Problem Possible cause Suggested remedy
The auxiliary electric heater is enabled but
not connected. 1. On the Parameters menu, set Aux Elec
Heat to Off.
2. Verify that the breaker for the auxiliary
heater is in the on position.
The mode is not set to Heat on the display. Change the mode to Heat.
The system has lost refrigerant. Contact a qualified service technician.
The airflow is blocked or restricted. 1. Remove any obstructions in the return
air stream.
2. Clean the return air filter and grille.
3. Check for crushed or restricted duct-
ing.
The ducting must be as straight,
smooth, and firmly supported as possi-
ble.
There is not enough airflow in the system.
The system is running in limit mode to com-
pensate for abnormal operating conditions
caused by environmental factors such as
seawater temperature, load, etc.
On the Troubleshoot menu, check System
Status for the operating mode. If the system
cannot resume normal operation within an
hour, a Limit Mode alarm will be sent to the
display until normal operation can be re-
sumed.
The variable speed compressor technology
slows down, but does not stop unless the
temperature set point is exceeded by 1 °F
(0.6 °C).
Adjust the temperature set point or use the
power button on the display to manually
turn off the system.
The compressor is not stopping.
An electrical component has failed. Contact a qualified service technician.
The Fan Operate mode is set for either Cy-
cled or Continuous. On the Parameters menu, change the Fan
Operate Mode to the desired setting.
The fan is not blowing or does not stop
blowing.
An electrical component has failed. Contact a qualified service technician.
The compressor cycled off because the
mode was changed. The compressor will cycle back on three
minutes after the mode change.
The mode icon is flashing.
The compressor cycled off because the tar-
get temperature was exceeded by 1 °F (0.6
°C) or more.
The compressor will cycle on once the cab-
in temperature no longer exceeds the set
point.
The filter warning displays. (is this text or
icon, if text, what text?)
The timer setting to clean or replace the air
filter has been reached. 1. Clean or replace the air filter.
2. On the Parameter menu, use the Filter
Hours Reset function to reset the timer.
(How?)
Fault: Return Air Sensor Failure (how are
faults communicated?)
An electrical connection or component has
failed. Contact a qualified service technician.
Fault: Suction Temp Sensor Failure An electrical connection or component has
failed. Contact a qualified service technician.
Fault: Discharge Pressure Transducer Failure An electrical component has failed. Contact a qualified service technician.
The flow of seawater is obstructed or
blocked. 1. Verify that the seacock is open and wa-
ter if flowing to the pump.
2. Clean the seawater strainer.
3. Check for a strong, steady flow from
the overboard discharge.
Fault: High Discharge Pressure
The seawater pump may be be airlocked. 1. Verify that the seawater plumbing is in-
stalled according to the instructions in
the installation manual included with
the air conditioning unit.
17