manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. iNels
  6. •
  7. Controllers
  8. •
  9. iNels JA3-018M User manual

iNels JA3-018M User manual

JA3-018M
02-9/2019 Rev.0
1/2
2
6
3
6
6
4
BUS +
BUS -
N
L
L
N
M M M
M M M
M M M
N
L
1
4
5
5
UP x
COM x
DOWN x
Shutter Actuator, 18-channel
EN
Characteristics
General instrucions
Description of device
Connection
CONNECTION TO THE SYSTEM, INSTALLATION BUS
iNELS3 peripheral units are connected to the system through the BUS installation. Installation
BUS conductors are connected to the terminal units to BUS+ and BUS- terminals, wires cannot be
interchanged. For installation of BUS it is necessary to use a cable with a twisted pair of wires with
a diameter of at least 0.8 mm, the recommended cable is iNELS BUS Cable, whose features best
meet the requirements of the BUS installation. Bearing in mind that in terms of all the properties
is it is possible in most cases also use the cable JYSTY 1x2x0.8 or JYSTY 2x2x0.8, however it
is not recommended as the best option. In the case of a cable with two pairs of twisted wires
it is not possible to use the second pair of the other for modulated signal due to the speed of
communications; it is not possible within one cable to use one pair for one segment BUS and the
second pair for the second segment BUS. For installation of BUS it is vital to ensure that it is kept
at a distance from the power lines of at least 30 cm and must be installed in accordance with its
mechanical properties. To increase mechanical resistance of cables we recommend installation
into a conduit of suitable diameter. BUS topology installation is free except for the ring, wherein
each end of the bus must terminate at the terminals BUS + and BUS- peripheral unit. While
maintaining all the above requirements, the maximum length of one segment of the installation
BUS can reach up to 500 m. Due to the data communication and supply of units in one pair of wires,
it is necessary to keep in mind the diameter of wires with regards to voltage loss on the lead and
the maximum current drawn. The maximum length of the BUS applies provided that they comply
with the tolerance of the supply voltage.
CAPACITY AND CENTRAL UNIT
It is possible to connect to the central unit CU3-01M or CU3-02M two independent BUSes by means
of terminals BUS1+, BUS1- and BUS2+, BUS2-. It is possible to connect to each BUS up to 32 units,
so it is possible to connect directly to the central unit a total of 64 units. It is necessary to comply
with the requirement of a maximum load of one BUS line - maximum up to 1000 mA current. When
connecting units which draw greater than 1A, BPS3-01M with 3A sampling can be used. It is the
sum of the rated currents of the units connected to the BUS line, other units can be connected
using the units MI3-02M, which generate further BUSes. These are connected to the CU3 unit via
the system BUS EBM and you can connect a total of 8 units via EBM BUS to the central unit MI3-02M.
SUPPLYING THE SYSTEM
For supplying power to system units, it is recommended to use the power source of ELKO EP titled
PS3-100/iNELS. We recommend backing up the system with backup batteries connected to the
source of PS3-100/iNELS (see sample diagram of connecting the control system).
GENERAL INFORMATION
To operate the unit, it is necessary that the unit is connected to a central unit CU3 series, connected
to the central unit of the system CU3, or to a system that already contains this unit as its expansion
to include further system.
All unit parameters are set through the central unit CU3-01M in the software iDM3.
There is LED diode on the PCB for indication of supply voltage and communication with the
central unit series CU3. In case that the RUN diode flashes at regular intervals, so there is standard
communication between the unit and BUS. If the RUN diode lights permanently, so the unit is
supplied from BUS, but there is no communication between BUS and unit. In case that RUN diode
is OFF, so there is no supply voltage on the terminals BUS+ and BUS-.
1. Supply terminals
2. Data BUS
3. LED indication of unit´s state
4. Output LED indication
5. Control buttons
6. Relay contacts
• JA3-018M is an actuator designed for control of roller shutters, blinds, awnings, garage doors,
entrance gates, etc.
• It controls electric drives that are controlled in two directions and have a built-in limit switch.
• The unit's status is indicated by the green RUN LED on the front panel
- If the power supply is connected, but there is no communication via BUS with master, the LED
RUN is on continuously.
- If the supply voltage is connected and the unit communicates by BUS, the LED RUN flashes.
• The status of the output contacts is indicated by the U/D LED:
- When the blind / roller blind is moving up / down, the corresponding LED lights up.
- If the number of switching operations per minute is exceeded, the corresponding LED flashes.
• JA3-018M in 6-MODULE version is designed for mounting into a switchboard on DIN rail EN60715.
Made in Czech Republic
2/2
JA3-018M JA3-018M/120V
ELKO EP, s.r.o. | Palackého 493 | 769 01 Holešov, Všetuly | Czech republic | e-mail: [email protected]
TECHNICAL SUPPORT | E-mail: [email protected] | Mobil: +420 778 427 366 | Tel.: +420 573 514 276, +420 573 514 211 | Fax: +420 573 514 227 | www.inels.com
Technical parameters
Warning
Before the device is installed and operated, read this instruction manual carefully and with full
understanding and Installation Guide System iNELS3. The instruction manual is designated for
mounting the device and for the user of such device. It has to be attached to electro-installation
documentation. The instruction manual can be also found on a web site www.inels.com. Attention,
danger of injury by electrical current! Mounting and connection can be done only by a professional
with an adequate electrical qualification, and all has to be done while observing valid regulations.
Do not touch parts of the device that are energized. Danger of life-threat! While mounting,
servicing, executing any changes, and repairing it is essential to observe safety regulations, norms,
directives and special regulations for working with electrical equipment. Before you start working
with the device, it is essential to have all wires, connected parts, and terminals de-energized. This
instruction manual contains only general directions which need to be applied in a particular
installation. In the course of inspections and maintenance, always check (while de-energized) if
terminals are tightened.
9x changeover 4 A/AC15
250 VAC, 24 VDC
1000 W/AC15, 100 W/DC
10 A
basic insulated.
(Cat. III surges by EN 60664-1)
basic insulated.
(Cat. II surges by EN 60664-1)
1 kV
100 mA / 10 V DC
300 min-1
15 min-1
1x 107
1x 105
9x yellow LED
BUS
green LED RUN
27V DC, -20 / +10 %, 5mA
AC 230V (50 Hz), AC 120V (60 Hz),
-15 / +10 %, 20 mA -15 / +10 %, 40 mA
max. 2 W
max. 2.5 mm2/1.5 mm2with sleeve
-20 to +55 °C
-30 to +70 °C
IP20 device, IP40 mounting in the switchboard
II.
2
any
switchboard on DIN rail EN 60715
6-MODULE
90 x 105 x 65 mm
346 g
Outputs
Output:
Switched voltage:
Switched output:
Peak current:
Output relays separated
from all internal circuits:
Isolation between relay out-
puts GATE1, GATE2 and GATE3:
Isolates. voltage open
relay contact:
Minimal switched current:
Switching frequency without
load:
Switching frequency with
rated load:
Mechanical life:
Electrical life AC1:
Output indication:
Communication
Installation BUS:
Status indication unit:
Power supply
Supply voltage by BUS /
tolerance / nominal current:
Supply voltage of power
section (relay) / tolerance /
nominal current:
Dissipated power:
Connection
Terminal:
Operating conditions
Operating temperature:
Storing temperature:
Protection degree:
Overvoltage category:
Pollution degree:
Operating position:
Installation:
Design:
Dimensions and weight
Dimensions:
Weight:
Flashing interval of the respective LED when the maximum number of contacts is exceeded when
the relay is switched on:
Flashing interval of the respective LED when the max. Number of contacts is exceeded when the
relay is switched off:
Indication LED
Flashing interval of all LEDs in case of power failure with relay on:
Flashing interval of all LEDs in case of power failure with relay off:

