Genvex Optima 310 DESIGN User manual

Version V1.02 - 0209
UK
User ManUal
Optima 310 DESIGN

2
Optima 310
Table of contents
Page
1. Control panel ...........................................................3
2. Installation................................................................4
2.1 Installation of the control panel................................4
2.2 Mounting..................................................................4
3. Start-up.....................................................................5
4. Operating..................................................................6
4.1 Operating and changing of data in the
operating menu........................................................6
4.2 Daily operating options............................................7
4.3 Main menu...............................................................8
4.4 Schedule for week menu.......................................16
4.5 Schedule for defrosting..........................................16
4.6 Schedule for set-points..........................................17
5. Function .................................................................18
5.1 Controlling Optima 310..........................................18
5.2 Extra capacity........................................................18
5.3 Reliability ...............................................................18
6. Connection to PC ..................................................19
6.1 Function description of data logger .......................19
6.2 Direct data logging.................................................21
7. Maintenance...........................................................22
7.1 Unit ........................................................................22
7.2 Water circuit and tank............................................22
7.3 Alarms....................................................................23
7.4 Dismantling/decommissioning the device..............23
8. Troubleshooting ....................................................24
8.1 Safety thermostat for electric heat surface............24
8.2 The device is not running ..................................... 24
8.3 Error on air side.....................................................24
Technical changes may have occurred after
publication of this document

3
Optima 310
1. Control panel
The control panel must be mounted on a wall that is
centrally located in the home.
Since the control panel functions as a room thermostat, it
is important to observe the following:
• Donotexposetodirectsunlight,
• Donotplaceonanouterwall,
• Donotbuilditintothewall,
• Donotplaceoveraheatsource.
A lamp close to the control panel can affect the light
sensor so that it will not regulate the light intensity as
intended.
There are 7 buttons in the ring on the front of the control
panel that are used to operate the panel. The function of
the buttons changes depending on the menu selected.
(More information is available under Operating)
There is an infrared movement sensor located under the
glass screen. You can use this to bring up the menu for
daily control options simply by moving your hand past the
control panel.
(This function can be turned off: See under Main menu/
Display/Menu item 5)
The following are located on the bottom of the control
panel:
1: SD card
2: Room sensor
3: Light sensor
4: Mini USB- socket for connection to computer
1: The SD-card, which can be removed, contains all
the control models and versions that make the control
panel compatible with older versions. The SD-card also
contains all the languages, menus, help texts, symbols
and collected data logs. During the start-up procedure,
the current versions are installed on the control panel
so that the controls can function without the SD-card.
However, the help texts will not appear on the screen and
the data logs will not be saved.
4: In order for a computer to read the data logs, it must
have the Genvex data logger program installed.

4
Optima 310
2. Installation
2.1 Installation of the control panel
The control panel is intended for hanging on a wall. The
control panel must be positioned in the home at a height
ofabout1.5metresfromtheoor.Thecontrolpanelmust
not be countersunk into the wall, since the panel also
functions as a room thermostat. It is also equipped with
a light sensor. The control panel must not be exposed to
direct sunlight. It must not be mounted on an outer wall or
the room sensor will not be able to measure the correct
room temperature and the light sensor will not regulate
the light in the display correctly. It is also recommended
that you do not place a lamp underneath the control panel
as this may also affect the light sensor.
2.2 Mounting
Find the place where the control panel is to be mounted,
marktheplacesfortheholesandscrewthettingonto
the wall.
Hold the wall frame against the wall and mark the holes
for mounting the frame. Drilling of holes, the size of the
holes and the corresponding screws for mounting will all
depend on the wall material.
Placethecontrolpaneldownintothettingsandtipitin
against the wall.
At the bottom of the control panel there is access to:
A: Terminal board. Connection to main circuit board
B: SD card
C: Room sensor
D: Light sensor
E: USB port
Fit a low-voltage cable 4 x 0.25 mm² between the unit
and the control panel. The maximum cable length is
50 m. The voltage drop will be too great if the cable
is over 50 m long and this may produce operational
disturbances.
Thewallxturecanbemountedintwoways:
Screwthextureontoasmoothwallandleadthe1.
cable up from below so that it is visible.
Fit a masonry junction box or a countersunk box to2.
e.g. a plaster wall. If another type of box is preferred,
to must be ensured that the screw hole match.
Connect the low-voltage cable to the terminal box. Check
that the cable is connected to the same numbers at both
ends. (Between the control panel and the main circuit
board in the unit)
Clipthecontrolpanelontothewallxturebymoving
itdownwardsalittlebitoutatthebottomandnishby
pressingitinatthebottomsothatitisushwiththewall.
To dismantle, pull the control panel out slightly at the
bottom and lift it up.
Pos. Amount Product no. Description
1 1 069014 House for panel
2 1 069015 Front for panel
3 1 069016 Plate for display
4 1 069012 Wallttings
5 1 069017 Glas for display

