2. Advanced settings
To adjust the settings press orPress so that the screen is off.
Then press and hold + together. The unit enters
the menu at Status 1: “SEN” and in Function 00 (flashing).
* These are advanced settings and should be adjusted with caution.
To move through menu Items 1-7 press the button.
See the menu below
2.1 ENTERING INTO ADVANCED SETTINGS MENU*
TherMiser TME operation
To prevent tampering and adjustment of the TherMiser unit, unit, press for 5
seconds appears. To unlock, press for 5 seconds flashes then disappears.
Manual Override . Press or to override current target temp. appears
and if heat required. Automatically resets to program mode at next time interval.
MENU NO. ICON FUNCTION OPTIONS FACTORY SETTING
1 SEN Controls sensor inputs
00: Built-in temp sensor only
01: External temp sensor only
02: Built in temp and External Skirting Temp Sensor
Note: If no external sensor fitted,“ERR” message
displays, unit will not function
00
2 OSV Upper limit of external/ThermaSkirt sensing temp, 5~99°C 42°C
3 DIF Differential hysteresis between off and on again
of external temp. 1~9°C 2°C
4 SFH Room temperature upper limit 5~99°C 35°C
5 SVL Room temperature lower limit 5~99°C 5°C
6 ADJ Calibrates tem of unit to the room, compensating
for external factors. -5~+5° 0°C
7 FRE Frost protection 00: Frost protection OFF
01: Frost protection ON. 5°C 00
8 PON Power on memory 00: Auto memory, no power
01: NO power = no memory 00
9FAC Factory reset
Adjust using until“00”
then press to restore
factory settings
00
2.2 LOCK SCREEN/MENU 2.3 LOCK SCREEN/MENU