Note that while serial conguration is in progress, the device may not respond to
requests.
The Auto Baud serial conguration process will complete once a WhoIs or
ReadProperty command is successfully received and processed.
The Auto Baud serial conguration procedure is started after a power-cycle (if enabled).
Device Information
The default device object identier is 607xxx, where xxx is replaced by the MS/
TP device address set by the “Device Address” object’s present value. The object
identier value will change as the device address changes. However, if a specic
object identier is written via BACnet MS/TP Communication Protocol, then that value
is stored and changes to the device address address will no longer affect the object
identier. See Appendix VI for the device object property tables.
Accessing the Measurements
The analog input object AI1 through AI4 are for viewing Air Velocity or Temperature in
the desired engineering units. The object property tables for these analog input objects
can be found in Appendix VI.
Device Address
This object provides the means to congure the BACnet MS/TP device address. The
valid range of the present value property is 000 – 127. A device reset is required for a
new value to take affect. Default value: 127
Serial Baud Rate
This object allows the serial communication speed to be congured from the set of
supported rates. If “Auto Baud” (7) is set (default), then the auto serial conguration is
performed each time the device resets/powers on. If any other value is set, auto serial
conguration is disabled and only that Serial Baud Rate is used.
Reset Factory Defaults
Resets all settings to factory default values. Writing the present value to ACTIVE(1)
will reset the device address, device instance, device name, max master, etc. A device
reset is required to complete the factory reset procedure.
Reset Factory Defaults - Via Wiring Method
A physical reset of factory defaults can also be performed using the following sequence:
1. Connect and power the unit.
2. Disconnect Cong.(WH) wire from power supply GND(BK) for 2 seconds.
3. Reonnect Cong.(WH) wire to power supply GND(BK) for 10 seconds.
4. Cycle power to the unit, waiting at least 5 seconds to reapply power to the unit. The
device communication settings should now be reset to factory default values.
BACnet MS/TP Communication Protocol Services
Device Communication Control Service (DM-DCC-B)
This device supports the Device Communication Control Service BIBB. The optional
time duration in minutes is also supported. This device is congured with a password
that must be provided to successfully execute this command. The password is “Dwyer”.
Reinitialize Device Service (DM-RD-B)
This device supports the Reinitialize Device Service BIBB. The supported device
states are COLDSTART and WARMSTART. All other states return error. This device
is congured with a password that must be provided to successfully execute this
command. The password is “Dwyer”.
MAINTENANCE/REPAIR
Upon nal installation of the Series AVPT, no routine maintenance is required; though
sensor should be kept clean and free of dirt or debris.
WARRANTY/RETURN
Refer to “Terms and Conditions of Sale” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.
Table 3 : BACnet MS/TP communication protocol object overview
Table 4: Serial Baud Rate
Value Serial Baud Rate
1
2
3
4
5
6
7
9600
19200
38400
57600
76800
115200
Auto Baud
Object Type
Dynamically
Creatable
Dynamically
Deletable
Object
Identier Object Name
Device No No 607xxx AVPT Velocity
Analog Input No No AI1
AI2
AI3
AI4
Velocity FPM
Velocity MPS
Temperature F
Temperature C
Positive
Integer Value
No No PIV1 Device Address
Multi-State
Value
No No MSV1 Serial Baud Rate
Binary Value No No BV1 Restore Factory
Defauls
Changes to Max Master require a power cycle/reset to take effect.
NOTICE
This symbol indicates waste electrical products should not be disposed
of with household waste. Please recycle where facilities exist. Check with
your Local Authority or retailer for recycling advice.
Property Default Value Property Data Type Access
Object Identier 607xxx BACnetObjectOdentier Read/Write
Object Name “AVPT Velocity” CharacterString(32) Read/Write
Object Type DEVICE(8) BACnetObjectType Read
System Status Operational(0) BACnetDeviceStatus Read
Vendor Name “Dwyer Instruments,
Inc.”
CharacterString Read
Vendor Identier 607 Unsigned Read
Model Name “AVPT” CharacterString Read
Firmware Revision “x.x” CharacterString Read
Application
Software Version
“x.x.x” CharacterString Read
Location CharacterString(32) Read/Write
Description “Thermal
Anemometer”
CharacterString(32) Read/Write
Protocol Version 1 Unsigned Read
Protocol Revision 14 Unsigned Read
Protocol Services
Supported
See PICS BACnetServices
Supported
Read
Protocol Object
Types Supported
See Table 3 BACnetObject
TypesSupported
Read
Object List See Table 3 BACnetArray Read
Maximum APDU
Length Accepted
480 Unsigned Read
Segmentation
Supported
NO_
SEGMENTATION(3)
BACnetSegmentation Read
APDU Timeout 0Unsigned Read
Number of ADPU
Retries
0Unsigned Read
Max Master 127 Unsigned Read/Write
Max Info Frames 1 Unsigned Read
Device Address
Binding
Empty BACnetAddressBinding Read
Database Revision 0Unsigned Read
Property List BACnetARRAY[n] of
BACnetPropertyIdentier
Read
Serial Number “xxxxxxxx” CharacterString Read
Sensor Firmware
Version (1002)
“x.x.x” CharacterString Read
Sensor Hardware
Version (1004)
“x.x” CharacterString Read
OBJECT TABLES
Table 5 : Device object