5
Optima 310
3. Start-up
Thersttimethedeviceisstarted,thecontrolpanel
display will show: “Choose language”.
Click “Next” to switch between Danish, English, German
and French.
Press “Enter” when the desired language is shown in the
display.
The control panel will now read the current program
version in the selected language according to the IC
circuit’s version on the main circuit board in the device.
The display will now show:
• Updatingmodel
• Wait1.5minutes(Ittakesapproximately
1.5 minutes to read the
current version)
• Languageload (91)
• Language OK
• Menuload (84)
• Menu OK
• Iconload (369)
• Menu OK
• Resettodefault
• Restarting……..
• Optima310
Then the display will then change to:
• ThesymbolBookmark
• Optima310
• Versionnumber
D (Display): 1.0
C (Controller): 3.0
Finally, the display changes to daily operation and the
device is now in operation with the default settings.
The menu items can now be set as desired for the house
in question and will thereby achieve the most optimal and
most effective utilisation and operation of the device.

6
Optima 310
4. Operating
Optima 310
All Genvex combined ventilation units and domestic hot
water pumps types Combi for houses and are delivered
with Optima 310 control systems, which have default
settings such that the unit can be put into operation.
The default setting is only a basic setting that should be
changed to the operating wishes and requirements of
the house in question and will thereby achieve optimal
utilisation and operation of the device. After the device
has been started, the control panel will be in stand-by and
will display one of the screen savers (can be changed in
the main menu under the item ‘display’). Pass your hand
over the control panel to bring up the symbols on the
screen that show the daily operating options.
4.1 Operating and changing data in
the operating menu
The display normally shows the screen with symbols for
daily operations, where the following buttons can be seen
in connection with daily operation.
Speed (1)
Use this function to set the fan speed to levels 0-1-2-3-4.
The button beside the speed symbol changes between
the 4 speeds. The installation can also be stopped by
holding down the button for 3-4 seconds.
Extended operation (2)
Use this function to set the timer to forced operation
from 0 to 9 hours Use the button next to the symbol for
extended operation to change from 0 to 9 hours. If the
timer is set to 0, speeds 3 and 4 will run until the speed is
changed manually. If the timer is set for between 1 and 9
hours, speeds 3 and 4 will automatically be linked back to
speed 2 after the number of hours the symbol was set at.
Electric catridge (3)
Use this function to turn on or off the supplementary after-
heat.
Use the button beside the after-heat symbol to change
between ON or OFF. If the symbol is set at ON and the
device is equipped with an after-heat surface, the after-
heat will commence as required. If, on the other hand, the
symbol is set to OFF, the after-heat will not commence,
even if it is required.
Temperature (7)
Use this function to set the room temperature.
Use the button next to the temperature symbol to set
the required temperature from 10-65°C. The current
temperature will be displayed at the centre of the screen.
Information (6)
Use this function to get a good overview of the device’s
current operating condition, e.g. temperature, fan setting,
relay status/functions, alarm, timer etc.
Use the button beside the info symbol to read the
installation’s operating condition (more information can be
found in the main menu section under the info operation
item).
Filter (5)
Usethisfunctiontoun-setthelteralarm.Thebutton
besidetheltersymbolun-setsthealarmforlter
change.Toun-setthelteralarm,changethelters
holddownthebuttonwiththeltersymboluntilthe
exclamation mark in the symbol disappears.
Main menu (4)
Use this function to enter the main menu and access the
sub-items date, calendar, user menu, display, information
menu and service menu.
Press help to see a guide for the item that is marked.
Press the exit to return to the previous display screen.
The setting will not be saved when you press here. Use
the arrow buttons to navigate in the menus. The two
arrow buttons will change to plus and minus when you
change the setting.
Use the Enter button to proceed through the menus. If a
menuitemhasbeenchanged,nishbypressingEnter
and the change will be saved.

