Dynisco 1400 User manual

Instructions for
Model 1400/1401 Digital Panel Indicators
P/N 974072
04/02 Rev. B
ECO # 26719

2
CONTENTS
Quick Start Instructions ................................................................................................................... 3
1. General Information ................................................................................................................. 5
1.1 Introduction ....................................................................................................................... 5
1.2 Product Specifications ........................................................................................................ 6
1.3 Options .............................................................................................................................. 9
1.4 Ordering Guide................................................................................................................ 11
2. Installation .............................................................................................................................. 11
2.1 Installation ....................................................................................................................... 11
2.2 Wiring Guidelines ............................................................................................................ 12
3. Instrument Configuration ........................................................................................................ 18
3.1 Front Panel Description .................................................................................................... 18
3.2 Instrument Configuration .................................................................................................. 19
4. Operating Instructions ............................................................................................................ 26
4.1 Preliminary ...................................................................................................................... 26
4.2 Operating Mode ............................................................................................................... 27
5. Loading Default Parameters .................................................................................................... 29
5.1 Preliminary ...................................................................................................................... 29
5.2 Loading Default Configuration Parameters........................................................................ 29
5.3 Loading Default Operating Parameters ............................................................................. 30
6 Error Messages ........................................................................................................................ 30
7 Repair ..................................................................................................................................... 31
8 Warranty ................................................................................................................................ 31

1400/1401 Digital Panel Indicators 3
MODEL 1400-4-3 QUICK START INSTRUCTIONS
1. MOUNTING
• Prepare panel cutout to dimensions shown below.
• Remove instrument from case by turning captive safety screw (2) counter clockwise.
• Grasp the bezel and slide the instrument out of its case.
• Slide the rubber gasket (1) over the case.
• Slide the instrument case (3) into the panel cutout.
• Slide the panel-mounting bracket (4) on to instrument case until it contacts back of panel.
• Tighten two Phillps screws on panel mounting bracket until case is securely mounted in panel
cutout.
• Slide the instrument back into the case and tighten safety screw.
2. WIRING
• Connect an appropriate length of either thermocouple extension wire (e.g. Type J), 3 wire RTD
leads, or in the instance of linear input option, signal wires to input terminals as shown below.
• Connect alarm(s) if applicable. Note that alarm defaults are High, Reverse Acting.
• Connect power to the appropriate terminals as shown below.

4
3. INSTRUMENT CONFIGURATION
• Remove instrument from case by loosening safety screw, grab bezel and slide out of case.
• Locate jumper V2 in Figure 20, page 21 and place in the open position.
• Slide instrument back in case and apply power. Display will now show COnF
• Press the F button until P1 is displayed.
• Refer to 3.2.3 Parameter List on page 22. Using the UP arrow, select appropriate P1 code for
input type and standard range.
• Press F button until P6 is displayed.
• Using the UP arrow, select the appropriate Alarm 1 type (e.g. High alarm, etc.).
• Press the F button until P7 is displayed.
• Using the UP arrow, select the appropriate Alarm 1 action (e.g. reverse or direct acting)
• Press the F button until P8 is displayed.
• Using the UP arrow, select if alarm is inhibited at startup. Set to OFF or ON.
• If Alarm 2 is to be utilized, repeat the same process as above for parameters P12 through P17.
• Press the F button until ConF is displayed.
• Slide instrument out of case, return jumper V2 to the closed position.
• Slide instrument back into case, secure with safety screw.
• Apply power to instrument, unit will display process temperature.
• Press the F button to set Alarm 1 and 2 threshold and hysteresis values.
• Instrument is now ready for use.
PLEASE NOTE:
The preceding Quick Start instructions are the basic settings required to install, wire, and get the
indicator operating. Please refer to the complete installation and operation manual for additional
functions.

