doble PHENIX 6CB User manual

VERSION 1.1 3/29/22
USER’S MANUAL
AC DIELECTRIC TEST SET
TYPE 6CB
MODEL NUMBER
6CB100/50-7.5
PHENIX TECHNOLOGIES
A Division of Doble Engineering
75 Speicher Drive
Accident, MD 21520
Phone 1 (301) 746-8118
Fax 1 (301) 895-5570
E-mail: info@phenixtech.com
Copyright © Phenix Technologies

TABLE OF CONTENTS
DESCRIPTION
SECTION
NUMBER
DANGER - SAFETY PRECAUTIONS 1
TECHNICAL SPECIFICATIONS
2
UNCRATING PROCEDURE 3
CONTROLS AND INDICATORS
4
OPERATING INSTRUCTIONS 5
INITIAL SETUP
6
TESTING PROCEDURE 7
DIELECTRIC TEST SYSTEM SOFTWARE 8
CALIBRATION
9
TROUBLESHOOTING 10
MECHANICAL MAINTENANCE
11
VACUUM AND OIL FILL PROCEDURE 12
CHECKING OIL PURITY
13
MAINTENANCE SCHEDULE 14
TRANSPORTING OF EQUIPMENT 15
STORAGE OF EQUIPMENT 16
CIRCUIT DIAGRAM SYMBOLS 17
ELECTRICAL SCHEMATICS 18
PARTS ORDERING INFORMATION 19
PARTS LIST
20
RECOMMENDED SPARE PARTS 21
RETURNED MATERIAL
22
CUSTOMER COMMENTS
23

SECTION 1: DANGER - SAFETY PRECAUTIONS 1-1
WARNING!!!
Complete Grounding of this unit is necessary for the
safe operation of this equipment. Disconnect inputs
before ungrounding this equipment

SECTION 1: DANGER - SAFETY PRECAUTIONS 1-2
GENERAL SAFETY PRECAUTIONS
This equipment is capable of providing POTENTIALLY LETHAL VOLTAGES! Improper operation
or test practices may result in injury or death to the operator or surrounding personnel.
The operation of High Voltage test equipment should only be performed by personnel familiar with
HIGH VOLTAGE testing and safety procedures. The operator of this equipment must be aware of
all hazards associated with High Voltage testing. The operator is responsible for himself and
others in close proximity of the testing area.
Some General Safety Practices for working with High Voltage Test Equipment have been listed
below for your reference.
Become familiar with your instrument before performing an actual test.
Know your work area, check that all circuits are de-energized and locked out.
Never work alone; always work with another qualified worker.
Mark off entire work area with barriers and warning tape.
Make all personnel aware of your testing activities.
Be aware of dangerous conditions that may arise from energizing a test specimen.
Never modify test equipment; modifications to equipment could introduce an unknown
hazard or hinder a designed-in safety feature.
DO NOT operate damaged equipment. Remove power, and do not use the equipment
until safe operation can be verified by service-trained personnel.
Phenix Technologies, Inc. assumes no liability for unsafe or improper use of test equipment.

SECTION 2: TECHNICAL SPECIFICATIONS 2-1
MODEL: 6CB100/50-7.5
Dielectric Test Sets are designed to measure the dielectric strength that an insulating material can
withstand before an insulation breakdown occurs at rated power frequencies.
INPUT
(Refer to Unit Serial Tag)
110-120
Volts AC 30
Amps AC 50/60
Hz 1 Phase
OR
220-240
Volts AC 15
Amps AC 50/60
Hz 1 Phase
OUTPUT
Tap #1:
Side Polished Ball
50.0 kVAC 150
mA (Max)
Tap #2:
Top High Voltage Spinning
100.0 kVAC 75
mA (Max)
DUTY
5 min ON/15 min OFF @ 7.50kVA
15 min ON/1 hr OFF @ 5kVA
1 hr ON/1 hr OFF @ 3kVA
DISTORTION
Less than 5% at full load
IMPEDANCE
Less than 15% at rated current
PD RATING
<10 pC
ENVIRONMENTAL OPERATING CONDITIONS:
TEMPERATURE:
10 – 40°C indoor/outdoor in far weather
HUMDITY:
<95% non-condensing
ALTITUDE:
<1000m (3300 ft.)
COOLING TYPE
ONAN (Oil-Natural/Air-Natural Convection)
REMOTE CONNECTION TYPE (IF PURCHASED)
Wi-Fi via Wireless Access Point

