
7. 1 95-86669
STARTU P
WARNINGS
1. DO NOT overshoot the setpoint of the unit by
more than 100ºF (55ºC). This could result in a
shift of the setpoint temperature.
2. DO NOT contact the sensing shell with
a heating device such as a soldering iron or
blowtorch, as this will damage the unit and cause
a shift of the setpoint temperature.
3.
Prior to performing any test, place the re panel
in Bypass/Inhibit to prevent actuation of deluge
systems or other output devices.
4. The heat detectors are hermetically sealed
and factory set, employing standard aluminum
test blocks at the temperatures listed in the
data sheet. A test kit with an aluminum block is
required as it simulates factory test equipment.
Heat transfer mediums such as liquid and air, or
test equipment including air, liquid or sand baths
are not recommended and should not be used for
testing purposes.
5. The calibration verication procedures pertain
to the heat detection element only.
6. While the detector is a repeatable device,
replacement is recommended should the unit be
subjected to the intense heat of a re.
VISUAL INSPECTION
The recommended maintenance procedure is to
perform a visual inspection in accordance with NFPA
72 guidelines, EN 54 practice, and/or other applicable
local requirements. During the visual inspection, verify
that the sensing shell is free of dents, dings or build-up
of foreign matter of any kind. If the shell is dented or
shows signs of any physical damage, the unit should
be replaced immediately. If the shell has been painted,
the unit should be replaced. If a build-up of dust has
accumulated on the unit, the unit may be cleaned with
a vacuum or damp cloth. Care should be used not to
damage the unit in any way.
DETECTOR OPERATION VERIFICATION
To verify the operation of individual detectors:
1. Remove power from the system.
2. Disconnect the detector from the system.
3. Connect an ohmmeter to the detector leads.
4. Apply heat evenly to the detector using an
appropriate heat source.
5. Verify that the internal contacts close.
6. Remove the heat immediately after activation.
7. Allow all detectors to cool.
8. Re-connect the detectors to the system.
9. Restore power to the system.
SYSTEM OPERATION VERIFICATION
When used with automatic fire extinguishing systems:
1. Place the fire panel in Bypass/Inhibit mode.
2. Heat the detector with an appropriate heat source.
3. The panel annunciator must change state to indicate
a successful detector test.
4. Remove the heat source from the detector.
5. Allow the detector to cool before resetting the panel.
6. When all detectors have been tested and have
cooled below the setpoint, reset the system.
7. Place the fire panel back into Normal mode.
MAINTENANCE
The Model HD detector is a repeatable device with
field proven reliability. Properly installed and applied,
the device offers reliable, economical performance.
Nonetheless, the units should be periodically checked
for proper operation, following the procedures
described in the Startup section of this manual. For
additional information regarding maintenance of the
detector, refer to the applicable standard.
CALIBRATION VERIFICATION
A special calibration test kit with a repeatable heat
source is required to accurately determine the
temperature setting of the detector. Please contact the
Det-Tronics factory for information regarding suitable
test kits.
CAUTION
Once the heat detector is exposed to ame, it
is recommended to replace it with a new unit to
maintain performance reliability.