Duemmegi Domino WEBS User manual

Domino
WEBS
WEBS: interface module between DFCP
controller and Ethernet network with
Web-Server function
WEBS module has been developed to be used in all appli-
cations of Domino system where it is required to control the
domotic system through an Intranet or Internet connection,
without difficult configuration procedures; for this ind of ap-
plications, in association with the specific program for the
development of graphical maps, WEBS module is very
user-friendly.
To use WEBS module, BDGraph upgraded to the latest
available version is required; this can be freely downloaded
from the website www.duemmegi.it. WEBS requires DFCP
controller with firmware upgraded to the latest available
version main microcontroller).
WEBS module can be used in two different operating
modes: in the first one it acts as a “bridge” between a local
Ethernet networ and Domino system, while in the second
operating mode it can be used as WEB-Server, with web
pages that can be created by the user.
WEBS module allows to manage any Domino bus vari-
ables, li e:
•input status
•status and command of real outputs
•status and command of virtual points
•registers
•system cloc
WEBS module has a 2-way terminal bloc for the connec-
tion to power-supply in the range 9 to 24V= (terminals +
and -). On the opposite side, the module features an Ether-
net connector and a 10-way connector allowing the con-
nection to DFCP controller by means of the provided flat
cable. Three LEDs on the front panel show the operating
status of the module: the green LED is on when the module
is supplied, while the yellow and the red LEDs report more
complex information (for more details see the “LEDs mean-
ing” paragraph).
A little hole on the front panel allows accessing to the Re-
set button; for more details see the related paragraph.
WEBS module is housed in a 3M DIN standard module.
The development of the maps to be loaded into WEBS
module is supported by the specific tool named BDGraph;
for details about the development of maps, see the related
manual “Graphical Maps”.
WARNING: the present technical sheet is applicable to
WEBS module with firmware upgraded to the latest
available release.
NOTE: the WEBS module can be used in Domino and
Contatto plants, with the same firmware, because it is able
to automatically recognize if the module is connected to
DFCP or MCPXT; for the Domino case, refer however to
the specific technical sheet.
Module Connection
The connections for the proper operation of WEBS module
are shown in the next schematic diagram.
+
Su ly _
/ ~
SUPPLY BUS
+-+-
DFCP
+_
WEBSWeb Server Module
Power su ly 24V= ±25% / 55mA
Eth DEVICE
ON SYS SD
DUEMMEGI
MILANO-ITALY
As shown before, WEBS module must be connected to a
dc power supply in the range 9 to 24V. After that it is nec-
essary to connect the module to the Ethernet networ and
to Domino DFCP controller; in this way WEBS module will
be full operating.
WARNING: for the connection to an Ethernet HUB, a
straight cable category 5 must be used, whereas for the di-
rect connection to a PC a cross cable is needed both
these cables are not provided).
O eration
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 1 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
WEBS module has been developed to be used in associa-
tion with DFCP Domino bus controller, which does not re-
quire any configuration procedure.
As said above, WEBS module can be used in two ways, as
bridge (interface between DFCP and Ethernet) or Web-
Server.
WEBS: bridge mode
By means of the bridge operating mode, it is possible to
ma e each operation allowed by the programming and di-
agnostics Tools (BDGraph, DCP IDE). It is possible to use
these tools through the local networ (LAN) or through In-
ternet (but in this case a VPN has to be enabled, or anyway
the router must be set in a proper way) after having entered
the IP address assigned to WEBS in the opening communi-
cation window used for the connection; in this way it will be
possible to interact with Domino system from any location
in the world (see “Configuration and setting up”).
The bridge modality is MONO-CLIENT, therefore WEBS al-
lows the access to only one user at a time (although at the
same time with Web-Server users).
WEBS: Web-Server mode
By means of this modality it is possible to upload into
WEBS a series of customized WEB pages that have been
created through the proper Tool BDGraph upgraded to the
latest available version. Through this modality, WEBS mod-
ule allows the interfacing to a common Web-browser (Fire-
Fox, Internet Explorer, etc.); to navigate across the WEB
pages, a password will be required (even if this is
optional). The pages loaded by the browser and stored in-
side the WEBS memory, must be created and customized
according to the plant and to the user's requirement. About
the development of these pages, see the “Graphical Maps”
manual.
Web-Server modality is MULTI-CLIENT; it is possible the
simultaneous access to a maximum of 4 users (plus one
user in bridge mode).
