D+H RZN 4416-M User manual

99.823.211.2/07/08
Instruction for use
D+H Mechatronic AG • Georg-Sasse-Str. 28-32 • D-22949 Ammersbek • Tel. +4940-60565219 • Fax +4940-60565264
Smoke Vent System
RZN 4416-M
installation
Safety system protects human life and material assets!
Connection, mounting and functional testing by a
specialist company authorized by the manufacturer.
Green control diodes in the buttons must constantly lighten,
otherwisesee"InformationsforStarting".
Repairpowerfailureatonce.Emergencypowersupplyfor72hours.
drive
group **
alarm *
signal indicating
board *
signal
contact *
2 lines
control
contact
of external
system *
2 lines
smoke or
thermal
detector
rain
detector
2 lines
smoke vent
button
230V/50Hz
power supply
ventilating
button * **,
* optional extension
of function
(separate components can
be retrofitted)
** RZN 4416-M / 3 groups
or
<>

2/20 RZN 4416-M Rev.:1.1
Maintenance
Oncea yearby a specialistcompany, whois
authorized by the appliance manufacturer.
Renew test badge, keep control book.
The respective current D+H maintenance
instruction is decisive.
D+H authorized expert companies have
been specially trained by D+H for carrying
out expertly this maintenance, and they get
automatically the latest maintenance
instructions.
Following tests must be carried out in the
course of maintenance:
- Outside examination / inspection of
system components
- Measuring of insulation resistances
- Checking of all relevant power supply units
- Functional testing of connected system
components
- Record of competent carrying-out of
maintenance, and designation according
to directions
Piktograph explanation
Content
Maintenance / Guarantee / Piktograph explanation ..............................................................2
Technical Data / Accumulator Control TID .............................................................................3
Introduction..............................................................................................................................4
View motherboard RZN 4416-K .............................................................................................5
Drives and smoke vent buttons .............................................................................................6
Wiring plan ..............................................................................................................................7
Connection cables..................................................................................................................8
Connection plans.............................................................................................................. 9-15
Starting ................................................................................................................................. 16
Encode of Line/ Group / control panel............................................................................ 17-19
Examination ......................................................................................................................... 20
Guarantee
You will get 2 years guarantee for all D+H products from date of verified handing over of the
system up to maximal 3 years after date of delivery, when mounting and starting has been
carried out by a D+H authorized distributor.
D+H guarantee is expired, with connection of D+H components with external systems or
with mixing of D+H products with parts of other manufacturers.
OK
Smoke and heat vent alarm
Control panel O.K.
Power supply
Vent button function “ON”
Vent/ smoke vent function “OFF”
Fault
Charging voltage regulator
Ground short
Regulator for OPEN-running time limitation
Regulator for ventilating time limitation
Fuse
Reset
min
15
245
30
sec
20
260
40

3/20
RZN 4416-M Rev.:1.1
24 V - Emergency Supply
Emergency power supply for 72 hours
Use VdS approved storage batteries only!
2x 12 V / 7.0Ah ±15 %
With connection of D+H alarm devices:
2x 12 V / 12Ah ±15 %
Accumulator Control TID
T Temperature-guided charging of accumulator
I Impedance measuring
Internal resistance of accumulator will be measured cyclically.
For example, if a total discharged accumulator is connected to the control panel
= malfunction (LED on PCB)
D Discharge control
In case of power failure and total discharge of accumulator, the control panel will
switch off. In this case, smoke vent is no longer ensured. In this case a malfunction
will be no more indicated either.
Technical Data
Rated voltage : 230 VAC, 50 Hz
Rated capacity : 500VA
Capacity Consumption
standby : 13.6 W
Interfering emission : EN 50081-2, EN 55022
Res. to jamming : EN 50082-1, EN 61000-4-2 to -6, EN 50204
Protective category : I
Fire resistance : -5 to + 40 °C
Protective system : IP 54
Class of rating
- Monitoring : Continuous duty
- Emergency state/ ventilation : Short-time duty
Output voltage : 24 VDC / res. ripple <10 %
Safe output
- rated current : 12.8A
- cutoff current : 16A
- each group max. : 6.3 A rated current resp. 8 A cutoff current
Dimensions : 500 x 500 x 210 (W x H x D)

