DualLite UFO-3AW User manual

Emergency Lighting Fluorescent Battery Pack
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should
always be followed including the following.
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter
connector must be open. Do not join inverter connections until installation is complete and AC power is
supplied to the emergency ballast.
2. This product is for use with most 32 W through 40 W T8, T10, or T12 single pin or bipin uorescent lamps,
including energy saving, circline, U-shaped and rapid-start (4-pin) long compact uorescent lamps.
3. Make sure all connections are in accordance with the National Electrical Code and any local regulations.
4. To reduce the risk of electrical shock, disconnect both normal and emergency power supplies and inverter
connector of the emergency ballast before servicing.
5. This emergency ballast is for factory or eld installation in either the ballast channel or on top of the xture.
6. This product is suitable for damp locations where the ambient temperature is 0°C minimum, +55°C
maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
7. An unswitched AC power source is required (120 through 277 VAC, 60 Hz).
8. Do not install near gas or electric heater.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not eld replaceable.
Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualied service personnel.
CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identied as suitable for use
with this inverter/charger pack.
SAVE THESE INSTRUCTIONS
WARNING - This product contains chemicals known to the State of California to cause cancer,
birth defects, and/or other reproductive harm. Thoroughly wash hands after installing, cleaning, or
otherwise touching this product.
UFO-3AW
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS - Auto Select
! IMPORTANT SAFEGUARDS !
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE
FOLLOWED, INCLUDING THE FOLLOWING:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. To prevent high voltage from being present on red & yellow output leads prior to installation,
inverter connector must be open. Do not join inverter connector until installation is complete and
AC power is supplied to the emergency ballast.
2. This product is for use with 16 W through 40 W (2ft - 4ft) T8 and T12 single pin or bipin for one
or two lamp emergency mode operation, instant start and rapid start; 40 W through 215 W (5ft -
8ft) T8 and T12 single pin or bipin for one lamp emergency mode operation, instant start and
rapid start; and 16 W through 31 W U-Bend T8 bipin for one or two lamp emergency mode
operation, instant start and rapid start flourescent lamp fixure
3. Make sure all connections are in accordance with the National Electrical Code and any local
regulations.
4. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and
inverter connector of the emergency ballast before servicing.
5. This emergency ballast is for factory or field installation in either the ballast channel or on top of
the fixture.
6. This product is suitable for damp locations where the ambient temperature is 0°C minimum,
+50°C maximum. Product is also suitable for installation in sealed and gasketed fixtures. Product
is not suitable for heated air outlets and wet or hazardous locations.
7. An unswitched AC power source is required (120 through 277 VAC, 50/60 Hz).
8. Do not install near gas or electric heaters.
9. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field
replaceable. Contact the manufacturer for information on service.
10. The use of accessory equipment not recommended by the manufacturer may cause an unsafe
condition.
11. Do not use this product for other than intended use.
12. Servicing should be performed by qualified service personnel.
CAUTION: Verify that all replacement lamp types marked on the installed luminaire are also identified
as suitable for use with this inverter/charger pack.
SAVE THESE INSTRUCTIONS
UFO-6W
Ni - Cd
CONTAINS NICKEL-CADMIUM
RECHARGEABLE BATTERY.
MUST BE RECYCLED OR
DISPOSED OF PROPERLY.
©
Hubbell Lighting, Inc. • 701 Millennium Blvd • Greenville, SC 29607 • (864) 678-1000 • FAX (864) 678-1415 • www.dual-lite.com
93063952
WARNING – This product contains chemicals known to the State of California to cause cancer, birth defects and/or other
reproductive harm. Thoroughly wash hands after installing, handling, cleaning, or otherwise touching this product.
09/17/15
B
2 1
2 1
A
B
A
SGHMDBEC-091027001
11.OCT.2010
B
REV DATE RECORD DESN CHCK
SHT 1
1 SHTS
N/A N/A
130X002
SEE NOTE
UNDER ART
C
ARTWORK-LOGO UL
SGH 10/11/10
SGH 10/11/10
---
SGH 10/11/10
DRAWING NO.SIZE
A
SCALE
CATALOG NO.
ENGINEERING:
CHECKED BY:
DIMENSIONS IN INCHES
DIMENSIONS IN [ ] IN MM
CONFORMS TO ASME Y14.5M
DO NOT SCALE PRINT
DRAWN:
THIRD ANGLE PROJECTION
MATERIAL: FINISH: PART NO.
REV.
CRITICAL DIMENSIONS
This document contains confidential and proprietary information of Dual Lite.
Receipt or possession of this document does not convey any rights to
reproduce or disclose its contents, or to make, use , or sell anything it may
disclose. Reproduction, disclosure, or use of the document or its contents,
without the specific written authorization of Dual Lite, may violate the
intellectual property rights of Dual Lite.
UNSPECIFED TOLERANCES: INCHES
X.X=±0.1 X.XX=±0.03 X.XXX=±0.010
FRACTIONS=±1/32 ANGULAR TOLERANCE=±1°
NONE
JEBJEBEC-160616002
16.JUN.2016
C
NO LISTING
UL LOGO
ARTWORK
P/N 1300827
56B5 LISTING
UL LOGO
ARTWORK
P/N 1300828
EMERGENCY
LIGHTING
EQUIPMENT
56B5
57B9 LISTING
UL LOGO
ARTWORK
P/N 1300842
EXIT FIXTURE
57B9