SECTION 2: TECHNICAL SPECIFICATIONS 2-2
METERING
Output
Voltmeter:
Instrument Type:
HMI
Meter Type:
Peak/(Square root of 2)
Accuracy:
± (0.8% of Reading + 0.2% of Range) + LSD (10-100% of range)
Range:
0-50kV, 100kV
Total Currentmeter:
Instrument Type:
HMI
Meter Type:
True RMS
Accuracy:
± (0.8% of Reading + 0.2% of Range) + LSD (10-100% of range)
Range:
0-30mA, 150mA
Specimen Currentmeter:
Instrument Type:
HMI
Meter Type:
True RMS
Accuracy:
± (0.8% of Reading + 0.2% of Range) + LSD (10-100% of range)
Range:
0-200uA, 2mA, 20mA, 150mA
D
IMENSIONS
CONTROLS/REGULATOR:
21.25"L x 16.75"W x 13.75"H x 67lbs.
540mmL x 426mmW x 349mmH x 30kg
HIGH VOLTAGE CYLINDER:
16"L x 16"W x 30"H x 178lbs.
406mmL x 406mmW x 762mmH x 81kg
CART:
22.5"L x 29.25"W x 50"H x 61lbs.
572mmL x 743mmW x 1270mmH x 28kg

SECTION 3: UNCRATING PROCEDURE 3-1
GENERAL PROCEDURE
1. Exercise care in removing shipping materials to avoid injury to personnel or damage to the unit.
Items in this shipment are large and heavy. Phenix Technologies recommends that 2 persons be
assigned to this task.
2. Perform visual inspection to determine if unit was damaged during shipment. If there are any
signs of physical damage (such as dents, scratches, oil leaks), contact the factory before
proceeding.
For questions or information regarding operation of the Test Set, please refer to the appropriate sections
of this manual. Further information is also available from:
Phenix Technologies’ Service Department
75 Speicher Drive
Accident, Maryland 21520
Phone 1 (301) 746-8118
Fax 1 (301) 895-5570
E-mail: info@phenixtech.com

SECTION 4: CONTROLS AND INDICATORS 4-1
6CB100/50-7.5
CONTROL PANEL
1. Ground Stud
Ground connection point for tying to high voltage cylinder ground.
2. Main Power Circuit Breaker
This is the main circuit breaker for the system. It provides a input overload protection for the
system and functions as the main on/off switch for the unit.
3. CON101 Main Input Power Connection
This connector is used to provide power to the system. Connect the provided input power cable
to test facility power.
4. CON102 TO HV TRANSFORMER
Power output connection to high voltage transformer. The power interconnect cable connects
here.
2
1
3
5
4
6
7
8
9
10
11
12
13

SECTION 4: CONTROLS AND INDICATORS 4-2
6CB100/50-7.5
5. TX1
Connection for metering interconnect cable. This is the metering and return connection. Do not
attempt to operate high voltage unit without this cable connected at both ends.
6. Security/Warning Circuit
Security Circuit - Provided for user connection of external interlock or auxiliary safety control
device such as emergency off switch, gate switch, foot switch, dead man switch, etc. Included
plug has shorting jumper installed to complete circuit. Jumper must be removed, and cable
connected to user supplied device by user if desired to use this provision. Only non-energized
switch or dry relay contact devices may be used. This is a series circuit that must remain closed
for high voltage to be activated.
Warning Circuit – Provides power to external warning light circuits. Voltage is provided to
different pins depending if HV is no or not. Reference included schematic to see what pins are
powered. Unit can be operated without use of this feature.
Security circuit and warning light accessories are available from Phenix Technologies that use
this connector. The accessories are able to be “daisy chained” together so that multiple
accessories can be used at once. The available accessories include flashing lights, foot
switches, and Green\Red-light pole with E-Stop switch.
7. Emergency Stop switch
Press under emergency conditions. Output will turn off. Button will stay down when pressed,
twist to release.
8. HV ON switch/lamp
Momentary switch turns high voltage on when pressed. HV ON lamp illuminates red when high
voltage is on.
9. HV OFF switch/lamp
Momentary switch turns high voltage off when pressed. HV Off lamp illuminates green when all
pre-conditions required for high voltage activation are met.
Conditions required for HV Off lamp illumination are:
·Power applied to unit and Main Power Breaker on, HMI illuminated.
·External Interlock circuit series loop must not be open.
·Emergency Off must not be pressed.
·Regulator position must be at zero. (Zero Start.)
·Overloads (if any) must be reset.
10. External USB Port
This standard female USB port allows for (optional) external data logging via USB drive. A
device must first be connected before data logging can be enabled. CAUTION: This port is not
isolated and requires the use of an external isolator if connection is made to a device with an
earth ground.
11. Infinity Dial
This dial is used to manually control the regulator voltage by controlling the regulator swing arm
when the manual test mode is selected. It is speed sensitive and has no physical stop-limit.
Rotate counterclockwise to decrease the voltage output, and clockwise to increase the voltage
output.
12. Human Machine Interface (HMI)
This touchscreen display controls status and test parameter information.