4/20 RZN 4416-M Rev.:1.1
Important Regulations
Observe regulations for danger warning systems VDE 0833, guidelines for electrical systems VdS 2221, VDE 0100,
DIN 18232 for smoke and heat vent systems, regulations of the local fire-brigade and of EVU for connection to mains
supply.
Introduction
Smoke and heat vent systems (RWA´s) are very important elements of structural
preventive fire protection.
Smoke and heat vent systems are appliances of preventive fire protection. They fulfil important functions in case of
fire: protection of human life by providing a smokeless layer, by which rescue routes are kept free for the fire-
brigade. Consequential damages by conflagration gases are reduced, and therefore, considerable material assets are
often protected from destruction. Precondition for this is, that the systems will function absolutely reliable in a case
of fire. Only electrical specialist companies are authorized to install these systems, who have electrical specialist
staff with relevant experiences in installing danger alarm systems or smoke and heat vent systems. Only these ones
can take on responsibility for functioning, and can ensure product liability for the whole system (see product liability
law BGBL.I S.2198 and BGB (bodily injury, compensation for damage)).
Therefore, regular maintenance and checking of functional readiness is imperative and has to be ensured. These
standard requirements are demanded according to regulations of the DIN, of the Association of German Insurer
against damage of property (VdS) and the respective local authorities. Recommended is, that maintenance work
should be carried out by authorized specialist companies, only.
Only regular and professional maintenance warrants the necessary and permanent
functional safety.
Only authorized specialist companies are allowed to install and maintain smoke and heat vent systems and system
components, constructed and distributed by D+H Mechatronic AG.All D+H Mechatronic AG partners belong to these
authorized specialist companies, who regularly undergo an in-house training to ensure their qualification and experience.
Smoke and heat vent systems must be maintained at annual intervals by authorized specialist companies according
to DIN 18232 section 2 paragraph 10.2, and VDE 0833 section 1 paragraph 5.3.4 for alarm systems and manufacturer
guidelines.
According to DIN VDE 0108 section 1 paragraph 9.1.1 accumulators for emergency supply (lead accumulators) must
be checked every six months by a person, who has been introduced to this task, and once a year, maintenance must
be carried out by specialist companies. Accumulator types, which are used for D+H Mechatronic AG smoke and heat
vent systems must be VdS approved, and must be released by D+H Mechatronic AG to use in smoke and heat vent
systems. According to DIN 18232 section 2 paragraph 10.2 the tests must be put down in an operational book, which
the operator/ building owner must present to the building supervision authority on request. This operational book is
available at D+H (Ord.-No.: 68.700.15)
Executed maintenance must be proved by a D+H Mechatronic AG maintenance/ and testing confirmation.
Inside Design
Akku-Position

5/20
RZN 4416-M Rev.:1.1
View motherboard RZN 4416-M
12345678
ON SAB
12345678
ON SAB
1234
ON SAB
12345678
ON SAB
1234
ON SAB
12345678
ON SAB
fuse EXT.
indication
alarm reset
line 1 ON/ OFF -
reset indicator
LED failure line 1
DIP switch S1
LED-
control
LED alarm line 1
DIP-switch S2 fuse drive
group 2
LED failure
group 2
DIP-switch S4
DIP-switch
S3
LED failure
line 2
LED alarm
line 2
LED failure
group 1
fuse drive
group 1
Alarm Reset
line 2 ON/ OFF
reset indicator
fuse
accumulator
accumulator -
connection LED-failure
accumulator
charging voltage
control accumulator
fire recognition element
(thermo maximum signal)*
ground short
DIP-switch S6
control panel
configuration
potentiometer
for
OPEN-running
time limitation
potentiometer
for ventilating
time limitation
fuse
drive
group 3
LED
failure
group 3
DIP- S5switch
power
supply LED-power
supply
RZN 4416-M
* for monitoring of the internal temperature of the control device. If the internal temperature is exceeding 72°C (caused by radiant
heat of a fire in immediate vicinity of the mounting place), the entire smoke and heat vent system will be emergency opened
under alarm conditions.