Other iNels Controllers manuals

iNels RFDAC-71B User manual

iNels

iNels RFDAC-71B User manual

iNels RFGB-20 User manual

iNels

iNels RFGB-20 User manual

iNels IM2-140M Simple manual

iNels

iNels IM2-140M Simple manual

iNels JA3-014M User manual

iNels

iNels JA3-014M User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels RFDEL-76M User manual

iNels

iNels RFDEL-76M User manual

iNels SA3-02M User manual

iNels

iNels SA3-02M User manual

iNels RF KEY - 40 User manual

iNels

iNels RF KEY - 40 User manual

iNels WTC2-21 Simple manual

iNels

iNels WTC2-21 Simple manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels RFDA-73M/RGB User manual

iNels

iNels RFDA-73M/RGB User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels MI2-02M Simple manual

iNels

iNels MI2-02M Simple manual

iNels RFOWB-20 User manual

iNels

iNels RFOWB-20 User manual

iNels RFDW-71 User manual

iNels

iNels RFDW-71 User manual

iNels SA3-02M Instruction manual

iNels

iNels SA3-02M Instruction manual

iNels SA3-012M User manual

iNels

iNels SA3-012M User manual

iNels RFSTI-111B User manual

iNels

iNels RFSTI-111B User manual

iNels SOPHY2 User manual

iNels

iNels SOPHY2 User manual

iNels RFGB-40 User manual

iNels

iNels RFGB-40 User manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels SA2-04M Simple manual

iNels

iNels SA2-04M Simple manual

iNels RFWB-20/G User manual

iNels

iNels RFWB-20/G User manual

iNels RF KEY User manual

iNels

iNels RF KEY User manual

Popular Controllers manuals by other brands

smart home INSTEON Touchlinc 2448 owner's manual

smart home

smart home INSTEON Touchlinc 2448 owner's manual

RainMaster Irritrol TWICE quick start guide

RainMaster

RainMaster Irritrol TWICE quick start guide

WindowMaster MotorController WCC 310 Installation instructions manual

WindowMaster

WindowMaster MotorController WCC 310 Installation instructions manual

Delta ASDA-A2 Series quick start

Delta

Delta ASDA-A2 Series quick start

Wyrestorm NetworkHD 100 series quick start guide

Wyrestorm

Wyrestorm NetworkHD 100 series quick start guide

Smarte VHX-7000-H user manual

Smarte

Smarte VHX-7000-H user manual

Data Video TPC-700 instruction manual

Data Video

Data Video TPC-700 instruction manual

GOAL ZERO 10 AMP user guide

GOAL ZERO

GOAL ZERO 10 AMP user guide

System air MZ3-Touch user manual

System air

System air MZ3-Touch user manual

SUNFLEX V6A FM user manual

SUNFLEX

SUNFLEX V6A FM user manual

digitalview 41721002X-3 instructions

digitalview

digitalview 41721002X-3 instructions

Homeline TWINDRIVE TD4 Advanced user manual

Homeline

Homeline TWINDRIVE TD4 Advanced user manual

EP Solar ViewStar Series user manual

EP Solar

EP Solar ViewStar Series user manual

Ink Bird ITC-100 user manual

Ink Bird

Ink Bird ITC-100 user manual

Sunricher SR-2831 manual

Sunricher

Sunricher SR-2831 manual

VIPA System 300S SPEED7 - CPU 315-4NE12 manual

VIPA

VIPA System 300S SPEED7 - CPU 315-4NE12 manual

Titanium TT-DX-01 quick start guide

Titanium

Titanium TT-DX-01 quick start guide

BRIDGEWERKS Magnum 200R user manual

BRIDGEWERKS

BRIDGEWERKS Magnum 200R user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.