INSTALLATION
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is
required. The emergency ballast must be fed from the same branch circuit as the AC ballast.
1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast
either in the ballast channel (see Illustrations 1 & 2) or on top of the fixture* (see Illustration 3).
2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure
all connections are in accordance with the National Electrical Code and any local regulations.
3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Drill a
1/2" hole and install the switch as shown (see Illustration 1 & 2). Refer to the wiring diagrams section and wire
the test switch so it removes AC power from the unswitched hot line to the emergency ballast.
4. Refer to Illustration 4 and install the charging indicator light so that it will be visible after the fixture is installed.
5. In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection
Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And
Emergency Power Supplies Before Servicing.”
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND YELLOW
OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO
NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER
IS SUPPLIED TO THE EMERGENCY BALLAST.
ILLUSTRATION 2
ILLUSTRATION 1 ILLUSTRATION 3
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If
a detached charging indicator light is used, connect by matching wire colors and install as shown
in Illustration 4.
*For installation on top of the fixture, wire bundle covers may be required by state or local codes. These covers are available from the
manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete infomation.
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND
YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR
MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS
COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST.
INSTALLATION
INSTALLATION
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is
required. The emergency ballast must be fed from the same branch circuit as the AC ballast.
1. Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast
either in the ballast channel (see Illustrations 1 & 2) or on top of the fixture* (see Illustration 3).
2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make sure
all connections are in accordance with the National Electrical Code and any local regulations.
3. Install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Drill a
1/2" hole and install the switch as shown (see Illustration 1 & 2). Refer to the wiring diagrams section and wire
the test switch so it removes AC power from the unswitched hot line to the emergency ballast.
4. Refer to Illustration 4 and install the charging indicator light so that it will be visible after the fixture is installed.
5. In a readily visible location, attach the label “CAUTION–This Unit Has More Than One Power Connection
Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And
Emergency Power Supplies Before Servicing.”
WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED AND YELLOW
OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO
NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER
IS SUPPLIED TO THE EMERGENCY BALLAST.
ILLUSTRATION 2
ILLUSTRATION 1 ILLUSTRATION 3
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. If
a detached charging indicator light is used, connect by matching wire colors and install as shown
in Illustration 4.
*For installation on top of the fixture, wire bundle covers may be required by state or local codes. These covers are available from the
manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete infomation.
ILLUSTRATION 1 ILLUSTRATION 2 ILLUSTRATION 3
NOTE: Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The
emergency ballast must be fed from the same branch circuit as the AC ballast.
1. 1. Disconnect AC power from the xture. Remove the ballast channel cover and install the emergency ballast
either in the ballast channel (see Illustrations 1 & 2) or on top of the xture* (see Illustration 3).
2. 2. Select the appropriate wiring diagram to connect the emergency ballast to the AC ballast and lamp. Make
sure all connections are in accordance with the National Electrical Code and any local regulations.

6. After installation is complete, supply AC power to the emergency ballast and join the inverter connector.
7. A short-term discharge test may be conducted after the emergency ballast has been charging for one hour.
Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
OPERATION
When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When
power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at
reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC
ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown
circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes.
MAINTENANCE
Although no routine maintenance is required to keep the emergency ballast functional, it should be checked
periodically to ensure that it is working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be illuminated.
2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. Either one or two
lamps should operate at reduced illumination.
3. Conduct a 90-minute discharge test once a year. Either one or two lamps should operate at reduced illumination
for at least 90 minutes.
REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL
ILLUSTRATION 4
NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label.
TROFFER STYLE FIXTURESTRIP STYLE FIXTURE
Charging
Indicator
Light
1/2" White
Bushing
Violet (+)
Brown (–)
Violet (+)
Brown (–)
1/2" White
Bushing
5/8" Black
Bushing
5/8" Black
Bushing
1/2" Punch
Fixture Fixture
Charging
Indicator
Light
WIRING DIAGRAMS
The following diagrams are typicalschematics
only. May be used with other ballasts. Consult
the factory for other wiring diagrams. Emergency
Ballast and AC Ballast must be fed from the
SAME BRANCH CIRCUIT.
IMPORTANT TEXT: REFER TO TABLE 1
REGARDING BROWN CONNECTOR
Table 1
LAMP
(DIAMETER)
BASE
TYPE
WATTAGE
(Length)
NO. of LAMPS
(EMERGENCY-
MODE)
BROWN
CONNECTOR
T8,T12
(1”, 1½”)
Single
or
Bipin
16 - 40 W
(2'-4')
1 CLOSED
2 OPEN
40 - 215 W
(5' -8') 1 OPEN
BROWN
BROWN
BROWN CONNECTOR CLOSED
BROWN
BROWN
BROWN CONNECTOR OPEN
JUMPER
WIRE
ILLUSTRATION 4

