Dor-O-Matic 96000 Series User manual

Series 96000 Slide Control
Installation Instructions
Dor-O-Matic
DOR - O – MATIC ®
7350 W. Wilson Ave.
Harwood Heights, IL 60706
Toll Free: 1-800-543-4635
In Illinois: 708-867-7400
Sales FAX: 708-867-0291
Technical Support 1-888-942-9945
www.doromatic.com
84657-084 REV. B July 2003

INSTALLATION
1. Preparation: Refer to Series 96000 Slide Installation Manual (DOM #96000-984) for header preparation instructions.
NOTE: Always disconnect
main power to operator prior to
servicing or cleaning.
2. Final Wiring Connections:
The Series 96000 header comes from the factory “pre-wired” to minimize installation time at the job site. Connect main power to the terminal block
at the end of the header (Figure 1). Connect accessories to the terminal block on the safety beam bracket or control box as needed (Figure 2).
Refer to the instruction manual of the accessory for complete wiring details.
A. Use a 115 volt, 60Hz, fused, 15 amp, 3-wire power supply.
B. Externally route the main power to the side of the header with the terminal block.
Do not run the main power in the wire channel the length of the header.
C. When wiring the header, place the main power in one wire channel and the accessory wiring in the other.
D. Secure all conductors and connections against physical damage.
E. Route all wiring away from moving parts, sharp edges and heat sources. Manually and slowly push doors open and closed and observe that
parts do not interfere with the wiring.
F. Use copper conductors only.
FIGURE 1: POWER WIRING DIAGRAM
84657-084 REV. B July 2003 Page 2 of 7

Orange
Red
White-Black
Blue
Red-Black
Green
Black
White

1. Close doors.
2. If the 4-position switch is used, be sure it is in the “2-way” position before proceeding.
3. Apply power to the system using the main power switch on the header/cover.
4. Apply an activation signal (activate inside or outside motion sensor, press keypad “test activate” or momentarily move the
4-way to the hold position).
5. Observe sizing cycle. If door slams open or closed, reduce sizing speed (SS) setting. Remove power and repeat steps 3
to 5.
Note: Allow the door to remain at the fully closed position for a minimum of one (1) second to complete the sizing
mode.
Caution: If the door sizing speed is set too fast, blown fuses and/or a tripped circuit breaker may occur if the
doors are activated when manually locked.
6. After sizing is complete, make adjustments to other settings as needed.
SETTING
: OPENING SPEED
: AUTO-REVERSE-OPEN
: BACKCHECK POSITION
: BACKCHECK SPEED
: HOLD-OPEN DELAY
: CLOSING SPEED
: AUTO-REVERSE-CLOSE
: LATCH POSITION
: LATCH SPEED
: ENERGY-WISE POSITION
: ELECTRIC LOCK
: SIZING SPEED
: FUNCTION
: STATUS ANNOUNCEMENT
SETTING VALUE
UP UP
DOWN DOWN
TEST
ACTIVATE
84725-600 REV. 0
DEFAULT
KEYPAD LABEL DRAWING
84657-084 REV. B July 2003 Page 4of 7

Setting Setting
Display
Value
Ranges
Factory
Default
Settings
Description
Opening speed OS 1 to 99 85 Controls the opening speed of the door. It is recommended that
the door be operated as slowly as practical for the traffic
conditions.
Auto-reverse opening AO 1 to 99 75 Controls the amount of force required to reverse the door when
opening (see FEATURES).
Backcheck position bP 1 to 32 08 Controls where backcheck position starts.
Backcheck speed bS 50 to 99 80 Controls the door speed during backcheck.
Hold Open Delay hd 1 to 32 01 Controls the amount of time the door stays open. If a presence
sensor is not installed, the time delay must be at least 4 seconds.
Closing speed CS 1 to 99 75 Controls the closing speed of the door. It must not exceed 1
ft/sec.
Auto-reverse closing AC 1 to 99 50 Controls the amount of force required to reverse the door when
closing (see FEATURES).
Latch position LP 1 to 32 07 Controls where latch position starts. It must be at least 2 inches
from the fully closed position.
Latch speed LS 50 to 99 85 Controls the door speed during latch.
Energy-wise EP 50 to 75 50 Adjusts the open position of the door from 50% to 75% of full
open when energy-wise switch is set to narrow.
Electric Lock EL ON or
OF
OF Enables (ON) or disables (OF) the electric lock delay. If EL is set
to OF, the door opens immediately upon reception of the
activation signal. If EL is set to ON, when the door is fully closed,
there is a 1 second delay between reception of the activation
signal and the actual opening of the door. This delay allows most
electric or magnetic locks time to unlock before the door opens.
Sizing speed SS 50 to 99 85 Controls the speed of door during sizing.
Function Fn 00 00 This setting not used at this time.
Status Announcement SA 00 00 This setting not used at this time.
Reset Power:
If main power needs to be reset for any reason, power must remain off for a minimum of ten (10) seconds to allow proper discharge of internal
circuitry.
84657-084 REV. B July 2003 Page 5of 7