1400/1401 Digital Panel Indicators 5
1. GENERAL INFORMATION
DIMENSIONS AND PANEL CUT-OUT
Fig. 1 Dimensions of the Panel Indicator
Fig. 2 Dimensions of the Panel Cutout
HORIZONTAL MOUNTING: Minimum distance between cutouts: 20 mm
PACKING OF MORE INSTRUMENTS IN A SINGLE CUTOUT (max. 10 instruments): The vertical
dimension of the cutout is the addition of the front dimensions minus 3 mm. Vertical dimension of
the cutout = (n x 48) - 3 mm where n is the number of instruments to be packed.
BEFORE PROCEEDING WITH INSTALLATION OF THE INSTRU–MENT READ CAREFULLY
SECTION 2 AND PARTICULARLY SECTION 2.2, E CONCERNING THE EXTERNAL LOADS.
1.1 INTRODUCTION
The 1400 Series is a family of general purpose digital panel indicators developed with the latest
technology available today and aimed to reduce costs and improve simplicity during installation and
use. As part of the Dynisco background, this family also maintains a high standard in quality,

6
reliability and man/machine interface simplicity.
Features like three independent alarms, alarm masking during start up, manual or automatic alarm
reset, programmable alarm hysteresis, max. measured value data hold, min. measured value data
hold, analog retransmission of the measured value and linear input scaling with programmable
digital filter on the measured value, offer the wide range of possible applications.
The 1400 comes with a complete availability of ranges from thermocouple, RTD, mV, V and mA
input and can also be supplied with three independent alarms.
1.2 PRODUCT SPECIFICATIONS
1.2.1 GENERAL SPECIFICATIONS
Case: PC/ABS black color; self-extinguishing degree: V-0 according UL94
Front Protection: Designed and tested for IP65 (*) and NEMA 4X (*) for indoor
locations (when panel gasket is installed)
(*) Tests were performed in accordance with IEC529, CEI 70-1 and
NEMA 250-1991 STD.
Installation: Panel mounting with mounting frame
Instrument removable from case by safety screw
Rear Terminal Block: With screw terminals and identification labels, connection
diagrams and safety rear cover
Dimensions: DIN 43700
1.89” x 3.78”, depth 3.5” (48 x 96 mm, depth 89 mm)
Cut-out: 1.77” x 3.62” + 0.32”-0.0” (45 x 92 mm +0.8 mm -0.0 mm)
Weight: 2 lbs. (600 g max.)
Display: High efficiency LED, 4 digits, 7 segments with decimal point, 12.7
mm height, from -1999 to +4000
Front Indicators: AL1 - AL2 - AL3 - PK - °C - °F
Power Supply: From 100 V to 240 V A.C. 50/60 Hz or 24 V AC/DC
Power Supply Variations: From -15% to +10% of the nominal value
Power Consumption: 6 VA max.

1400/1401 Digital Panel Indicators 7
Insulation Resistance: > 100 M⍀according to IEC 348
Isolation Voltage: 1500 V r.m.s. according to IEC 348
Conversion: Dual slope integration
Resolution: 30000 counts
Sampling Time: 500 ms typical
Accuracy: ±0.2% fsv ±1 digit @ 25°C ambient temperature
Common Mode Rejection Ratio: 120 dB @ 50/60 Hz
Normal Mode Rejection Ratio: 60 dB @ 50/60 Hz
Noise Rejection: High frequency electromagnetic noise: according to IEC 801-4
level 3
Electric discharge: 8 kV
Temperature Drift: TC inputs: 울200 ppm/°C on fxv (CJ excluded)
RTD input: 울400 ppm/°C on fxv
Linear inputs: 울300 ppm/°C on fsv
Ambient Temperature: From 0 to 50°C
Storage Temperature: From -30 to +70°C
Humidity: From 20% to 85% RH, non-condensing
Protection: WATCH DOG circuit for automatic restart
DIP SWITCHES for protection against tampering with
configuration and calibration parameters
Approvals: UL, CSA (1400 only), CE
1.2.2 INPUTS
Three types of inputs are available:
A) THERMOCOUPLE:J, L, K, R, S, T, N
Type of TC and °C/°F programmable
Line Resistance: 100 V max, with maximum error 0.1% of span

