Donaldson Torit Dalamatic Cased DLMC 1/2/15 User manual

This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
This manual is property of the owner. Leave with the collector when set-up and start-up are complete. Donaldson Company reserves the
right to change design and specifications without prior notice.
Illustrations are for reference only as actual product may vary.
Dalamatic®Cased
DLMC 1/2/15, 1/3/15, 1/4/15, 1/5/15, 1/7/15, 2/2/15, 2/3/15, 2/4/15,
2/5/15, 2/6/15, 2/8/15, 3/3/15, 3/5/15, 3/6/15, 3/7/15, 3/8/15, 4/5/15 and
4/8/15 - Units Built After July 2006
Installation and Operation Manual
Installation, Operation, and Service Information
IOM AD3626001 (ENG)
Revision 4
English
Master Language

Donaldson Company, Inc.
Process owners/operators have important responsibilities relating to combustible hazards.
Process owners/operators must determine whether their process creates combustible dust,
fume, or mist. If combustible dust, fume, or mist is generated, process owners/operators should at a
minimum:
• Comply with all applicable codes and standards. Among other considerations, current NFPA standards
require owners/operators whose processes involve potentially combustible materials to have a current
Hazard Analysis, which can serve as the foundation for their process hazard mitigation strategies.
• Prevent all ignition sources from entering any dust collection equipment.
• Design, select, and implement fire and explosion mitigation, suppression, and isolation strategies that
are appropriate for the risks associated with their application.
• Develop and implement maintenance work practices to maintain a safe operating environment, ensuring
that combustible dust, fume, or mist does not accumulate within the plant.
Donaldson recommends process owners/operators consult with experts to insure each of these
responsibilities are met.
As a manufacturer and supplier of Industrial Filtration Products, Donaldson can assist process owners/
operators in the selection of filtration technologies. However, process owners/operators retain all
responsibility for the suitability of fire and explosion hazard mitigation, suppression, and isolation strategies.
Donaldson assumes no responsibility or liability for the suitability of any fire and/or explosion mitigation
strategy, or any items incorporated into a collector as part of an owner/operators hazard mitigation strategy.
Improper operation of a dust control system may contribute to conditions in the work area or facility that
could result in severe personal injury and product or property damage. Check that all collection equipment is
properly selected and sized for the intended use.
DO NOT operate this equipment until you have read and understand the instruction warnings in the
Installation and Operations Manual. For a replacement manual, contact Donaldson Torit.
This manual contains specific precautionary statements relative to worker safety. Read thoroughly and comply
as directed. Discuss the use and application of this equipment with a Donaldson Torit representative. Instruct all
personnel on safe use and maintenance procedures.
Model Number _____________________________ Serial Number ______________________________
Ship Date _________________________________ Installation Date _____________________________
Customer Name _______________________________________________________________________
Address _____________________________________________________________________________
____________________________________________________________________________________
Filter Type ____________________________________________________________________________
Accessories __________________________________________________________________________
Other________________________________________________________________________________
Data Sheet

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
i
DANGER indicates a hazardous situation which, if not avoided, will result
in death or serious injury.
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION, used with the safety alert symbol, indicates a hazardous
situation which, if not avoided, could result in minor or moderate injury.
NOTICE is used to address practices not related to personal injury that
may result in damage to equipment.
Magnehelic®and Photohelic®are registered trademarks of Dwyer Instruments, Inc.
Contents
Description................................................................................1
Purpose and Intended Use ....................................................1
Operation...................................................................................3
Inspection on Arrival...............................................................4
Installation Codes and Procedures ......................................4
Installation.................................................................................4
Foundations or Support Framing .......................................5
Collector Location................................................................5
Site Selection .......................................................................5
Rigging Instructions.................................................................5
Hoisting Information ............................................................5
Standard Equipment................................................................7
Shipping Information ...........................................................8
Collector Installation............................................................9
Provisional Anchor Bolt Recommendations....................9
Manifold Installation..........................................................11
Compressed Air Installation.............................................11
Electrical Wiring.................................................................12
Solid-State Timer Installation...........................................13
Helix Tube Filter Installation .............................................15
Preliminary Start-Up Check .................................................17
Typical Start-Up Sequence...............................................17
Typical Shut-Down Sequence..........................................17
Maintenance Information.....................................................18
Operational Checklist ........................................................18
Filter Removal and Installation.........................................18
Optional Equipment................................................................22
Fan Blower ..........................................................................22
Magnehelic®Gauge .........................................................23
Photohelic®Gauge ............................................................24
Delta P Control....................................................................26
Delta P Plus Control ..........................................................27
Antistatic Option.................................................................28
Interlocks and Alarms .......................................................28
Platforms and Ladders ......................................................28
Explosion Vent ....................................................................29
Explosion Vent Membrane Replacement.......................29
Troubleshooting......................................................................30