1. Keypad Label 10. J10C 19. J1 (AC In)
2. Setting Down 11. J10A 20. CB1
3. Setting Up 12. Test Activate Push Button 21. F1 (Main Fuse)
4. Value Down 13. Value Display 22. J3 (Hall Effect Sensor)
5. Value Up 14. Setting Display 23. J2 (Factory Wired Sensors)
6. Default Setting Push Button 15. J7 (Transformer Secondary) 24. J5 (Electric Lock Circuit)
7. Description Label 16. J8 (Sensor Power) 25. J6 (Not Used)
8. Transformer 17. F2 (Sensor Fuse) 26. J4 (Motor Drive)
9. J10B 18. J9 (Transformer Primary)
FIGURE 3: CONTROL BOX FEATURES
CB1 (MOTOR/CONTROL CIRCUIT BREAKER)
4. Operational Walk-Through Test:
NOTE: It is assumed that during the installation process, any problems would have been found and corrected before this point. However, it is
recommended that a complete walk-through test now be performed.
A. Give the system an activation signal. The door should open smoothly and silently to the back check point, where it should slow down rapidly
and drift into the fully open position without slamming.
B. Maintain the activation signal to verify that the door does NOT time out and close while being activated.
C. If a door safety device is used, step into the door opening. Remain in the door opening making sure that the door does NOT close.
D. Step out of the door opening. After both the activating area and door opening are clear, the door should time out at the pre-set time delay and
begin to close. The door should close quietly and smoothly to the latch point, where it rapidly slows down and drifts into the fully closed
position without slamming.
5. Release of the System for Use:
A. Remove all tools and installation equipment, and clean any debris from the vicinity of the door.
B. Install all safety, traffic control, and instruction decals to the door as required. THIS IS VERY IMPORTANT! Failure to do this leaves the
installer LIABLE for any accident that might occur. THIS MUST BE DONE!
C. Verbally explain the proper operation of the door system to the owner or to the person in charge.
6. For Doors that are manually/mechanically secured:
A. Locking:
1) Place switch in “OFF”
2) Allow door to close completely
3) Secure door
B. Unlocking inside:
1) Unsecure door
2) Place switch in “1-WAY” or “2-WAY”
3) Activate door once
C. Unlocking outside:
1) Unsecure door
2) Activate morning entry or manually open door
3) Place switch in “1-WAY” or “2-WAY”
84657-084 REV. B July 2003 Page 6of 7

84657-084 REV. B July 2003 Page 7of 7
FEATURES
1. Easy Open: When the door is fully closed and manually opened a few inches, it will automatically open the rest of the way.
2. Adjustable Automatic Reversing: If the door is stalled during the closing cycle, it will automatically stop and reverse to the fully open position. Then
the door will close to the point of obstruction and drop to slow speed, looking for the obstruction. This cycle will occur 5 times until the obstruction is
removed. After the fifth cycle, the door will stop, requiring an activation signal or manual opening to re-start the system. If the door is stalled during
the opening cycle, it will automatically stop and reverse to the fully closed position. The door will remain closed until the next activation signal, at
which point it will open normally. Reversing forces should be adjusted in accordance with all applicable safety codes.
3. Energy-wise (Optional): The energy-wise feature allows the customer to reduce the opening size. When the weatherwise switch is set to
“NARROW”, the door will only open from 50% - 75% of the normal door opening.
(If energy-wise not used, door opens to 100% of opening)
4. Beam Shut-Off: So the door is fully closed, the beam signal is disregarded so that it cannot be used to open the door. Once the door is activated,
the beam signal is allowed to re-open the door if either safety beam is interrupted during the closing cycle.
5. 4-Way Switch Operation:
When the 4-Position Switch is set to:
“OFF”, easy open, interior and exterior activation will not open the door. The morning entry switch will open the door.
“1-WAY”, only interior activation will open the door. Exterior activation will not open a closed door but will re-open a door in the closing cycle.
“2-WAY”, interior and exterior activation will open the door.
“HOLD OPEN”, the door will remain open.
If the 4-Position Switch is not used, Default = “1-WAY”.
6. Morning Entry (Optional): The morning entry feature allows outside entry using a keyswitch when the 4-way switch is in the OFF position. The
morning entry switch connects to the controller terminal block between COMMON and MORNING ENTRY (see Figure 2).
7. Sidelite Safety (Optional): The sidelite safety feature slows the opening speed of the door when an obstruction is sensed in the sidelite area. The
sidelite safety sensor contacts connect to the controller terminal block between COMMON and SIDELITE SAFETY (see Figure 2).
DO’S AND DON’TS
1. Do NOT try to use this operator on large, heavy doors without checking with the factory first.
2. Do NOT connect any remote activating device to the door unless it is located within the ”line of sight” of the door.
3. Do NOT attempt to use a fuse larger than specified.
4. Do NOT attempt to modify the factory wiring or connect any wiring into an existing electrical circuit or any other electrical device.
5. Do make certain that the operator is connected to a dedicated 115 volt circuit from the main circuit breaker panel.
6. Do make certain that the operator is properly grounded with a separate green wire.
7. Do make certain that all connections are proper and secure before turning the power on.
8. Do make certain that all wires are properly dressed and secured to prevent any interference.
9. Do make certain that all safety labels and instruction decals relating to door operation are properly applied to the door before leaving the job.
10. Do verbally instruct the owner or person in charge of the proper operation of the door.
11. Do disconnect main power to the operator prior to servicing or cleaning.
12. Do instruct the owner or person in charge of his responsibility of inspecting the door for the following:
A. Occasional damage
B. Developing problems
C. Minor preventative maintenance
D. Who and where to call for service when required.
Table of contents