8
Cold Junction: Automatic compensation from 0 to 50°C
Burn Out: Detection of an open input circuit (wires or sensor) with
underrange or overrange selectable indication
Input Impedance: >1 M ⍀
Ranges: See table
RANGE TABLE
TC Type Ranges Note
J -150/+1850°F -100/+1000°C IEC 584-1
K -150/+2500°F -100/+1370°C IEC 584-1
L -150/+1650°F -100/+900°C DIN 43710-1977
R 0/+3200°F 0/+1760°C IEC 584-1
S 0/+3200°F 0/+1760°C IEC 584-1
T -150/+750°F -100/+400°C IEC 584-1
N 0/+2550°F 0/+1400°C IEC 584-1
B) LINEAR INPUT
Input Type: See table
STANDARD RANGE TABLE
Input Type Input Impedance Accuracy
0 - 20 mA 5 ⍀
4 - 20 mA 5 ⍀
0 - 60 mV M 1 M⍀
12 - 60 mV M 1 M⍀0.1% W 1 digit
0 - 5 V M 200 k ⍀@ 25°C
1 - 5 V M 200 k ⍀
0 - 10 V M 400 k ⍀
2 - 20 V M 400 k ⍀
Readout: Keyboard programmable between -1999 and +4000

1400/1401 Digital Panel Indicators 9
Decimal Point: Programmable in any position
C) RTD (RESISTANCE TEMPERATURE DETECTOR)
Input: For RTD Pt100 ⍀, 3 wire connection with °C/°F selectable.
Input Circuit: Current injection (100 µA)
Line Resistance: Automatic compensation up to 3 ⍀/wire with no measurable error
Calibration: According to DIN 43760
Standard Ranges: See table
STANDARD RANGE TABLE
Input Type Ranges
RTD Pt 100 ⍀-320/+1100°F -200/+600°C
199.9/+600.0
Burn Out: Up scale or down scale programmable for open circuit of one or
more wires
1.2.3 ADDITIONAL FUNCTIONS
Peak Detection: Indication of the max. and min. value measured by the instrument
Digital Filter: Applied to the measured value with a time constant of 1, 2, 3, 4 or
5 s.
Offset On The Measured Value: It is possible to set an offset (engineering units) to the measured
value
Safety Lock: For protection of the alarms threshold values
1.3 OPTIONS
1.3.1 ALARMS
Number of Alarms: Up to 3 independent alarms
Threshold: From 0 to 100% of the readout span
Hysteresis: Programmable from 0.1 to 10.0% of the readout span

10
Type of Alarm: High or low alarms programmable
NOTE: The alarm becomes active at the alarm threshold value and will be reset at the alarm
threshold value plus or minus the hysteresis value, according to the alarm type.
Reset: Automatic or manual, programmable
Output of Alarm 1 and 2: Two relays, SPDT
Contact Rating: 3 A-30VDC on resistive load or 3 A-250V AC on resistive load
Relay Status: Relay energized in non-alarm condition (fail safe)
Alarm Indication: AL1, AL2 and AL3 indicators lit when alarm is in ON status
1.3.2 ANALOG RETRANSMISSION (1401 ONLY)
Analog Retransmission (option)
Type: 0-20mA, 4-20mA, 0-10V or 2-10V (programmable)
The output is galvanically isolated
Max. Load: 500 ⍀max for mA output
5K ⍀min for V output
display resolution (in E.U.)
Output Resolution = _________________________ • 20 mA
retransmission span in (E.U.)
NOTE: The resolution cannot be better than 0.05% of output span (10 µA for 20 mA output or 5
mV for 10 V output).
Accuracy: ±0.1% of f.s.v.
NOTE: The given accuracy is referred only to the retransmission circuit. It does not take into
account all the other accuracy (input accuracy, linearization, etc.).
NOTE: 1) It is possible to change the standard output 0-20mA to 0-10V, by means of “CUT/
SHORT” on retransmission PCB (see Section 3). The minimum load for Volt output is
equal to 5kohm. The device is supplied with mA output calibration. For Volt output, it is
necessary to re-calibrate the instrument.
2) The analog re-transmission is mutually exclusive with the relay AL3.