1
Donaldson Company, Inc.
Combustible materials such as buffing lint, paper, wood, metal dusts, weld fume, or flammable
coolants or solvents represent potential fire and/or explosion hazards. Use special care when
selecting, installing, and operating all dust, fume, or mist collection equipment when such combustible
materials may be present in order to protect workers and property from serious injury or damage due to a
fire and/or explosion.
Consult and comply with all National and Local Codes related to fire and/or explosion properties of
combustible materials when determining the location and operation of all dust, fume, or mist collection
equipment.
Standard Donaldson Torit equipment is not equipped with fire extinguishing or explosion protection systems.
The Dalamatic Cased, Model DLMC, dust collectors
are continuous-duty collectors with bag-style filters
designed to handle product recovery applications and
operations generating nuisance dust. The DLMC provides
continuous filtration and high collection efficiency while
maintaining a relatively constant system resistance.
Standard sizes range from 323 to 5164 sq ft (30 to 480 sq
meters) of filter area. A solid-state timer provides the
interface for filter cleaning control.
Options include a pyramid hopper for use with a
55-gallon drum or rotary airlock, a trough hopper for use
with a screw conveyor, or hoppers for use with bin-style,
dust disposal pails.
The DLMC separates solid particulate from an airstream
as part of a manufacturing process.
The DLMC is commonly used in the chemical, mineral,
food, plastic, metal compound, and pharmaceutical
industries. High temperature applications are possible
with attention to gaskets, caulking, and filter media
choices. Extreme conditions may require special paint
and structural modifications.
Although primarily designed for negative pressure
systems, the DLMC can be used under positive pressure.
Contact Donaldson Torit for information on positive
pressure systems.
Description Purpose and Intended Use
Misuse or modification may result
in severe personal injury and/or
property damage.
Do not misuse or modify.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
2
Collectors are rated for the following loads as calculated
per relevant sections of the IBC 2012 code*:
Basic Wind Speed & Exposure ............90 mph, Exposure C
Seismic Spectral Acceleration, Ss................................ .1.5 g
Seismic Spectral Acceleration, S1................................. 0.6 g
Installed Collector Base Elevation...............................Grade
Risk Category.......................................................................... II
Compressed air supply, psig ........................................ 90-100
Housing rating, inches water gauge ............................... - 20
Control power...............................................120-Volt 50/60 Hz
*If collector was supplied with a Record Drawing,
the specifications on the drawing will supersede the
standard specifications above.
Pyramid Hopper
Typical Side View
Pyramid Hopper UMA Hopper with 4 cu
ft. Bins
Trough Hopper
Rating and Specification Information

3
Donaldson Company, Inc.
During normal operation, dust-laden air is drawn through
the dirty air inlet. Dust will hit the baffle causing the dust
particle velocities to be reduced. From there, natural pre-
separation, caused by the effects of gravity, takes place
with larger particulate falling directly to hoppers and fine
particles collecting on the outside surface of the filter.
Clean, filtered air passes to the center of the filter and
discharges through the clean-air outlet.
Filter cleaning is completed using pulse-jet technology.
A jet tube positioned over each filter distributes a pulse
of compressed air through the filter. As the compressed
air enters the filter, airflow is temporarily reversed
dislodging the dust cake formed on the outside of the
filter. The dust cake falls into the hopper and exits
through the hopper outlet.
outlet header
sealing frame
and ring
accumulated dust
cake
filter
clean-air plenum
dirty air plenum
air inducted by
force of jet
clean-air plenum
dirty-air plenum
airflow temporarily
reversed dislodging
dust cake
Normal Operation Filter Cleaning Operation
clean-air outlet
jet tube
tubesheet (seal frame)
wire insert
(used with felt bags)
jet tube injecting
compressed air
dust cake falls into the
hopper (DLMC)
Collector Operation
Operation

