Pictures for illustrating purposes only 10
A fresh mains cold water service should be used to supply the
unit. The water pressure should be between 1 & 6 bars & should
not exceed 40°C in temperature.
The water supply connection is under the bottom of the unit. The
humidifier is delivered with a water inlet hose of 50 cm long with
a 3/4" female fitting to the cold water supply. A direct copper
connection is PROHIBITED.
A check valve should be located on the mains and cold wa-
ter service connection to the unit.
The inlet valve base has a basket filter (s.a. page 36).
The RTH humidifier uses water to produce steam so leaka-
ge may happen causing potential damage. If an installation
in false ceiling or above prime rooms (such as museum,
exhibition or laboratory rooms) is considered, ensure that
the floor below the humidifier is constructed from water-
proof materials (with draining facilities) to withstand any
water spilling during servicing or if a problem occurs.
Information about the water quality : chloride concentration :
< 75mg/l, phosphate concentration : < 5mg/l, chlorine consentra-
tion (3 to 6° dA) : < 100mg/l, poor concentration inCO2, organic
elements in poor concentration.
The RTH humidifier can run with the following water quali-
tiers :
x Tap or raw water : water TH between 5° and 40° French
grade.
x Demineralized water : 30μS minimum (caution : the de-
mineralized water is corrosive; use appropriate piping ma-
terial : inox, PVC)
x Softnened waters (not recommanded)
The cation exchangers (softeners) do not suit for the water supply as they do not bring down the mineral salt
content disolved in the water, the polyphosphate measuring devices as well.
A water softener consists basically in replacing a calcium ion by a sodium ion the solubility capability of which is
about 7 times higher. So a water softener does not affect the quantity of mineral salts contained in the water but
alters their nature.
An excess of sodium chloride may generate foam which disturbs greatly the correct running of the humidifier. It
is essential that a duplex softener be used.
A small volume of tap water must be added to the softener water to get a TH value of 10° minimum
(however a TH value of 12° is highly recommended). A water analysis should be made to determine the
sodium chloride content.
We would not recommend the use of cation exchangers as this increases functionning costs significan-
tly.
Water supply service
Check valve
Water inlet hose with 3/4"
female union
ELECTROVAP RTH-V2
Water connection