7
Optima 310
4.2 Daily operation options
The menu item with the Display symbol
This menu is divided into 12 menu items
–01 Language.
Use this to choose between Danish, English,
German or French text in the display.
-02 Program info.
ThismenushowswhichOptimaisttedonthe
device and its version number:
Example: Optima 300 DK D: 1.0 C: 3.0
D represents the control panel’s version number.
C represents the controller version number, i.e.
the program version.
-03 Screen saver.
The following settings can be selected here:
0: Screen saver off
1: Screen saver off, but with light dimming.
2: Room temperature + light dimming
3: Clock + light dimming
4: Clock and Room temperature + light
dimming,
5: Black screen + light dimming
-04 Pause time.
Use this to set how long it should take from
when none of the symbols on the display for
daily operation have been used until it
automatically reverts to the screen saver. From
daily menu to screen saver variable = 1 to 10
minutes. The other automatic return
connections cannot be adjusted. If no button
has been pressed within the time intervals
indicated below, it will automatically revert to
the previous display:
Change in menu item back to menu item = 30•
seconds.
From menu item to main menu = 2 minutes•
From menu item to daily menu = 2 minutes•
-05 Auto wake-up.
It is possible to de-activate the auto wake-up
function, where you can change from the screen
saver to the display with the symbols for the daily
control options by passing your hand over the
control panel. If the function is set to OFF, press
any button to display the daily operating options.
-06 Auto lightness.
If this menu item is set to OFF, the brightness
level for the screen saver will remain at the
brightness level that was entered in item 09 and
through operation with the entered value in item
07. If the menu item is set to ON, the brightness
level of the screen saver will automatically
regulate between the entered values in items 09
and 10 and, when operating, between the
entered values in items 07 and 08. Both will
depend on how dark the room is.
-07 Lightness day.
Use this to enter the maximum brightness for the
control panel when the room is fully lit.
-08 Lightness night.
Use this to enter the minimum brightness
level for the control panel when the room is in
complete darkness.
-09 Lightness day screensaver.
Use this to enter the maximum brightness for the
screen saver when the room is fully lit.
-10 Lightness night screensaver.
Use this to enter the minimum brightness level
for the screensaver when the room is in complete
darkness.
-11 Default reset.
Ifthesetpointsareconguredsothatthe
installation no longer functions as expected and
the cause cannot be found, it is possible to
choose between 2 different options to reset the
menu items to the default settings.
Press 1 to change all menu items to the default•
settings except for the menu items for Speed
(Level), Filter timer, Calendar and Defrost
temperatures.
Press 2 to change all menu items to the default•
settings.
Note: Before performing a reset, ensure that the currently
entered values are noted in a table for the set items.
-12 Safety menu.
It is possible to prevent access to selected main
menu items so that they cannot be changed
withoutapassword,whichisa4-digitgure.For
thersttime,press0fourtimesandthenEnter.
Items 13 to 18 will open. Select the password
under point 18, which will be the password to
access items 13 to 18.
-13 Date and time.
If this item is set to ON, it will not be possible
to enter the menu for Date and Time without
using the selected access code in item 18.
-14 Calendar.
If this item is set to ON, it will not be possible to
enter the menu for Calendar without using the
selected access code in item 18.

8
Optima 310
-15 User menu.
If this item is set to ON, it will not be possible to
enter the menu for User without using the
selected access code in item 18.
-16 Display.
If this item is set to ON, it will not be possible to
enter the menu for Display without using the
selected access code in item 18.
-17 Service menu.
If this item is set to ON, it will not be possible to
enter the menu for Service without using the
selected access code in item 18.
-18 Password.
Enter the selected password here and use this
also in item 12 to enter items 13 to 18. If
you forget your password, contact Genvex
Service department for assistance. To change
the password, enter a new password in this item
and press enter. All passwords will now be
changed to the new password.
4.3 Main menu
There is a book icon at the bottom centre of the daily
control options. This gives access to the main menu.
Press this button to enter the main menu, which is
divided into 6 menus:
• Dateandtime
• Calendar
• Usermenu
• Display
• Infooperation
• Servicemenu
The control buttons change function. Pressing on
“Arrow down” or “Arrow up” will change the symbol to a
horizontal arrow that shows the current location. Press
“Enter” to access to the current menu’s sub-items. Press
“Arrow down” or “Arrow up” again to select the required
menu item. When the horizontal arrow is next to a
menu point, the 2 lines will change place, the font size
will change and the text “Set” will be added. Pressing
“Enter” next to the selected menu item will change the
background of the item to grey. Use the “+” and “-”
buttons to change the current value. Press “Enter” again
to save the changed setting. If you do not wish to make
any changes, it is possible to go back out of the menus
by pressing the button “Exit”. Pressing “Help” will bring
up a short help text on the screen that explains the menu
item. Press one of the buttons to exit the help program.
If no button is pressed within a short period of time, the
control system will automatically exit the programs.
Date and time
Usethisfunctiontocongureandchangethedate.
This menu is divided into 6 menu items:
• 01Hours.
Enterthecurrenthourgurehere.
Changing between “summer” and
“winter” time manually sets the time one
hour back or forward.
• 02Minutes.
Enter the current minute post the hour
here.
• 03Weekday.
Enter the current weekday can be
entered here.
Monday = 1,
Tuesday = 2,
Wednesday = 3,
Thursday = 4,
Friday = 5,
Saturday = 6,
Sunday = 7
• 04Date.
The current can be entered here.
• 05Month.
The current month can be entered here.
January = 1,
February = 2,