SECTION 4: CONTROLS AND INDICATORS 4-3
6CB100/50-7.5
13. Capacitive Preload Switch
Used to allow full voltage when HV transformer is lightly loaded (<3kVAr). This cannot be
switched with high voltage on. Push-to-Turn feature will open the main contactor and turn HV off
if switching is attempted while HV is on.

SECTION 4: CONTROLS AND INDICATORS
4-4
6CB100/50-7.5
High Voltage Tank
1. XFRM Input
Input power connection to high voltage cylinders from control/regulator box.
2. Ground Stud
Main ground point for unit. Connection to facility ground. Ground all other unit pieces to this point.
This must be grounded at all times.
3. CM Connections
Connection points for current metering. See INITIAL SETUP section for connection details.
4. TX1
Metering connection between high voltage cylinder and control/regulator box.
5. Tap #2 (Top Spinning)
100kV output connection.
6. Tap #1 (Side Tap)
50kV output connection.
1
2
3
4
5
6

SECTION 5: OPERATING INSTRUCTIONS 5-1
HMI CONTROLS
This system is equipped with an embedded controller and resistive touch screen that functions as the
HMI (Human-Machine Interface). The touch screen is used mainly to set up test parameters and display
test readings. It is also used for calibration and troubleshooting. A menu style interface with touch buttons
is used to navigate the HMI. This manual section will describe each of the screens of the HMI.

SECTION 5: OPERATING INSTRUCTIONS 5-2
HMI CONTROLS: MAIN SCREEN
The main screen displays voltage and current reading, unit status, and dwell timer values. This is the
main operating screen of the device.
MAIN SCREEN (STANDBY STATE)
1. Status Bar
Indicates the main status message of the unit. There are three types of states that the unit can be
in. These are state Standby, Fault, Energized. Refer to the HMI CONTROLS: STATUS BAR
subsection for detailed message information.
2. ABORT TEST button
When pressed during test, unit automatically returns regulator to zero position and then shuts off
high-voltage. HV off button will illuminate and test results will display on screen when high-voltage
is off. The ABORT TEST button is blue when unit is energized and is greyed out when unit is off.
3. BURN MODE button
The burn mode button label text displays the action that will occur if the button is pressed. The
button can only be pressed if the button is blue, if it is grayed out, the button is presently not
available to switch states. The button state can only be switched when the output is de-
energized. The illuminating rim indicates the present status of the burn mode (Presently shown
“ACTIVE”). Burn mode is a purchased option.
4. RESET OVERLOAD button
Resets overloads after an instantaneous voltage overload, instantaneous current overload, long-
term current overload, or thermal overload.
5. RESET TIMERS button
When press will resets only Remaining Dwell Timer while unit is energized. Resets all timers
while unit is off.
6. CONFIGURE TEST button
Press to enter the Configuration Screen.
2
3
4
5
6
7
8
1

SECTION 5: OPERATING INSTRUCTIONS 5-3
HMI CONTROLS: MAIN SCREEN (Cont’d)
7. VIEW MENU button
Press to enter the Menu Screen.
8. OS Menu buttons

SECTION 5: OPERATING INSTRUCTIONS 5-4
HMI CONTROLS: MAIN SCREEN (Cont’d)
MAIN SCREEN (ENERGIZED STATE)
9. Output Voltmeter
Displays voltage of selected tap when unit is Energized.
10. Regulator Bar Graph
Displays current regulator output voltage relative to maximum regulator output voltage.
11. Dwell Voltage
Displays the target dwell voltage for the test (Setpoint).
12. Ramp Rate
For automatic tests, the output voltage will rise by the Ramp Rate every second until target Dwell
Voltage is reached. For manual tests, the output voltage will rise at this rate if the knob is turned
once per second. The rate will vary in proportion to the knob speed.
13. Remaining Dwell Time
Displays the time remaining for the test at Dwell Voltage.
14. Dwell Time Bar Graph
Displays the time remaining for the test at Dwell Voltage relative to the total dwell time.
15. Main Currentmeter
Displays the total current when in Total Current mode or return terminal current when in Return
Current mode.
16. Main Currentmeter Bar Graph
Displays the main current relative to the configured overcurrent trip-point. Unit will trip off when
the bar is full.
15
16
17
18
9
10
11
12
13
14

SECTION 5: OPERATING INSTRUCTIONS 5-5
HMI CONTROLS: MAIN SCREEN (Cont’d)
17. Main Current Limit
Displays the configured overcurrent trip-point. Unit will trip off if this value is exceeded.
18. Duration
Displays the amount of time since high-voltage was turned on.