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
4
Installation Codes and Procedures
Codes may regulate recirculating
filtered air in your facility.
Consult with the appropriate authorities
having jurisdiction to ensure compliance
with all national and local codes regarding
recirculating filtered air.
Safe and efficient operation of the collector depends on
proper installation.
Authorities with jurisdiction should be consulted
before installing to verify local codes and installation
procedures. In the absence of such codes, install
collector according to the National Electric Code,
NFPA No. 70-latest edition and NFPA 91 (NFPA 654 if
combustible dust is present).
A qualified installation and service agent must complete
installation and service of this equipment.
All shipping materials, including shipping covers, must
be removed from the collector prior to or during collector
installation.
Failure to remove shipping
materials from the collector will
compromise collector performance.
Inspect collector to ensure all hardware is properly
installed and tight prior to operating collector.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100-psig
supply pressure.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed air lines to remove
debris before connecting to the collector’s
compressed air manifold.
Installation
Use proper equipment and adopt
all safety precautions needed for
servicing equipment.
Electrical service or maintenance work must
be performed by a qualified electrician and
comply with all applicable national and local
codes.
Turn power off and lock out electrical
power sources before performing service or
maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Site selection must account for
wind, seismic zone, and other
load conditions when selecting the location for
collectors.
Codes may regulate acceptable locations for
installing dust collectors. Consult with the
appropriate authorities having jurisdiction to
ensure compliance with all national and local
codes regarding dust collector installation.
Collectors must be anchored in a manner
consistent with local code requirements.
Anchors must be sufficient to support dead,
live, seismic, and other anticipated loads.
Consult a qualified engineer for final selection
of anchorage.
Inspection on Arrival
1. Inspect collector upon delivery.
2. Report any damage to the delivery carrier.
3. Request a written inspection report from the Claims
Inspector to substantiate any damage claim.
4. File claims with the delivery carrier.
5. Compare collector received with description of
product ordered.
6. Report incomplete shipments to the delivery carrier
and your Donaldson Torit representative.
7. Remove crates and shipping straps. Remove loose
components and accessory packages before lifting
collector from truck.
8. Check for hardware that may have loosened during
shipping.
9. Use caution removing temporary covers.

5
Donaldson Company, Inc.
Do not lift collector by the door handles.
The lifting lugs provided have been designed to
support the individual sections of the collector
as shipped to the site. Do not use the lifting
lugs to lift the entire weight of the collector.
Carefully follow the assembly sequence to
avoid exceeding the load capacity of the lifting
lugs.
The collector is suitable for either indoor or outdoor
installations. Reference the Rating and Specification
Information.
Collector Location
Donaldson Torit equipment is not
designed to support site installed
ducts, interconnecting piping, or electrical
services. All ducts, piping, or electrical
services must be adequately supported to
prevent severe personal injury and/or property
damage.
When hazardous conditions or materials are
present, consult with local authorities for the
proper location of the collector.
Dust collection equipment may
reach peak sound pressure
levels above 80 dB (A). Noise levels should be
considered when selecting collector location.
Locate the collector to ensure easy access to electrical
and compressed air connections, to simplify solids
collection container handling and routine maintenance,
and to ensure the straightest inlet and outlet ducts.
Foundations or Support Framing
Prepare the foundation or support framing in the
selected location. Foundation or support framing must
comply with local code requirements and may require
engineering.
Foundation and support framing must be capable of
supporting dead, live, wind, seismic and other applicable
loads. Consult a qualified engineer for final selection of
foundation or support framing.
Note: Collectors with explosion vents are not
available in portable configurations.
Site Selection
This collector can be located on a foundation or
structural framing.
Provide clearance from heat sources and avoid any
interference with utilities when selecting the location.
Ensure the inlet has at least five diameters of straight
duct prior to the collector inlet including a transition to
the full inlet dimensions. Inlet transition should have a
taper with a maximum of a 90-degree included angle.
Consider the effects of condensation caused by
temperature difference between the process airstream
and outdoor temperatures.
Consider forklift access for solid collection container
removal.
Rigging Instructions
Suggested Tools & Equipment
Clevis Pins and Clamps Lifting Slings
Crane or Forklift Pipe Sealant
Drift Pins Pipe Wrenches
Drill and Drill Bits Screwdrivers
End Wrenches Socket Wrenches
Adjustable Wrench Spreader Bars
Torque Wrench (inch/lbs, 9/16-in Socket)
Hoisting Information
Failure to lift the collector
correctly can result in severe
personal injury and/or property damage.
Use appropriate lifting equipment and adopt
all safety precautions needed for moving and
handling the equipment.
A crane or forklift is recommended for
unloading, assembly, and installation of the
collector.
Location must be clear of all obstructions, such
as utility lines or roof overhang.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
6
Do Not lift with
this orientation
angle not to
be less than 60°
from horizontal
X
Recommended Lifting
Use all lifting points provided.
Use clevis connectors, not hooks, on lifting slings.
Use spreader bars to prevent damage to collector’s
casing.
Check the Specification Control drawing for weight and
dimensions of the collector and components to ensure
adequate crane capacity.
Allow only qualified crane or forklift operators to lift the
equipment.
Refer to applicable OSHA regulations and local codes
when using cranes, forklifts, and other lifting equipment.
Lift collector and accessories separately and assemble
after collector is in place.
Use drift pins to align holes in section flanges during
assembly.