It is also possible to use 5 different login/passwords, each
one with its own credentials; it is possible to set username
and password for an Admin user and 4 different usernames
and passwords for the other users. It is possible to differen-
tiate, in this way, the maps for each user and therefore the
controls that each user can perform.
LEDs meaning
Three LEDs (green, red and yellow) on the front panel of
WEBS show the operating status of WEBS module. The
green LED shows the power on condition; the red LED fea-
tures the function of System LED (SYS) and it offers a visu-
al signaling and flashing with different duration depending
on the module operating status; the next table lists these
modes:
Red LED On [sec] Off [sec]
DFCP Connected 0.1 1.5
DFCP Not connected 0.9 0.1
Wrong MAC address Fisso ----------
SD-Card not present 0.5 0.5
Reset in progress 0.1 0.1
If a polling is running trough the bridge mode, the flashing
of red LED is fast and irregular. In the case of firmware up-
grading, the red LED flashing with “dimming” effect.
The yellow LED (SD) shows the access to the SD-card
memory and it flashes in irregular mode when a client is
connected in Web-Server mode.
Reset button
A little hole on the front panel allows the access to the Re-
set button; this button must be used only in the case of ef-
fective needing and it has the following functions:
Reset of the module: while the module is powered, push
and hold down the button; when the Red LED starts to
flash quic ly (after 2 seconds about) release the button.
Restoring of default parameters: while the module is
powered, push and hold down the button; after 2 seconds
about the Red LED starts to flash quic ly. The flashing con-
tinues for 3 seconds about, after that the flashing slows
down; after further 10 seconds, the Red LED return to flash
quic ly. At this time release the button and the default pa-
rameters (IP address, password, etc.) will be restored.
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 2 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
Configuration and setting u
After having properly connected the WEBS module, several
simple configuration procedures must be executed in order
to ma e the module well operating.
To access to the configuration panel of the WEBS module
it is possible to use any browser (FireFox, Internet Explor-
er, Google Chrome, etc.).
WARNING: to modify the settings and the configuration of
WEBS module, it is necessary to access as administrator.
tep 1: users and password configuration
In the address bar of the browser enter the following:
http://192.168.1.253/webpass.htm
A window as ing for user name and password will be
shown; the default ones for the administrator access are:
username: admin
assword: admin
It is a good practice, first of all, to change the administrator
and users login/password before to use the module.
User names and passwords, as the other parameters, can
be modified in any moments according to the requirements.
The configuration page for passwords configuration is the
following:
It is necessary to choose the wanted voice to modify and
then, for each one, save the new settings.
It is possible to enable or disable the Auto login of each
user in the event of a LAN connection: in practice for which
the user has enabled the Auto Login, when connected to
the LAN, will no longer provide the login credentials . How-
ever, using a remote connection, the login credentials are
always required. To enable or disable the Auto Login is
necessary, following the selection of user from the previous
window, select Yes to enable Auto Login, or No to disable
Auto Login. If each user have selected Yes for this option,
the WEBS module proceed with the following hierarchy:
user 1, user 2, user 3, user 4, Administrator. Ta ing the ex-
ample of the admin user, the configuration window of the
Auto Login option will be as follows:
For each saving the following page will be shown:
To proceed with users configuration, select Passwords,
otherwise select Reset WEBS to ma e operating the new
settings. Otherwise select IP Configuration to proceed with
the web parameters configuration described in the follow-
ing.
tep 2: IP configuration and web parameters
After the configuration of the passwords it is possible to ac-
cess to the configuration page. In the address bar of the
browser enter the following:
http://192.168.1.253/webconfig.htm
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 3 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
The configuration page loo s li e the following:
It is possible, in this configuration page, to set the wanted
parameters for IP address, Gateway, Subnet Mas , and the
Bridge Port. The shown values in the previous picture are
the default ones. The configuration dialog allows to enable
browser's cache, this option speeds up the response time
of the module itself.
Change these parameters as required and then press the
Save button; in this way will appear the following page:
Select Reset WEBS to ma e operating the new settings;
will appear the next message:
A new login request will appear after 5 seconds.
tep 3: uploading of html pages
For the uploading of html pages (the user Web site), as
mentioned in the Graphical Maps manual, it is necessary to
enter in the address bar of the browser the following (as-
suming to have assigned the IP address 192.168.1.253 to
WEBS module):
http://192.168.1.253/webupload.htm
The upload page loo s li e the following:
To upload the user's Web pages, push the button “Browse”
and select the .BIN file previously created on your comput-
er (see Graphical Maps manual); at this time push the “Up-
load” button.
If an error occurs during the upload, the following message
will be shown:
Information Pages
Entering the following address (the WEBS IP address
192.168.1.253 is supposed):
http://192.168.1.253/webinfo.htm
it is possible to show any parameters of WEBS module, as
shown in the following picture:
WARNING: the access to information page of WEBS mod-
ule is granted only to Administrator.
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 4 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
This page shows all settings previously assigned, and the
Firmware version of WEBS; from this page it is not possible
to modify any parameters.
By clic ing on IP Configuration it is possible to go bac to
the configuration page of WEBS module
(.../webconfig.htm).
Connected Users Info
It is possible to monitor the connected users in Web-Server
and Bridge modality: in the address bar of the browser en-
ter the following:
http://192.168.1.253/webconn.htm
As shown in the previous screen-shot, the first 4 lines re-
port the IP address of the connected users in Web-Server
modality, and the fifth-line reports the connected user in
Bridge modality.
WARNING: the access to the connected users page is
granted only to the Administrator.
Diagnostics
In the address bar of the browser enter the following:
http://192.168.1.253/webdiag.htm
in this way it is possible to show the SD-CARD status and
the connected unit. The related screen-shot is the follow-
ing:
WARNING: the access to diagnostic page is granted only
to the Administrator.
Logout
To close the connection with WEBS module, however op-
tional operation, it is necessary to execute the logout from
the module entering in the browser bar the following ad-
dress:
http://192.168.1.253/weblogout.htm
A message confirming the logout will be then shown.
Remote Reset
If unexpected events occur, causing the bloc ing of WEBS
module, it is possible to use a special command to execute
the RESET of the module from a remote location (through
the networ ); this RESET is similar to the hardware reset of
module. In the browser bar enter the following address:
http://192.168.1.253/webreset.htm
WARNING: the reset of WEBS module is granted only to
the Administrator. Each time that a change has been made
to the configuration parameters, it is necessary, to be oper-
ative, to RESET the module.
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 5 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
Firmware U dating
To execute the Firmware Update of WEBS module, the
program BootWEBS u graded to the latest available
version. It also requires that the PC is connected to the
RS232 serial port of DFCP (or, in alternative, RS485 by a
s ecific converter). DFCP must be connected to the
WEBS module to be updated through the specific flat ca-
ble. DFCP must have main firmware upgraded.
Start the BootWEBS program, the following will be shown:
From the menu select “Communication”; the window
shown in the following picture will be opened.
Press the button “Automatic Detection” to enable the
communication with DFCP, then press the button “Close”.
An Ethernet connection can be used by the specify of the
IP address of connected converter to the serial port of
DFCP; this converter can NOT be the same WEBS in
bridge modality.
From the program menu select “File” and then “O en”; it is
possible, in this way, to load the .HEX file to be download-
ed into WEBS module. Select “Communication” and the
“Program”; in this way the following window will be shown.
The “ID & Ver” button allows to visualize the current ver-
sion of the firmware uploaded in the WEBS module.
Clic on the button “Activate Boot”; the red LED on WEBS
module will start to flash with “dimming” effect, shown that
the module is ready to receive the new firmware. Then
press the button “Program” and wait for the end of the op-
eration. At the end of upgrading, to ma e operating the
module, clic on button “Reset PIC”, then select “Close” to
quit the program.
Technical characteristics
Power Supply 9 ÷ 24V SELV
MAX current consumption 105mA @ 9V
55mA @ 24V
DFCP Interface Proprietary SPI interface
Ethernet interface 10/100BaseT Ethernet
Housing DIN standard 3M per guida
DIN
Operating temperature -5 ÷ +50 °C
Storage temperature -20 ÷ +70 °C
Protection degree IP20
Outline dimensions
90mm
58mm
53mm
+_
WEBSWeb Server Module
Power su ly 24V= ±25% / 55mA
Eth DEVICE
ON SYS SD
DUEMMEGI
MILANO-ITALY
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 6 of 7
HOME AND BUILDING AUTOMATION

