
7.1 10 95-8242
INSTALLATION
IMPORTANT
The installation procedure described in this
manual is intended for wiring and programming
the standard R7404 Controller used with the
C7050B Detector. It is important to note that the
R7404 Controller is available with various operating
programs (EPROMs). This can affect the system
programming and/or terminal conguration of the
controller. Since the installation procedure and
application instructions vary with each model,
specic information is supplied in a separate manual
that is specic to the equipment being installed.
When installing any “special purpose” version of
the R7404 Controller, always use the manual that is
supplied with the controller in conjunction with this
manual. If a conict arises, follow the procedure in
the manual for the specic equipment involved.
Device Manual Form Number
R7404 with STAR Logic 95-8294
R7404 for Remote Surveillance System 95-8249
R7404 for Nuclear Surveillance System 95-8256
WIRING REQUIREMENTS
The wiring to the detector must be a shielded cable 22
gauge (0.643 mm diameter) minimum, with at least a
600 volt rms rating. If there are two detectors in a zone,
they may share a cable. If the detector leads are run in
conduit, the conduit must not be used for wiring from
other electrical equipment. Detectors can be located up
to 2000 feet (600 meters) from the controller.
Shielded cable is required for the “B” (signal) leadwires.
As with any field device, shielded cable for all wires
providesmaximumprotectionfromRFI/EMIsources.In
applications where the wiring cable is installed in conduit,
the conduit must not be used for wiring to other electrical
equipment.
Since moisture can be detrimental to electronic devices,
it is important that moisture not be allowed to come in
contact with the electrical connections of the system.
Moisture in the air can be trapped within sections of
conduit, therefore the use of conduit seals is required
to prevent damage to electrical connections caused by
condensation within the conduit. These seals must be
water-tight and explosion-proof and are to be installed
even if they are not required by local wiring codes. A seal
must be located as close to the detector as possible. In no
case should this seal be located more than 18 inches (46
cm) from the detector. If a conduit swivel is used, a seal
must be located between the detector and the swivel.
When local codes require an explosion-proof installation,
an additional seal is also required at any point where the
conduit enters a non-hazardous area.
When pouring a seal, the use of a fiberdam is required
to assure proper formation of the seal. The seals should
never be poured in temperatures that are below freezing,
since the water in the sealing compound will freeze and the
compound will not dry properly. Contamination problems
can then result when temperatures rise above the freezing
point and the compound thaws. The shielding of the cable
should be stripped back to permit the seal to form around
the individual leads, rather than around the outside of the
shield. This will prevent any siphoning action that might
occur through the inside of the shield.
It is recommended that conduit breathers also be used.
In some applications, alternate changes in temperature
and barometric pressure can cause “breathing,” which
allows the entry and circulation of moist air throughout the
detector and connected conduit. Joints in the conduit
system and its components are seldom tight enough the
prevent this “breathing.” Moisture in the air can condense
at the base of vertical conduit runs and equipment
enclosures, and can build up over a period of time. This
can be detrimental to electronic devices. To eliminate this
condition, explosion-proof drains and breathers should be
installed to automatically bleed off accumulated water.
Cable made specifically for harsh, salt-water environments
must be used in areas where high humidity or salt water
is a problem. In all cases, typical cable insulation
resistance should measure 100 megohms or more,
using a high voltage insulation tester (megohmmeter). If
cable resistance drops below 10 megohms, it should be
replaced immediately to avoid shorting.
IMPORTANT
Disconnect the detectors and controller before
applying a megohmmeter to the cable.
When using steel wire armored or mineral-insulated
copper-sheathed cables, select an approved gland with
a watertight compression stage and an overall gland
shroud for outdoor applications. A sealing washer must
be fitted between the gland and the conduit entry to
ensure IP66 rating.
NOTE
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies with
applicable regulations that relate to the installation
of electrical equipment in a hazardous area. If in
doubt, consult a qualied official before wiring the
system.