7
Donaldson Company, Inc.
Standard Equipment
Dalamatic Cased dust collectors are delivered partially
assembled in sections compatible with truck capacity
and load restrictions. All models require field assembly of
the leg, hopper, filter section, compressed air manifold,
and ducts.
leg and crossbrace
hopper
cabinet ground lug
(optional, not shown)
tubesheet (seal frame)
filter bag and cage (insert)
dirty-air inlet
clean-air outlet
solenoid enclosure
top inspection
panel
blow pipe (jet tube)
lifting lug
Typical Installation
(Collector shown with rear inlet and front outlet. Other options include side inlets and outlets and a top outlet to be
used with a mounted TBI fan.)
Typical systems include one of several hopper
arrangements designed for compatibility with various
solids-handing containers. A typical DLMC also has a
steel structure to support the collector.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
8
Shipping Information
Upper Section
2-Tier
1600-lb
2-Tier
2850-lb
2-Tier
4150-lb
3-Tier
2050-lb
3-Tier
3600-lb
3-Tier
5150-lb
A B C D
E F
J K L
Lower Section, tarp required with open top
4-Tier
2650-lb
4-Tier
4600-lb
4-Tier
6600-lb
2-Tier
925-lb
4-Tier
1850-lb
2-Tier
1500-lb
4-Tier
3000-lb
2-Tier
2100-lb
4-Tier
4150-lb
2-Tier
5400-lb
3-Tier
6700-lb
4-Tier
8550-lb
PN Q R
TS U V
2-Tier
2650-lb
4-Tier
5450-lb
G H
M
All weights are approximate
Front view is shown
Pyramid
Hopper
and Legs
Single Outlet
Pyramid
Hopper
and Legs
Trough
Hopper
and Legs
Manifold**
Assembly
1-Bank 1250-lb* NA NA 2/5-Tier
2-Bank 1650-lb* 1400-lb* 1300-lb* 200-lb/Bank
3-Bank 2050-lb* 1850-lb* 1600-lb* 6/8-Tier
4-Bank 2800-lb* NA 1850-lb* 225-lb/Bank
*Add 150-lb for 72-in legs
**Includes electrical, valves, tubing, and manifold
Example:
Model DLM 6/4/15 = 6 banks wide x 4-tiers high
1. Find the number of banks in the first column and follow
the row to the 4-Tier column.
2. This collectors ships with two upper sections (L).
3. Hopper and legs ship separate.
Banks 2-Tier 3-Tier 4-Tier 5-Tier 6-Tier 7-Tier 8-Tier
1 (1) A (1) E (1) J (1) E, (1) N (1) A, (1) S (1) E, (1) S (1) J, (1) S
2 (1) B (1) F (1) K (1) F, (1) P (1) B, (1) T (1) F, (1)T (1) K, (1) T
3 (1) C (1) G (1) L (1) G, (1) Q (1) C, (1) U (1) G, (1) U (1) L (1) U
4 (1) D (1) H (1) M (1) H, (1) R (1) D, (1) V (1) H, (1) V (1) M, (1) V
5 (1) B, (1) C (1) F, (1) G (1) K, (1) L (1) F, (1) P, (1) G, (1) Q (1) B, (1) T, (1) C, (1) U (1) F, (1) T, (1) G, (1) U (1) K, (1) T, (1) L, (1) U
6 (2) C (2) G (2) L (2) G, (2) Q (2) C, (2) U (2) G, (2) U (2) L , (2) U
7 (1) C, (1) D (1) G, (1) H (1) L, (1) M (1) G, (1) Q, (1) H, (1) R (1) C, (1) U, (1)D, (1) V (1) G, (1) U, (1) H, (1) V (1) L, (1) U, (1) M, (1) V
8 (2) D (2) H (2) M (2) H, (2) R (2) D, (2) V (2) H, (2) V (2) M, (2) V
9 (3) C (3) G (3) L (3) G, (3) Q (3) C, (3) U (3) G, (3) U (3) L, (3) U
10 (2) B, (2) C (2) F, (2) G (2) K, (2) L (2) F, (2) P, (2) G, (2) Q (2) B, (2) T, (2) C, (2) U (2) F, (2) T, (2) G, (2) U (2) K, (2) T, (2) L, (2) U