6/20 RZN 4416-M Rev.:1.1
Smoke Vent Button
Place(s) of mounting:
Maximal 8 smoke vent buttons can be
connected.
Maincontrol must bemountedonground-floor
according to VdS 2221.
Secondarycontrolistobeinstalledinallother
floor levels according to VdS 2221.
Install buttons so, that they are accessible
any time and clearly visible.
Mounting height:
1,5m above upper edge of firm flooring.
Fastening:
With plug screws 4,5 x 40mm diagonal, or
direct on 55mm flush box with 2 screws.
Housing colour:
Standard:deep orange (RAL2011),
according to VdS 2592.
However, deviating colours might be locally
required (e.g. grey, blue, yellow, red).
Please consult your D+H distributor.
Drives
Smoke and heat vent opening:
Smoke gases are to be carried off as
unhindered as possible through smoke and
heat vent opening in case of fire.
According to relevant rules, openings have
to be placed always in the upper part of a
building.
The smoke and heat vent opening can be
mounted in the wall as well as in the ceiling.
Size, kind and arrangement of the opening
is of decisive significance for an optimal
effect of the smoke and heat vent system.
The important thing here is, that an escape
must not be hindered by the window wing
itself, by structural facts like offsets, or the
like.
Minimum ventilating surface is given by le-
gal regulations and structural facts. The
smoke vent opening must be at least 1m² or
5% of the basis, dependent on the LBO.
The valuated sizes of opening angles of
smoke and heat vent systems must be in
agreement with the responsible fire
protection authority.
Observe!Windowwings,openinginward, must
not project in escape/ and rescue routes and
obstruct them.
High-Speed function:
All D+H drives with SHEV high-speed
function are supported. In daily ventilation
operation, a considerable noise reduction
is achieved through the reduced drive speed.
In case of SHEV the drives run - triggered
through the orange monitoring line - with a
very high speed to reach the OPEN position
defined within 60 seconds at the most.
Mounting of the drives:
Please take mounting informations from the
relevant instruction for use of the respective
drive, because of varied possibilities for
choosing drives.
Attention:
When Dip switch 8 is on ON, the smoke
vent will be triggered with an OPEN-
impulse every 2 minutes for a duration of
30 minutes according to VdS 2581. For this,
the drive must be blockage safe according
to VdS 2580 par. 4.7. . All D+H drives meet
this precondition. Otherwise Dip switch 8
is to be switched on OFF.

7/20
RZN 4416-M Rev.:1.1
M
230VAC
24VDC
Legend
Drive 24VDC at smoke vent flap
(Lines must end in flush
mounted distribution box, see
symbols above).
RZN surface or flush type
(230VAC / 24VDC) in proximity
of smoke vent flap.
Smoke vent button (RT43-H/N)
surface24VDCcirca1,5m above
upper edge firm flooring ( 55mm
flush socket by customer)
Vent button 24VDC (e.g. LT 43)
circa 1,2 above upper edge firm
flooring (at flush type 55mm
flush socket by customer)
Fire detector 24VDC
(FO 1362 or FT 1262)
Wiring Plan (Paragon)
230 V Supply
Provide for separate electric circuit.
Mark fuses.
Plug covering cap over mains binder on
motherboard of control panel.
Connecting cable: NYM-I 3x1.5
Connecting load: 500VA
Weak Current Lines
Install and feed separately from supply
mains.
Mark cable and terminal box red.
M
to further
ones
to further
ones
See cable wiring table
JY (St) Y
2x2x0,6
Fire
detector
Ventilation
button
Contact
external control
Secondary
control
Main control
230V 50Hz
not possible to switch off
JY (St) Y
2x2x0,6
JY (St) Y
4x2x0,6
JY (St) Y
4x2x0,6
JY (St) Y
2x2x0,6
Control
panel
230VAC
24VDC
Drive