1400/1401 Digital Panel Indicators 11
1.4 ORDERING GUIDE
Model Code Options Description Code Power Voltage
1400 0 Thermocouple and RTD input 3 100 - 240 VAC
(switching)
4 Thermocouple and RTD input 1 24 V AC/DC
with dual alarm and linear input
1401 5 Thermocouple/RTD and linear input 3 100 - 240 VAC
(switching)
with dual alarm and analog output
2. INSTALLATION
2.1 INSTALLATION
1) Make the instrument panel cut-out with the specified cut-out dimensions.
2) Undo the screw (2).
3) Remove the unit from the instrument case (3).
4) Slide the gasket (1) onto the instrument case (3).
5) Slide the instrument case (3) through the cut-out.
6) Slide the mounting frame (4) from the rear over the instrument case so that the snap-in elements
of the mounting frame (4) engage in the recesses at the side.
7) Use a screwdriver to snug the mounting frame (4) and the instrument case (3).
8) Slide the instrument from the front into the instrument case (3).
9) Secure the instrument in the case with the screw (2).
Fig. 3 Installing the Digital Panel Indicator

12
2.2 WIRING GUIDELINES
Connections are to be made with the instrument housing installed in its proper location.
Fig. 4 Rear Terminal Block 1400
Fig. 5 Rear Terminal Block 1401

1400/1401 Digital Panel Indicators 13
A) POWER LINE
Fig. 6 Power Line Wiring
NOTE: 1) To avoid electric shock, connect power supply at the end of the wiring procedure only.
2) The power supply input has no fuse protection. Please provide it externally.
B) INPUTS
Thermocouple Input
Fig. 7 Thermocouple Input Wiring
NOTE: 1) Don’t run input wires together with power cables. Use proper thermocouple extension
wire cable preferably shielded (see table).
2) If shielded cable is used, the shield must be grounded at one point only.
3) Pay attention to the line resistance; a high line resistance may cause measurement errors
(see Product Specifications).
From 100 V to 240 V AC or
24 V AC/DC LINE
12
13

14
THERMOCOUPLE COMPENSATING CABLE COLOR CODES
Thermocouple British American German French
Material BS 1843 ANSI MC 96.1 DIN 43710 NFE 18-001
T Copper + White + Blue + Red + Yellow
Constantan - Blue - Red - Brown - Blue
Blue Blue Brown Blue
J Iron + Yellow + White + Red + Yellow
Constantan - Blue - Red - Blue - Black
Black Black Blue Black
K Nickel Chromium + Brown + Yellow + Red + Yellow
Nickel Aluminum - Blue - Red - Green - Purple
Red Yellow Green Yellow
R Platinum/Platinum + White + Black + Red + White
13% Rhodium - Blue - Red - White - Green
Green Green White Green
S Platinum/Platinum + White + Black + Red + White
10% Rhodium - Blue - Red - White - Green
Green Green White Green
E Chrome + Brown + Violet – –
Constantan - Brown - Red – –
Brown Violet – –
B Platinum 30% RH – + Grey – –
Platinum 6% RH – - Red – –
– Grey – –
Linear Inputs
Fig. 8 Linear Input Wiring

1400/1401 Digital Panel Indicators 15
NOTE: 1) Don’t run input wires together with power cables
2) Use proper cable, preferably shielded
3) Pay attention to the line resistance; a high line resistance may cause measurement
errors.
4) If shielded cable is used, the shield should be grounded at one point only (see Fig. 9)
RTD Input
Fig. 9 RTD Input Wiring
NOTE: 1) Don’t run RTD wires together with power cables
2) If shielded cable is used, the shield must be grounded at one point only
3) Use copper wires with appropriate size (see Product Specifications)
4) The resistance of the 3 wires must be the same
Any external components (like zener barriers etc.) connected between sensor and input terminals
may cause errors in measurement due to excessive and/or not balanced line resistance or possible
leakage currents.
C) ALARM 1 AND ALARM 2 RELAY OUTPUTS
Fig. 10 Alarm 1 Relay Wiring

16
Fig. 11 Alarm 2 Relay Wiring
The relay output is an SPDT relay, without snubber network.
The contact ratings are: 3 A/30 V DC on resistive load or
3 A/250 V AC on resistive load.
The MTBF is 2 x 105at specified rating.
D) ALARM 3 RELAY OUTPUT
Fig. 12 Alarm 3 Relay Wiring
The relay output is an SPST relay, without snubber network.
The contact ratings are: 2 A/30 V DC on resistive load or
2 A/250 V AC on resistive load.
The MTBF is 2 x 105at specified rating.
E) INDUCTIVE LOADS
Switching inductive loads, high voltage transients may occur. These transients may damage the
internal contacts, PCB or affect the performance of the instrument. In this case an external snubber
should be connected across the terminals as near as possible to the terminals (see Fig. 13).