9
Donaldson Company, Inc.
Collector Installation
Anchors must comply with local
code requirements and must be
capable of supporting dead, live, wind, seismic,
and other applicable loads.
Anchor sizes shown are provisional, as final
anchor sizing will depend on jobsite load
conditions, collector location, foundation/
framing design variables and local codes.
Consult a qualified engineer for final selection
of anchors.
Reference Typical Foundation Anchor and leg assembly
drawing shipped with the collector prior to starting
assembly.
1. Carefully follow the caulking and sealing
recommendations during the assembly process.
2. Prepare the foundation or support framing in the
selected location. Locate and install anchors.
3. Assemble the legs and cross bracing.
4. Level all horizontal and vertical members. Use shims
under legs if necessary.
5. Lift hopper into position over the leg structure and
lower slowly.
6. Use drift pins to align holes.
7. Secure joints with bolts, washers, and hex nuts
supplied.
8. Tighten all hardware on legs and cross braces
before removing crane.
10. Apply sealant to the hopper flange. See Sealant
Detail.
11. Lift the filter section into position over the hopper
and lower slowly.
12. Use drift pins to align holes. Install bolts loosely until
all bolts are in place. If the collector has vertical
site joints, apply sealant as shown before bolting
together.
13. Install the bolts at the clean-air plenum base to
hopper flange first.
14. Access the tubesheet (seal plate) joining bolts
through the front access doors. Take special care
with sealant at the tubesheet joint between the
clean- and dirty-air plenums. See Tubesheet Joining
Bolts. Tighten bolts to distribute sealant.
15. Secure all bolts, washers, and hex nuts. Tighten
uniformly to form an airtight seal.
16. Install upper filter sections and bolt on external
flange stiffeners the same way if shipped separately.
Models with horizontal site
joints have lifting lugs that must
be removed before installing the upper filter
sections.
17. Ducts must be independently supported.
Anchor should project
a minimum of 1 3/4-in
and account for nut,
washer, base plate
and shims/grout.
Embedment depth
Typical Foundation Anchor
Provisional Anchor Bolt Recommendations
1. Consider Hilti HIT-HY 200 Anchor System or
equivalent. Quantity of anchor bolts should match the
number of holes provided in the base plates.
2. Anchor diameter is typically 1/8-in less than
baseplate hole diameter.
3. Corrosive environment or outdoor installation may
require stainless steel anchors.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
10
3/16-in diameter
continuous bead
of sealant. Apply
to each side of the
bolt pattern
Apply generously
to prevent leakage.
Sealant Detail
remove and discard
after section
is installed
(2 pieces)
Sealant Detail
top inspection panel removed
bolt-on external
flange stiffener
Note: the opening is only for the
inspection panel and should not
be used as an inlet.
Sealant Detail