8/20 RZN 4416-M Rev.:1.1
Gesamtstrom /
total consumption 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10
3x 1,5mm² 240 120 80 60 48 40 34 30 26 24 21 20 18 17 16 15 14 13 13 12 m
3x 2,5mm² 400 200 130 100 80 65 55 50 44 40 36 33 30 28 26 25 24 22 21 20 m
*5x 2,5mm² 800 400 260 200 160 130 110 100 88 80 70 65 60 56 52 50 47 44 42 40 m
**7x 2,5mm² 1200 600 390 300 240 200 170 150 130 120 110 100 92 85 80 75 71 67 63 60 m
Detector Cables (Line):
The detector cables are monitored for short
circuit and for break.
The opening device is automatically
triggered and opens up in case of fault, when
DIP-switch 7 is on ON.
Smoke vent button cable and cable of
automatic detectors:
- weak current sheathed flexible cable YR
6 x 0.8
or
- house wiring cable IY(ST)Y 4 x 2 x 0.6
Cables through areas not monitored:
An increased time of functioning of the cable
canberequired,whendrivelinesareinstalled
throughbuildingparts,whicharenotmonitored.
- Safetylinewith functional conservation
... E90, according to DIN 4102* or standard
guidelinesfor line systems MLAR.
(see supplementary sheet 1 to DIN VDE
0108)
* Notice: No type designation is given
for these cables, because of a large
variety on the market. Please consult
your D+H distributor about these.
The smoke vent control panel is designed
for opening smoke vent devices, which
operate by thermal ascending force and by
automatic fire recognition devices (thermal
detector, smoke detector), and they release
either self-acting or manual by smoke
detectors at an early stage of a fire, and
remain in opened position without further
power consumption. In these cases,
functioning preservation of the electrical line
system is required only at an early stage of
fire. Protected wiring is required with
protection against mechanical damages
according to DIN 18232 section 2.5.5
paragraph 4.
Control Cables (Group):
Cables from the smoke vent control panel to
connection of drive (drive lines have a
monitoring wire, in which fire recognition
devices (thermal maximal detector e.g. THE)
canbelooped-in):
- Safetyline,withfunctional conservation
... E30, according to DIN 4102* or standard
guidelines for line systems MLAR.
Cables for D+H Smoke and Heat Vent Systems
cross section (mm²) = plain cable length (m) x total current
80
* Connect in parallel 2 wires for each drive line.
Line lengths and Cross sections:
Number of wires and cross-sections indicated, refer to required lines only. In case of
using a line with earthed conductor (green/ yellow), this one will not be counted in and
must not be wired.

9/20
RZN 4416-M Rev.:1.1
Standard Connection with RT 43-H / -N
10k *W
line
line
–
–
closed
open signal (optional)
–N
open
monitored
Mot.a
Mot.b
56712341122
optional
RM RT LT
345678
line
-
control
alarm
closed
malfunction
external
excitiation vent button
LT 43 (-SD)
fire
detector
Typ**
operating contact
alarm resistor
10k *W
10kW
1kW
out
out
in
in
closed
–N
open signal
open
last
first or
penultimate
first or
penultimate
LT 43
L
L
P
P
RZN 4416-M
drives***
brown
blue
black
orange
2x47kW
black
brown
blue
thermal
detector
THE 4
RZN 4416-M
RM MOT
branch box
Length of line and
cross sections,
see page 12
<>
last
RT 43-N
10kW
alarm
control
-
line
line
malfunction
closed
27
83164
line
-
control
alarm
closed
23164
7
5
smoke vent button
RT 43-H
alarm
zu
red
green
yellow
2 resistors
47k or
terminal
module
W
* Terminal resistors for line monitoring:
They are pinched in control panel for transport. Take it off there and connect according to
plan. Terminal resistors must remain at binder RM 1,2, when no fire detector or external
control exists.
** Fire detectors
Only D+H system approved detectors must be used (see page 7).
***For detailed information concerning the connection, please refer to the instruction for
use of respective drive.