1400/1401 Digital Panel Indicators 17
Fig. 13 External Protection for Inductive Load Greater than 40 mA AC
The value of capacitor (C) and resistor (R) are shown in the following table.
INDUCTIVE C R RESISTOR OPERATING
LOAD (µF) (⍀) POWER (W) VOLTAGE
<40 mA 0.022 100 1/2 260 V AC
<150 mA 0.1 22 2 260 V AC
<0.5 A 0.33 47 2 260 V AC
The same problem may occur when a switch is used in series with the internal contacts as shown in
Fig. 14.
Fig. 14
In this case it should be better to protect the switch also as shown in Fig. 14. Anyway the cable
involved in relay output wiring must be as far away as possible from input or communication cables.

18
F) ANALOG RETRANSMISSION OUTPUT WIRING
For mA output the maximum load is equal to 500 V.
For V output the minimum load is equal to 5 kV.
Fig. 15 Analog Retransmission Output Wiring
3. INSTRUMENT CONFIGURATION
3.1 FRONT PANEL DESCRIPTION
Fig. 16 Front View Digital Panel Indicator
3.1.1 INDICATORS
AL1 - AL2 - AL3
Indicator OFF = no alarm condition
Indicator ON = alarm condition
Indicator flashing = the alarm condition has disappeared but the instrument is waiting for a
manual reset of the alarm.
PK Indicator OFF = instrument shows the measured value
Indicator ON = instrument shows the “Peak high” value
Indicator flashing = instrument shows “Peak low” value

1400/1401 Digital Panel Indicators 19
3.1.2 DISPLAY
The display continuously shows the measured value in eng. units. During configuration and
calibration set up, this display is used to show parameter’s name and the relative value.
3.1.3 KEYBOARD DESCRIPTION
Increases the parameter value or to display the peak high value.
Decreases the parameter value or to display the peak low value.
Selects all the parameters. By pushing the F button the parameters will be shown
sequentially on the display and, at the same time, the value of the previous parameter will
be stored.
During configuration and calibration procedures and alarm threshold setting, it is used to
scroll back to the parameter without storing a new value.
Manual reset of alarms.
Used to reset peak high and peak low and restart the peak detection procedure.
Used to start the default parameters loading procedure.
3.2 INSTRUMENT CONFIGURATION
3.2.1 PRELIMINARY HARDWARE SETTINGS
1) When an analog input different from factory setting (0-20mA) is desired, the jumpers J602 and
J603 should be properly set, in accordance with Fig. 17.
▲
▼
F
R
R▼
+
R F
+
▲ ▼
+

20
Fig. 17 Jumpers for Analog Input
2) The instrument is shipped with a 20mA ( standard) analog retransmission (when
fitted). When it is desired to use a 10 V analog retransmission, the solder jumpers should be set
properly in accordance with the table below.
Output Type SH 5 SH 6 SH 7 SH 8 SH 9
20 mA open open open open open
10 V close close close close close
Fig. 18 Jumpers for Analog Output
3) This device is capable of detecting lead breaks indicating overrange condition as the factory
This manual suits for next models
2
Table of contents
Popular Control Panel manuals by other brands

Gent
Gent Xenex1 Operating manual and Log book

EDM
EDM Solution-16 Safecom Operator's manual

Honeywell
Honeywell Securit 800L Specifications

AERMEC
AERMEC VMF-E2D Use and installation manual

Pneumercator
Pneumercator TMS2000 Operation & maintenance manual

Siemens
Siemens SIMATIC HMI OP 73micro operating instructions