11
Donaldson Company, Inc.
Manifold Installation
1. Apply a suitable sealant, based on temperature
and application, to the hose stem adapter flange
and completely circle flange shown in manifold
illustration.
2. Lift the assembly up to fit against the bottom of the
clean-air plenum and bolt into position.
For ease of installation, mount
manifold assembly to a pallet and
lift into place.
3. Remove plastic plug. If necessary, install steel plug
from the opposite tap to the plug.
4. Carefully tighten the jet tubes.
5. Remove all plastic plugs.
6. Bolt center of manifold assembly (two bolts) to the
collector clean air manifold.
Manifold Installation
connecting
hose
solenoid enclosure
compressed air filter regulator and safety
exhaust valve (supplied by others)
diaphragm
valve
hose clamp
hose stem
adapter flange
sealant bolt to clean
air manifold
Compressed Air Requirements
2 Tier Collectors 55-psig
3 Tier Collectors 65-psig
4-8 Tier Collectors 90-100 psig
1. Remove the plastic pipe plug from the collector’s air
manifold and connect the compressed-air supply
lines. Use thread-sealing tape or pipe sealant on all
compressed-air connections.
2. Install a customer-supplied shut-off valve, bleed-
type regulator with gauge, filter, and automatic
condensate valve in the compressed-air supply line.
3. Set compressed-air supply pressure to a level
suitable for the filters (90-psig). The pulse-cleaning
controls are factory set to clean one or more filters
every 10-seconds during a cleaning cycle.
Compressed Air Installation
Turn compressed air supply OFF,
bleed and lock out lines before
performing service or maintenance work.
A safety exhaust valve should be used to
isolate the compressed air supply. The safety
exhaust valve should completely exhaust
pressure in the collector manifolds when
closed, should be capable of being interlocked
with fire or explosion mitigation equipment
and should include provisions to allow closed-
position locking.
Do not set compressed-air
pressure above 100-psig as
component damage can occur.
All compressed air components must be sized
to meet the system requirements of 90-100-psig
supply pressure.
Compressed air pressure must be set to
the pressure listed in the Compressed Air
Requirements table to ensure proper operation.
The compressed-air supply must be oil
and moisture free. Contamination in the
compressed air used to clean filters will result
in poor cleaning, cleaning valve failure, or poor
collector performance.
Purge compressed-air lines to remove
debris before connecting to the collector’s
compressed-air manifold.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
12
Compressed Air Pulse Cleaning Control System
diaphragm
bleed hole
compressed air
from manifold
diaphragm
valve closed
pilot
valve closed
controller compressed air
diaphragm
valve open
pilot
valve open
controller
to jet tube
connection tube
connection tube
Electrical Wiring
Electrical installation, service,
or maintenance work must
be performed by a qualified electrician and
comply with all applicable national and local
codes.
Turn power off and lock out electrical
power sources before performing service or
maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
All electrical wiring and connections, including electrical
grounding, should be made in accordance with the
National Electric Code (NFPA No. 70-latest edition).
Check local ordinances for additional requirements that
apply.
The appropriate wiring schematic and electrical rating
must be used. See collector’s rating plate for required
voltage.
An electric disconnect switch having adequate amp
capacity shall be installed in accordance with Part IX,
Article 430 of the National Electrical Code (NFPA No.
70-latest edition). Check collector’s rating plate for
voltage and amperage ratings.
Refer to the wiring diagram for the number of wires
required for main power wiring and remote wiring.