10/20 RZN 4416-M Rev.:1.1
Parallel Connection of
Smoke Vent Buttons - RT 43-H / -N
**Fire detectors
Only D+H system approved detectors must be used (see page 7).
345678
RZN 4416-M
line
–
control
alarm
closed
RM/RT
Smoke vent button
RT 43-H
Smoke vent button
RT 43-N
10kW
alarm
alarm
control
control
-
-
line
line
line
line
malfunction
closed
closed
22
7
8733116644
alarm
alarm
zu
closed
red
red
green
green
yellow
malfunction
*
*
* shunt connection
by customer
10k *W
line
–
12
Fire detector
Typ**
10k *W
out
out
in
in

11/20
RZN 4416-M Rev.:1.1
Parallel Connection of
2 x 2 Smoke Vent Buttons - RT 43-H / -N
**Fire detectors
Only D+H system approved detectors must be used (see page 7).
345678
RZN 4416-M
line
–
control
alarm
closed
malfunction
RM/RT
Smoke vent button
1st lane
Smoke vent button
lane2nd
RT 43-H RT 43-H
RT 43-N
RT 43-N
10kW
alarm
alarm
control
control
-
-
line
line
line
line
malfunction
malfunction
closed
closed
22
77
8833116644
alarm
alarm
zu
zu
red
red
green
green
yellow
yellow
line
line
-
-
control
control
alarm
alarm
closed
closed
2233116644
77
55
last smoke
vent button
each
first to
penultimate
smoke vent
button each
*
*
* shunt connection
by customer
10k *W
line
–
12
Fire detector
Typ**
10k *W
out
out
in
in

12/20 RZN 4416-M Rev.:1.1
Standard Connection with RT 42
* Terminal resistors for line monitoring:
They are pinched in control panel for transport. Take it off there and connect according to
plan. Terminal resistors must remain at binder RM 1,2, when no fire detector or external
control exists.
** Fire detectors
Only D+H system approved detectors must be used (see page 7).
***For detailed information concerning the connection, please refer to the instruction for
use of respective drive.
10k *W
line
line
–
–
closed
open signal (optional)
–N
open
monitoring
Mot.a
Mot.b
56712341122
optional
RM RT LT
345678
line
-
control
alarm
closed
external
excitiation vent button
LT 43
(-SD)
fire
detector
Typ**
operating contact
alarm resistor
10k *W
10kW
1kW
out
out
in
in
closed
–N
open signal
open
last
first or
penultimate
LT 43
L
L
P
P
smoke vent button
RT 42
RT 42
10kW
alarm
control
-
line
line
closed
273164
alarm
closed
red
green
line
-
control
alarm
closed
23164
7
5
RZN 4416-M
drives***
brown
blue
black
orange
2x47kW
black
2 resistors
47k or
terminal
module
W
brown
blue
thermal
detector
THE 4
RZN 4416-M
RM MOT
branch box
length of line and
cross sections,
see page 12
<>
last
first or
penultimate

13/20
RZN 4416-M Rev.:1.1
Parallel Connection of
Smoke Vent Buttons - RT 42
**Fire detectors
Only D+H system approved detectors must be used (see page 7).
Smoke vent button
1st lane
RT 42
Smoke vent button
2nd lane
RT 42
10kW
RT 42
RT 42 line
line
line
–
–
–
control
control
control
alarm
alarm
alarm
closed
closed
closed
7
7
72
2
23
3
3
1
1
1
6
6
6
4
45
4
OKOK
345678
RZN 4416-M
line
–
control
alarm
closed
RM / RT
7
231645
*
*
* shunt connection
by customer
10k *W
line
–
12
Fire detector
Typ**
10k *W
out
out
in
in