SECTION 5: OPERATING INSTRUCTIONS 5-6
HMI CONTROLS: TEST RESULTS MESSAGE
When the unit has been energized, and then it de-energized and regulator has returned to the zero
position, a Test Results Screen will show over the Main Control Screen. The Test Results Screen will
display if test was completed successfully or if there was a fault.
TEST RESULTS MESSAGE
1. End Test State
Displays reason or state for test ending.
A. “Test completed successfully” displays when all test parameter were met in either automatic
or manual mode.
B. “Test ended manually by operator” displays when test has been manually ended when either
the HV-Off button or the ABORT TEST button has been pressed.
C. “Test ended due to specimen failure” displays when test configuration current limits are met.
D. “Test ended due to unit fault” displays when E-Stop, SX Circuit, or Main Circuit Breaker open,
or if unit Activation Key expires.
E. “Test ended due to unit overload” displays when the voltage, current, or thermal limits of the
unit have been exceeded.
5
1
2
3
4

SECTION 5: OPERATING INSTRUCTIONS 5-7
HMI CONTROLS: TEST RESULTS SCREEN (Cont’d)
2. Test End Cause
Displays the specific reason the test was ended. If test ended due to fault, specific fault error will
show. See Status Bar Fault states.
A. If test was completed successful, will show “All test parameters met”.
B. If test was ended manually, no fault was detected, and test parameters were not met, will
show: “No fault detected”
3. Relevant test values
Displays different values depending on the reason the test was ended.
A. If test ended due to fault, displays failure voltage, maximum voltage and Dwell time remaining
when failure occurred.
B. If test completed successfully, displays maximum voltage and current measured.
C. If test ended due to manual stoppage, displays the maximum voltage and current, as well as
Dwell time remaining when the test was ended.
4. Reset Overload button
Press to reset any overloads and return to Main Screen. (Only shown if test ended due to
overload).
5. OK button
Press to return to Main Screen.

SECTION 5: OPERATING INSTRUCTIONS 5-8
HMI CONTROL: CONFIGURATION SCREEN
To run a test, test parameters must first be set up. Setting these parameters allows the unit to
automatically run the entire test cycle or have some functions automated when test is done manually.
Value ranges are based off the selected output tap.
NOTICE: Make sure the correct Output Tap is selected before entering parameters.
CONFIG TEST SCREEN
1. Dwell Voltage
Press to set the output voltage Dwell Voltage. In Automatic mode, this is the value the unit will
automatically ramp to. In Manual mode, this is the level that will cause the dwell timer to begin
counting down. Dwell Voltage can be set between 10% and 100% of Output Tap rating.
2. Test Type
Select Automatic, Manual, or Remote (IF PURCHASED) test mode. Selected option displays in
green.
3. Configure Logging Button
Press to enter the Data Logging Screen for external logging of test data via USB. See Data Logging
Screen.
4. Data Logging Info
Indicates if data logging is enabled or disabled. If enabled will display chosen file name.
5. Current Meter Mode
Press to switch between Total Current mode and Return Current mode. The selected mode is
displayed on the button. If the unit is not equipped with Return Current Mode, this button will be
grayed out.
1
2
3
13 12
11
10
9
4 5 6 7 8

SECTION 5: OPERATING INSTRUCTIONS 5-9
HMI CONTROL: CONFIGURATION SCREEN (Cont’d)
6. Apply button
Press to save entered settings and return to the Main Screen.
NOTICE: Settings WILL NOT be saved unless applied.
7. Revert button
Press to restore most recently applied settings.
8. Cancel button
Press to return to Main Screen without saving changes.
9. Output Tap
Press to select the HV transformer tap being used.
10. Over Current
Press to set the main current trip level. Adjustable from 10% to 105% of tap rating.
11. Over Voltage
Press to set the output voltage trip level. Adjustable from Dwell Voltage to 105% of tap rating.
12. Ramp Rate
Press to select output voltage ramp rate in Volt/Second. Adjustable in a range that will cause the
regulator to go from 0% to 100% in 15 to 150 seconds.
13. Dwell Time
Press to set the dwell time at dwell voltage. If in Automatic mode, output will automatically ramp to
zero and shut off when dwell time expires.
Other manuals for PHENIX 6CB
1
This manual suits for next models
1
Table of contents
Other doble Test Equipment manuals