4 Conguring Victron Products
4.1 VE.Congure Settings
You will need the latest rmware on all connected devices.This section presumes familiarity with VECongure software.
These settings are for an off-grid application.These parameters once set will become the default values used if
communication with the AES battery is interrupted for some reason. During normal operation the charge characteristics are
governed automatically by the CCGX via DVCC, with instructions from the connected AES battery. However it is necessary
to set the discharging parameters for DC input low shut-down found under the InverterTab. After setting the parameters,
‘send’ all parameters to the inverter and CCGX. Restart the CCGX after completion.
General Tab 44-24-2800 42-48-6650
Overruled by remote (1) Enable Enable
Enable battery monitor Enable Enable
SoC when Bulk nished (2) 95% 95%
Total battery capacity (per battery installed) installed x 110 Ah installed x 130 Ah
Charge efciency (2) 95% 95%
Inverter Tab 44-24-2800 42-48-6650
DC input low shut-down (3) 24.0 V 48.0 V
DC Input low restart (4) 26.0 V 52.0 V
DC input low pre-alarm (5) 25.5 V 51.0 V
Enable AES (6) Disable Disable
Charger Tab 44-24-2800 42-48-6650
Enable charger Enable Enable
BatteryType (2) Blank Blank
Lithium batteries (2) Enable Enable
Charge curve (2) Select: Fixed Select: Fixed
Absorption voltage (2) 27.2 V 54.4 V
Float voltage (2) 26.8 V 53.6 V
Charge current per battery installed
(Recommended < Maximum)
installed x
(78 A < 110 A)
installed x
(92 A < 130 A)
Repeated absorption time (2) (7) 1.0 < 3.0 Hr 1.0 < 3.0 Hr
Repeated absorption interval (2) 7.0 Days 7.0 Days
Absorption time (2) (7) 1.0 < 3.0 Hr 1.0 < 3.0 Hr
(1) Enabled is recommended.
(2) Precautionary setting as they are ignored during normal operation and communication with AES Battery.
(3)The lowest operating voltage allowed, increase voltage as required.
(4) Restart voltage after DC input low shut-down, recommended to be set to the minimum value (minimum varies according to
the DC Input low shut-down value).
(5) 51.0 V value (approximately 15% SoC) will trigger low battery warning, increase or decrease as preferred.
(6) ‘Enable AES’ has no relation to the AES Battery, refer to Victron manuals for information on setting and function.
(7)The recommended minimum is 1.0 hour. A longer period of time may be required to compensate for multiple batteries to
achieve a smooth completion of charge.
▲ NOTE
• Conrm the Float Voltage after completing the installation of any Victron
‘Assistants’, and if necessary reset the Float Voltage back to 26.8 V / 53.6 V.
M8” bolt (supplied with battery)
Copper compression lug
Shrink-wrap to
color-code the cable
Terminal surface
Lock washer (supplied with battery)
Flat washer (supplied with battery)
Battery cable lug
Ensure nothing is between
the terminal surface and the
battery cable lug