14/20 RZN 4416-M Rev.:1.1
Connection of magnetic clamps on RZN 4416-M
Magnetic clamps 24V
(max. 500mA
overall power)
*The resistor must not be used, when line connections with 2-detector dependency are
employed!
Connection of several fire detectors
Connection of one fire detector
N- N+ Z + M1 M2 D1 D2
-+
-+
interrupter
key
magnetic
clamp
terminal resistor
line
-
10K
single fire detector
180R
1
2
3
4
5
6.
7
*
line
-
10K
first fire detector second to penultimate
fire detector
ultimate
fire detector
180R
1
2
3
4
5
6.
7
*180R
1
2
3
4
5
6.
7
*180R
1
2
3
4
5
6.
7
*
terminal resistor

15/20
RZN 4416-M Rev.:1.1
M
M
Zentrale Abzweigdose
Abzweigdose
am Motor
weitere Abzweige
gleichartig schalten
Abzweigdose
am Motor
Abzweigdose
br.
br.
bl.
bl.
7
6
5
MMMMM M M M
3x2,5²
25m
M M M M M M M M
4x2,5² 3x2,5²
50m50m
MMMMM M M M
3x2,5²
4x2,5²
40m
75m
M M M MM M M M
4x2,5²
5x2,5²
75m 75m
200m
controlpanel branchbox
connectinthe
samewayfurther
derivations
branchbox
branchbox
atdrive
branchbox
atdrive
Connection Examples
Connection with line derivation:
supply wires Mot a / Mot b derive off in par-
allel, monitoring will be looped through all
cables up to group end.
Example 1: 1 lane
Simple installation, but unfavourable for
voltage drop: All drives on one line.
Example 2: 2 lanes
Control panel in centre, one side wired as
derivation, the other as terminal line.
Observe 4 wires for derivation!
Example 3: 2 lanes on one side
Derivation and terminal lines in same
direction; number of drives vary according
to line lengths.
Observe 4 wires for derivation!
Example 4: 3 lanes
3 line lanes have been provided due to
extremely long distances: 2 line lanes with
3 drives each on 75 m line as derivation,
and 1 line lane with 2 drives on 200 m line.
Observe 4 wires for derivation!

16/20 RZN 4416-M Rev.:1.1
yes
no
Factory-set?
(Dip switch)
yes
Delivery condition of DIP-switches
see page 17.
Informations for Starting
Carry out following sight and performance checks for switching-on the smoke and heat vent
control panel. no
yes
yes
yes
yes
yes
yes
no
no
no
no
no
no
All cable
connected?
Partial or incomplete connection of components can
cause malfunction.
Check following connections: mains 230V, drives,
smoke vent buttons, when necessary fire detectors
and vent buttons. See wiring and connection plans
page 9-15.
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
Performance check alarm/reset and ventilation
10kΩresistance in
smoke vent button?
10kΩresistance in
fire detector?
Stop module 2x47kΩ
in conduit box?
Connect mains
mains control
lightens?
Connect
accumulator lines control
lightens?
Smoke
vent flap opens and
closes?
Cramp stop module on last or only drive in conduit box
on wire 5 yellow, 6 black, 7 black. See connection plan
page 9-15.
Check line safety fuse in E distribution and fuse mains
in control panel.
Mains still not available or line switch
on "0" or one of fuses faulty.
Resistance must be cramped in electric last button on
binding posts 3/ 8 (RT 43-H) or binding posts 3/ 7
(RT 42). See connection plan page 9-15.
Resistance must be cramped in last or only fire detector
on binding post 2 and 4 (type FO/FT). Resistance
remains in control panel between binding post RM 1
and 2, when no fire detector available.
See connection plan page 9-15.
Possibly change poles in drive.