13
Donaldson Company, Inc.
Electrical installation, service
or maintenance work during
installation must be performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out electrical power
sources before performing installation, service,
or maintenance work.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Solid-State Timer Installation
The solid-state timer is used to control the filter cleaning
system.
Solenoid Connection
The collector is equipped with electric solenoid valves
(typically 120V) that controls the pulse-cleaning valves,
which in turn clean the filters.
Solenoid enclosures are mounted near or on the
collector’s compressed-air manifold.
Wire the solenoids to the solid-state timer following the
wiring diagram supplied with the collector. Filter life and
cleaning operation will be affected if not wired correctly.
Timer and Solenoid Specifications
Power to the solid-state timer is supplied to Terminals
L1 and L2, which are intended to operate in parallel
with the fan starter’s low-voltage coil. On fan start-up,
power is supplied to the timer and the preset OFF time is
initiated. At the end of the OFF time, the timer energizes
the corresponding solenoid valve to provide the ON time
cleaning pulse for one diaphragm valve and then steps to
the next until all filters have been cleaned.
To pulse when the fan is OFF, install a toggle switch as
shown on the Solid-State Timer Wiring Diagram. When
the toggle switch is ON, the timer receives power and
energizes the solenoid valves’ pulse-cleaning operation
even though the fan is turned OFF.
1. Using the wiring diagram supplied, wire the
starter, solid-state timer and solenoid valves. Use
appropriate wire gauge for rated amp load as
specified by local codes.
2. Plug the program lug into the pin that corresponds
with the number of solenoid valves controlled.
3. With power supply ON, check the operation of the
timer and valves. The valves should open and close
sequentially at factory set 10-second intervals.
4. If a gauge or similar device is used to control the
solid-state timer, the jumper on the pressure switch
portion of the timer should be removed. The solenoid
valves will then pulse only when the differential
pressure reaches the high-pressure setpoint. The
valves will continue to pulse until the low-pressure
setpoint is reached.
The solid-state timer voltage
must match the voltage of the
rating of the timer provided (typically 120VAC).
Do not mount the solid-state timer directly
to the collector as mechanical vibration can
damage the timer.

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
14
Fan Starter Control Box
Disconnect
1FU
2FU
3FU
208-230V
60 Hz/3Ph
IL1
IL2
IL3
1M 1OL 1T1
1T2
1T3
230V
115V
H1 H2
H3 H4
X1 X2
stop
start
1M
1M
1TGS
fan
motor
OFF time ON time
program
pins program jumper
pressure
switch
timing
logic
power
supply control
logic
4FU, 3A
105 to 135 V
50-60 Hz
solenoid
valves
COM
L1
L2
L3
Disconnect, fuses, low voltage blower starter, and 1TGS switch are customer-supplied.
Note: Check that the program jumper is attached to the correct program pin number
for the number of solenoid outputs used.
Use wiring diagram provided with unit
Wiring by others
Wiring by factory
L1 L2 2
1
Solid-State Timer Typical Wiring Diagram
Input
105-135V/50-60Hz/1Ph
Output Solenoids
The load is carried and turned ON and OFF by the 200
watt maximum-load-per-output solid-state switch.
Pulse ON Time
Factory set at 100-milliseconds, or 1/10-second.
Do not adjust pulse ON time
unless the proper test equipment
is available. Too much or too little ON time can
cause shortened filter life.
Pulse OFF Time
Factory set at 10-seconds, adjustable from 1.5-sec
minimum to maximum 30-seconds.
Operating Temperature Range
-20° F to 130° F
Transient Voltage Protection
50 kW transient volts for 20-millisecond duration once
every 20 seconds, 1% duty cycle.
Solenoid Valves
115-Volt at 19.7 watts each

15
Donaldson Company, Inc.
jet tube
venturi
Step 3
Helix Tube
insert clamp
seal frame
Helix Tube Filter Detail
Helix Tube Filter Installation
1. Open access door and remove jet tube retainer.
(Retainer is only used on collectors that are 4 tiers or
taller.)
2. Remove jet tubes and set aside. Cover the openings
to the diaphragm valves. To remove jet tube, unbolt
the top of the jet tube from the top.
3. Remove the hex nuts securing the insert clamps.
Remove the clamps and set aside.
4. Starting on one side of the collector, place a helix
tube filter in a seal frame slot as shown Helix Tube
Filter Installation.
Be careful to not scrape the
filters when slipping them
through the seal frame.
5. Install a second helix tube filter adjacent to the prior
helix tube filter.
6. Install a venturi on both adjacent helix tube filters
and place a clamp over one end of both venturis.
Install a nut and tighten using a deep well socket
and extension. See Clamps and Inserts. Do not
overtighten. Maximum recommended torque is
20 ft/lb.
Note: Tighten bottom clamp first.
jet tube
(only 1 shown)
jet tube
retainer bar
Jet Tube Retainer Helix Tube Filter Installation