EMERGENCY BALLAST AND AC BALLAST MUST BE FEDFROM THE SAME BRANCH CIRCUIT.
TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.
WIRING DIAGRAMS for 1-LAMP emergency operation
4
WIRING DIAGRAMS for Emergency-Only fixtures
FIG B ONE (1) LAMP RAPID START BALLAST
FIG A ONE (1) LAMP INSTANT START BALLAST
FIG D TWO (2) LAMP RAPID START BALLAST
FIG E THREE (3) LAMP INSTANT START BALLAST FIG F THREE (3) LAMP RAPID START BALLAST
FIG G FOUR (4) LAMP INSTANT START BALLAST FIG H FOUR (4) LAMP RAPID START BALLAST
FIG C TWO (2) LAMP INSTANT START BALLAST
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
1 LAMP
RAPID START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP
RED
YELLOW
YEL/BLK
BLUE RED
RED
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
2 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
RED
YELLOW
YEL/BLK
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
3 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
( )
EMERGENCY
RED
YELLOW
YEL/BLK
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
BLUE
BLUE
RED
RED
3 LAMP
RAPID START
BALLAST
BLACK
WHITE
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
BLU/WHT
BLU/WHT
YELLOW
YELLOW
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
YELLOW
BLUE
4 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
RED
( )
EMERGENCY
RED
YELLOW
YEL/BLK
LAMP 4
RED
YELLOW
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
4 LAMP
RAPID START
BALLAST
RED
RED
BLACK
WHITE
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
LAMP 2
LAMP 1
LAMP 3
LAMP 4
BLU/WHT
BLU/WHT
YELLOW
BRN
BRN
BLUE
BLUE
YELLOW
( )
EMERGENCY
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
1 LAMP
INSTANT
START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP
RED
YELLOW
YEL/BLK
RED
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WALL SWITCH
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
( )
EMERGENCY
2 LAMP
RAPID START
BALLAST
BLUE
BLACK
WHITE
BLU/WHT
BLUE
LAMP 2
LAMP 1
RED
YELLOW
YEL/BLK
BLUE RED
RED
YELLOW
YELLOW
FIG I ONE (1) 32- 40 W LAMP WITHOUT AC BALLAST
E
M
E
R
G
E
N
C
Y
B
A
L
L
A
S
T
WHT/RED
RED
WHITE
VIOLET (+)
BROWN (-)
WHITE
WHT/BLK
COMMON
(CAP UNUSED LEAD) BLACK 120V
OR
ORANGE 277V
TEST
SWITCH
INVERTER
CONNECTOR
CHARGING
INDICATOR
BLK
HOT
BLK
(CAP)
(CAP)
LAMP
RED
YELLOW
YEL/BLK
BLU/WHT
BLUE
(CAP)
(CAP)
© Copyright Hubbell Lighting, Inc.• 701 Millennium Bvld • Greenville, SC 29607 • (864) 678-1000 •
FAX(864) 678-1415 • www.dual-lite.com 93081034
05/17
Other DualLite Batteries Pack manuals
Popular Batteries Pack manuals by other brands

Deka
Deka HRC800 Installation and operating instructions

Briggs & Stratton
Briggs & Stratton 1760266 owner's manual

Fxlion
Fxlion BP-BV300 user manual

Kobalt
Kobalt K20-LB20A user guide

AA Portable Power Corp
AA Portable Power Corp CH-L1486 user manual

Living Spaces
Living Spaces Freemotion LS2500 owner's manual

Stryten Energy
Stryten Energy M Series Installation and operating instructions

Nosram
Nosram VTEC X-treme Race-1S-3.7V user manual

SUNKET-ESS
SUNKET-ESS LFP5000 Operation manual

UPOWER Ecoline
UPOWER Ecoline NauticBattery NA-12Li300BL quick start guide

Inventus Power
Inventus Power PROTRXion S-12V100-TRX-HD quick start guide

V-TAC
V-TAC ESS Series instruction manual