17/20
RZN 4416-M Rev.:1.1
12345678
ON
1234
ON
12345678
ON
S1, S3 S2, S4, S5 S6
Codification of group S2, S4, S5
Factory preset of the DIP-Switch
Switch 1 on ON = OPEN-running time limitation
If Dip switch 1 is switched on ON, the OPEN-running time limitation can
Using a potentiometer, running time in Open direction can be
Limited. If the vent button is actuated in Open direction, the drive
will run open as long as the running time is set.
Using a potentiometer, ventilation time can be set. Drives will
automatically close again, after the adjusted time has expired.
Switch 2 on ON = Ventilation time limitation
Switch 3 on ON = OPEN-retriggering
Only possible in conjunction with group-DIP-switches4=ON
(storage operation in CLOSED-direction)!
Only possible in conjunction with group-DIP-switch1=ON
(OPEN-running time limitation)!
be retriggered again.
Switch 4 on ON = Storage operation in CLOSED-direction
Switch 4 on OFF = Key operation in CLOSED-direction
Switch 5 on ON = Storage operation in OPEN-direction
Switch 5 on OFF = Key operation in OPEN-direction
Switch 6 on ON = Group CLOSED in case of alarm
Switch 7 on ON = Group fault on alarm
smoke vent
opens group fault
Switch 8 on ON = Alarm re-clocking
Press ventilating button 1x shortly > the drive will be closing up to its
final position
The drives will be closing only so long as the ventilating button is pressed.
Press ventilating button 1x shortly > the drive will run open up to its
final position.
The drives will run open only so long as the ventilating button is pressed.
The group will be closing in case of alarm!
The control panel will be switched on alarm, that means, the
in case of (e.g. in case of an interrupted control line).
The smoke vent is triggered for a duration of 30 minutes in intervals of
2 minutes according to VdS 2581. .See page 6 about this
min
15
245
30
sec
20
260
40

18/20 RZN 4416-M Rev.:1.1
Codification of Control Panel S6
Codification of Line S1, S3
Switch 1 on ON = Line 2 on group 3
“OFF“
Line 2 is also effective on group 3
In case of alarm of one line, the other line will be set on alarm as well
Factory-setting must be on
Actuate DIP-switch (ON / OFF).
LED’s will light up for 3 seconds in control panel
Switch 1 on OFF =
Switch 2 on ON = Central alarm
Switch 3 on ON = Power failure-CLOSED
ON
Switch4onON =
Switch 5 =
Switch 6 on ON = LED Test / Reset WDT error (Watch Dog Timer)
Switch 7 =
Switch 8 =
Group 3 is independent of line 2
If the power supply breaks down, the drive will close.
Only when group-DIP switch 4 (key operation in CLOSED-direction) =
idle
idle
idle
Bus control
Switch 1 on ON = Two-smoke detectors dependency
Attention!
Switch Smoke detector alarm can be reset only in control panel
Dip switch 2 must be switched on OFF, when remote reset is desired of smoke detectors by the
smoke vent button.
Switch
Switch
Alarm will be triggered only, if at least two smoke detectors of one line respond.
False alarm of one smoke detector will be prevented.
Two smoke detectors in one room must be always installed.
If only one smoke detector is connected to one line, switch is on OFF!
Smoke detector alarm can be reset by single pressing on button in smoke
vent button.
(Only in conjunction with FO 1362)
See also page 14 about this.
2onON =
3 on ON = Line fault = alarm
smoke vent opens
line fault
4=
The control panel will be switched on alarm, that means the at
a (e.g. at an interrupted detector line or short circuit).
idle
not