Domino
WEBS
Correct dis osal of this roduct
(Waste Electrical & Electronic Equipment)
(Applicable in the European Union and other
European countries with separate collection sys-
tems). This mar ing on the product, accessories or
literature indicates that the product should not be
disposed of with other household waste at the end
of their wor ing life. To prevent possible harm to
the environment or human health from uncontrolled waste dispos-
al, please separate these items from other types of waste and re-
cycle them responsibly to promote the sustainable reuse of materi-
al resources. Household users should contact either the retailer
where they purchased this product, or their local government of-
fice, for details of where and how they can ta e these items for en-
vironmentally safe recycling. This product and its electronic ac-
cessories should not be mixed with other commercial wastes for
disposal.
Installation and use restrictions
tandards and regulations
The design and the setting up of electrical systems must be per-
formed according to the relevant standards, guidelines, specifica-
tions and regulations of the relevant country. The installation, con-
figuration and programming of the devices must be carried out by
trained personnel.
The installation and the wiring of the bus line and the related de-
vices must be performed according to the recommendations of the
manufacturers (reported on the specific data sheet of the product)
and according to the applicable standards.
All the relevant safety regulations, e.g. accident prevention regula-
tions, law on technical wor equipment, must also be observed.
afety instructions
Protect the unit against moisture, dirt and any ind of damage dur-
ing transport, storage and operation. Do not operate the unit out-
side the specified technical data.
Never open the housing. If not otherwise specified, install in closed
housing (e.g. distribution cabinet). Earth the unit at the terminals
provided, if existing, for this purpose. Do not obstruct cooling of the
units. Keep out of the reach of children.
etting up
The physical address assignment and the setting of parameters (if
any) must be performed by the specific softwares provided togeth-
er the device or by the specific programmer. For the first installa-
tion of the device proceed according to the following guidelines:
•Chec that any voltage supplying the plant has been removed
•Assign the address to module (if any)
•Install and wire the device according to the schematic dia-
grams on the specific data sheet of the product
•Only then switch on the 230Vac supplying the bus power sup-
ply and the other related circuits
A lied standards
This device complies with the essential requirements of the follow-
ing directives:
2004/108/CE (EMC)
2006/95/CE (Low Voltage)
2002/95/CE (RoHS)
Note
Technical characteristics and this data sheet asre subject to
change without notice.
DUEMMEGI s.r.l. - Via Longhena, 4 - 20139 MILANO
Tel. 02/57300377 - Fax 02/55213686 – www.duemmegi.it
Rel.: 2.2 October 2012 Page 7 of 7
HOME AND BUILDING AUTOMATION
Table of contents
Other Duemmegi Control Unit manuals
Popular Control Unit manuals by other brands

Texas Instruments
Texas Instruments TPA6047A4 user guide

Gardena
Gardena 1243 operating instructions

Sony
Sony HDCU2500 Maintenance manual

GEZE
GEZE SecuLogic TZ320 Installation and Commissioning Instructions with Terminal Diagram Brief instructions

Toto
Toto Connelly TS221D Installation and owner's manual

American Valve
American Valve 3700 Ball Valve Installation, Maintenance & Operating Guide