
Series 629HLP Differential Pressure Transmitters
Specications - Installation and Operating Instructions
Bulletin P-629HLP
The Series 629HLP Differential Pressure Transmitters are suitable for measuring
over-pressure, under-pressure, and differential pressure in compatible gases and
liquids with 1% accuracy. The 629HLP is suitable for all measuring tasks in commercial,
industrial or sanitary applications. Its single diaphragm design, allows it to measure
small increment pressure changes, and converts them to a linear analog output signal
from 4-20 mA or 0-10VDC.
Installation
Location/Mounting
The transmitter can be mounted in various locations as long it is not subject to
excessive vibration, shock, or extreme temperature (see Specications). The tubing
feeding the pressure port may be of any length, but longer lengths will increase the
response time slightly. Avoid sharp bends, and depending on the vibration and shock
it is recommended to install attenuating components.
To facilitate installation, mounting bracket A-629HLP-BKT, is available as accessory.
Position/Orientation
The transmitter is not sensitive to installation position. However, factory calibration
is performed with the unit in a vertical position and horizontal pressure connections.
Pressure Connections
Pressure connections are 1/4˝ female NPT or 1/4˝ female BSPT. Avoid excess sealant
and ensure the pressure passages are not blocked.
The piping should allow removal and reinstallation of the transmitter without shutdown
of the pressure system. Especially in applications where the differential pressures are
measured at high static line pressures that are above the overpressure limit of the
transmitter. It is recommended to install the 629HLP transmitter with a 3 way manifold
and a bypass valve (see Figure 1).
The manifold with the bypass valve will help to balance the pressure between the low
and high side of the transmitter.
Dwyer offers a 3-way Block manifold option for this purpose.
Close the drain valve and open the bypass valve. Then both shutoff valves are opened
to apply line pressure equally to both sides of the transducer. Finally, close the bypass
valve. To remove the transducer, open the bypass valve, close the shutoff valves and
open the drain valve.
Figure 1
SPECIFICATIONS
Service: Compatible gases or liquids.
Wetted Material: 304 SS.
Housing Material: ABS.
Enclosure Rating: IP65.
Accuracy: ±1% from -5 to 60°C (23 to 140°F).
Stability: ±1% FS/year.
Temperature Limits: Ambient: -10 to 60°C (14 to 122°F); Process: -10 to 80°C (14
to 176°F).
Relative Humidity: 10% to 90% non-condensing.
Installation Position: Not position sensitive.
Pressure Limits: See Pressure Range Limits chart.
Burst Pressure: See Pressure Range Limits chart.
Static Pressure Limits: See Pressure Range Limits chart.
Output Signal: 4-20 mA, 0-10 VDC.
Response Time: 50 ms.
Rated Supply Voltage: 0-10 VDC Output: 12-36 VDC or 12-32 VAC (@ Max load
of 2k Ω) 4-20 mA output: 8-36 VDC.
Max Loop resistance: (Supply Voltage – 8 V) / 0.02 for 4-20 mA output.
Power Consumption: Vout = 13 mA max, Iout = 24 mA max.
Electrical Connections: Form A DIN 43650.
Process Connections: 1/4˝ female NPT, 1/4˝ female BSPT.
Weight: 1 lb 4 oz (567 g).
Approvals: CE, RCM.
DIN CABLE
INLET
Ø.418 I.D.
3-1/4
[82.40]
2-3/16
[55.40]
2-7/16 [62.00]
1/4 NPT OR
1/4 BSPT
1-3/16
[30.00]
1-3/16
[30.00]
2-1/8
[53.81]
1-21/32
[42.00]
SHUTOFF VALVES DRAIN VALVE
PRESSURE MEASUREMENT SOURCE
SHUTOFF VALVES
PRESSURE RANGE LIMITS
Pressure
Range
Maximum Static
Pressure
*Maximum Differential
Over Pressure
**Burst Differential
Pressure
0 to 1 bar
0 to 2.5 bar
0 to 4 bar
0 to 6 bar
0 to 15 psi
0 to 30 psi
0 to 60 psi
0 to 90 psi
25 bar
25 bar
25 bar
25 bar
360 psi
360 psi
360 psi
360 psi
5 bar
5 bar
12 bar
12 bar
70 psi
70 psi
174 psi
174 psi
8 bar
8 bar
18 bar
18 bar
115 psi
115 psi
260 psi
260 psi
Note: *The differential pressure limit, between high and low ports, that the
transmitter can withstand without affecting transmitter performance
**Differential pressures between high and low ports that exceed overpressure limits
will result in permanent diaphragm deformation, and any pressure higher than the
burst pressure limits will rupture the diaphragm.
MODEL CHART
Example 629HLP -01 -P2 -S1 -FC 629HLP-01-P2-S1-FC
Series 629HLP Differential pressure transmitter
Range 01
02
04
06
15
30
60
90
0 to 1 bar
0 to 2.5 bar
0 to 4 bar
0 to 6 bar
0 to 15 psi
0 to 30 psi
0 to 60 psi
0 to 90 psi
Process
Connections
P2
P4
1/4˝ female NPT
1/4˝ female BSPT
Output Signal S1
S5
4-20 mA
0-10 VDC
Options FC
NIST
Factory calibration
NIST certicate
Note: PSI ranges available upon request. Contact factory for details.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com