19/20
RZN 4416-M Rev.:1.1
Delivery Condition RZN 440x-M
Function
Two-smoke detectors dependency
Smoke detector alarm only to be reset in control panel
Line fault = Alarm
Idle
OPEN-running time limitation
Ventilating time limitation
OPEN-retriggering
Duty cycle in CLOSED-direction
Duty cycle in OPEN-direction
Group CLOSED in case of alarm
Group fault on alarm
Alarm re-clocking
Two-smoke detectors dependency
Smoke detector alarm only to be reset in control panel
Line fault = Alarm
Idle
OPEN-running time limitation
Ventilating time limitation
OPEN-retriggering
Duty cycle in CLOSED-direction
Duty cycle in OPEN-direction
Group CLOSED in case of alarm
Group fault on alarm
Alarm re-clocking
OPEN-running time limitation
Ventilating time limitation
OPEN-retriggering
Duty cycle in CLOSED-direction
Duty cycle in OPEN-direction
Group CLOSED in case of alarm
Group fault on alarm
Alarm re-clocking
Line 2 on group 3
Central alarm
Power failure-CLOSED
Bus Control
Idle
LED Test / Reset WDT error (watch dog timer)
Idle
Idle
ON OFF
Switch
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Line 1
Group 1
ON OFF
Conf. at
starting
Line 2
Group 2
S1
Group 3
Control panel
S2
S3
S4
S5
S6
Delivery
condition

20/20 RZN 4416-M Rev.:1.1 All sizes in millimetre • Rights to technical modifications reserved. • Reprintingandphototechnical
reproduction also in extracts has to be expressively authorized by D+H Mechatronic AG.
Preparation:
Notifyuser,that the system isout ofoperation
before starting with inspection.
Notify user about false alarms.
Interrupt or switch off monitored alarm
indication and remote controls.
Inspection:
Check all appliances and cable connections
for outer damage and dirt accumulation.
Fire detectors, smoke vent buttons, smoke
vents and so on must not be impaired in
their function by goods in storage or
structural changings.
Smoke vent button:
Open smoke vent button.
Press red button , red display diode
lightensinbutton and control panel.
Smoke vent must open.
Press masked button (1 sec.), red display
diode extinguishes in button and control
panel.
Smoke vent must close.
Automatic fire detectors:
Release smoke detector individual by D+H-
smoke detector tester, as an alternative by
cigarette smoke (response delay circa 20
sec.).
Red display diode must lighten.
Smoke vent must open.
For closing wait until there is no more smoke
indetector.
Reset line in control panel (switch off/ switch
on press button), red display diode
extinguishes in button and control panel.
Press masked button in smoke vent
button. Smoke vent must be closing.
The line can also be directly reset via smoke
ventbutton, if Dipswitch9 isswitchedon OFF.
For this, press masked button in smoke
vent button (for 1 second).
Red display diode extinguishes in button
and in control panel. Smoke vent must close.
At severe dirt accumulation visible from
outside or false alarms, send detector in for
maintenance and install an exchange
detector.
External control (optional):
Release external control.
Smoke vent must open.
Open contact in external system for closing,
for example by resetting of fire detector
system.
Press masked button in smoke vent
button (1 second). Red display diode
extinguishes in button and control panel.
Smoke vent must close.
Emergency supply:
Detach fuse MAINS on motherboard of
control panel.
Greenmainsindicationdiode oncontrol
panel must not lighten.
Repeat functioning testing.
Green control diode in smoke vent
buttons must not lighten. Ventilation is out of
function.
If Dip switch 4 and 5 on ON, the group will be
automatically closing.
Examination
Every six months and after repair by a specialist or staff, who has been introduced to the task.
Eliminatefailingsatonce.Keepcontrolbook.
Other manuals for RZN 4416-M
1
Table of contents
Other D+H Fan manuals
Popular Fan manuals by other brands

Click
Click CLF6-BLK user manual

Field Controls
Field Controls VentCool 2.4 installation manual

Fanaway
Fanaway LD-0003-10/WH/GS/E27 Installation instructions manual

Construction Solutions
Construction Solutions DBX1000 Installation and Product Manual

Broan
Broan qtr050F instructions

Vogue
Vogue 373016 user manual