-GB • Subject to modifications • R9-03-2016 19
•Route the wires through the membrane grommets (1)
into the surface-mounted socket (2) of the MATRIX
control panel.
•Mount the surface-mounted socket on the wall.
•Route the wires through the opening in the mounting
plate (1) of the MATRIX control panel.
•Place the mounting plate (1) on the surface-mounted
socket (2) and screw the mounting plate (1) to the sur-
face-mounted socket (2).
•Pay attention that the new gasket is sealed correctly in
order to ensure the IP54 protection type!
1
2
1
2

Assembly and Installation MATRIX control panel
20 PR-2011-0110-GB • Subject to modifications • R9-03-2016
5.3 Integration of MATRIX BSZ circuit board
The MATRIX BSZ circuit board is an intermediate terminal to be used if two wires
are connected using one terminal in MATRIX OP5x (IP20 and IP54) control pan-
els (necessary for loop-through of the network).
5.3.1 Mounting MATRIX BSZ in the flush-mounted socket
•Usethegroovetobreakoffthebottompartofthecircuit
board and place it in the flush-mounted socket.
•Route the wires through the flush-mounted socket and
connect the bus cable (refer to 5.5 Cable recommenda-
tions MATRIX.Net) as follows:
Tab. 5-1: Terminal designation
•Use the supplied cable to connect the circuit board with
the terminals of the mounting plate of the MATRIX
OP5XC control panel, as illustrated in Table 5-1 on
page 20.
Groove
Klemme Signal
Supply voltage 95 GND
99 Vcc
MATRIX.Net 96 Low
98 High
NOTE!
A cable strap is used to provide cable
strain relief and shielding.
This manual suits for next models