Dalamatic Cased, DLMC 1/2/15 through 4/8/15
16
Clamp and Inserts
venturi
Helix Tube
insert clamp
hex nut
Venturi Installation
7. Repeat to install all helix tubes.
8. Replace jet tubes with the open end pressed firmly
into its locator and the orifices directed toward the
helix tube filter. See Helix Tube Filter Detail.
8. Reinstall jet tube retainer bars on collectors 4 tiers
tall or taller.

17
Donaldson Company, Inc.
1. Check that the collector is securely bolted to the
floor or mounting pad.
2. Check that all duct installation is complete and all
removable panels are in place.
3. Check that all hopper outlets are fitted with
containers or closed to prevent airflow from entering
the system through the hopper outlets.
4. Check all electrical connections for tightness and
contact.
5. Check for proper rotation as noted on the fan and/or
hopper discharge device housing.
To reverse rotation, single-phase power supply:
Follow manufacturer’s instructions on the motor’s
nameplate.
To reverse rotation, three-phase power supply:
Switch any two leads on the motor junction box.
Do not interchange a power lead
with the ground wire. Severe
personal injury and/or property damage may
result.
6. Check and remove all loose items in or near the inlet
and outlet of the collector.
7. Check that all remote controls and solenoid
enclosures (if applicable) are properly wired and all
service switches are in the OFF position.
8. Check that all optional accessories are installed
properly and secured.
9. Turn power ON at source.
10. Turn the compressed-air supply ON. Set
compressed-air supply pressure to a level suitable
for the filters (90-psig).
11. Turn fan motor ON.
Do not look into fan outlet to
determine rotation. View the fan
rotation through the back of the motor.
Check that the exhaust plenum is free of tools
or debris before checking blower/fan rotation.
Stand clear of exhaust to avoid personal injury.
12. Turn the Solid-State Timer ON and check that valves
operate in the proper sequence by monitoring the
LEDs on the front panel.
13. Verify operation of interlocks and audible warning
system, if equipped.
Instruct all personnel on safe use and maintenance
procedures.
Electrical work during
installation, service or
maintenance must be performed by a qualified
electrician and comply with all applicable
national and local codes.
Turn power off and lock out electrical
power sources before performing service or
maintenance work.
Turn compressed air supply OFF, bleed and
lock out lines before performing service or
maintenance work.
Check that the collector is clear and free of all
debris before starting.
Do not install in classified hazardous
atmospheres without an enclosure rated for
the application.
Optional fans over 600 lbs must be
independently supported.
Preliminary Start-Up Check
Typical Start-Up Sequence
1. Turn powered discharge components, such as screw
conveyor or rotary airlock, ON.
2. Turn the equipment being served ON.
3. Turn Solid-State Timer and compressed-air supply
ON.
4. Turn main blower ON, if equipped.
Typical Shut-Down Sequence
To clear residual deposits from the filter bags, filter body,
and equipment served:
1. Turn main blowers OFF, leaving compressed-air
supply ON to allow off-line filter cleaning.
Note: Contact your Donaldson representative for
shutdown instructions for explosion vented
collectors.
2. Wait 10 to 15 minutes and turn Solid-State Timer and
compressor OFF.
3. Turn rotary valves, screw conveyors, or other
discharge devices OFF after the dust dislodged by
the aftershift cleaning is removed from the hopper.
This manual suits for next models
15
Table of contents
Other Donaldson Torit Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Watts
Watts Pure H2O Series Installation, operation and maintenance manual

AQUAPHOR
AQUAPHOR ONYX operating manual

Acqua Brevetti
Acqua Brevetti BravoMAX M Installation and operating manual

emaux
emaux NT-UV Series user manual

SkyJuice
SkyJuice SkyHydrant Set up and operating instructions

Potterton
Potterton ZLF 160 installation manual