9
Optima 310
March = 3,
April = 4,
May = 5,
June = 6,
July = 7,
August = 8,
September = 9,
October = 10,
November = 11,
December = 12.
• 06Year.
The current year can be entered here.
Calendar
Usethisfunctiontocongureandchangeeachday
settingfortheweek.Eachdaycanbeconguredtorun
with different ventilation speeds as required. It is possible
tocopythecongurationfromonedaytoanother.It
is possible to press ON or OFF here, i.e. if there is
a time when there are no people in the building, the
daily settings can be turned off and the device will run
according to the manual settings, e.g. level 1.
This menu is divided into 9 menu items:
• 01
Use this to choose between controlling the
device manually or control the speed (air
exchange) and temperature automatically
accordingtoaxeddayprogram.Ifthe
menu item is set to OFF, the device will be
controlled manually according to the speed
and temperature selected. If the menu item is
set to ON, the device will controlled according
to the day programs entered in the menu
items 02 to 08.
• 02
Monday. Up to 10 change times can be
entered for one day. The times can be entered
in random sequence. Enter the hours in the
rstcolumn.Entertheminutesinthesecond
column. Enter the speed in the third column
S. Use the fourth column to enter the
temperature difference to which the
temperature should be lowered. Example:
If the temperature is set to 21ºC and you then
enter – 2.0º, the device will aim at 19ºC. If the
speed has been changed manually on the
button under daily operation, the program will
revert to the day program at the next change-
time point is passed.
Examples of a day program:
01 07:30 H3 -0.0
02 09:15 H1 -1.0
03 17:00 H3 -0.0
04 18:00 H2 -0.0
05 23:30 H2 -2.0
It is not necessary to use all change-times if the line
only reads 0, it will be skipped by the control system.
03to-08.Thesedayscanbelledin•
individually in the same way as under item 02.
• 09Copyday.Usethismenuitemtocopy
one day to another, where the same change-
times, speeds and temperature lowering are
required. For example: From Thursday to
Tuesday.
User menu
Usethisfunctiontocongureandchangethefollowing
sub-items:
Item 1: Temperature
Conguretherequiredtemperaturebetween10°Cand
30°C in order to change the ventilation temperature. It is
apreconditionthatasuitableafter-heatsurfaceistted
tothedevice.Usebypasstoconguretheventilation
temperature to between 2°C and 30°C. (The room sensor
is mounted in the control panel).
Item 2: Service water
Itispossibletocongurethetemperaturetowhich
the heat pump shall heat the service water. It can be
conguredbetween0°Cand55°C.Thedefaultsettingis
52°C.

10
Optima 310
Item 3: Electric cartridge ON/OFF
Byconguringtheset-pointtoON,theelectriccartridge
will engage as required. If the set-point is set to OFF, the
electric cartridge will not engage, even if required. When
the fresh air temperature is below 0°C, it is recommended
that the electric cartridge to supplement the service water
heating and thereby reduce the heating time.
The default setting is OFF
Item 4: Timer levels 3 and 4
At speeds 3 and 4, the device will automatically
reconnect to speed 2 after the number of hours that are
conguredinitem17byconguringtheset-pointtoON:
If the set-point is set to OFF, the device will run at speed
3 or 4 until it is manually changed to another speed. The
timer can also be operated directly with the button with
the symbol for extended operation on the display for daily
operating options.
Item 5: Change lter
Thereisabuilt-inltertimerthatcountshowlongthe
devicehasbeenrunningsincethelastchangeoflter.
Thesetpointcanbeconguredfrom1-6,which
corresponds to 1-6 months.
It is recommended that the set-point should initially be set
at 3, corresponding to 3 months.
Iftheltersaretoodirtyaftertheperiodcongured,
conguretheset-pointtoalowernumber.
Ifisnotnecessarytochangethelterafterthecongured
period,theset-pointcanbeconguredtoalarger
number.
Whenthetimerreachestheconguredvalueforthe
changeoflter,“Alarm”and“Changelter”willbeashat
the top of the screen saver.
Whentheltershavebeenchanged,returntothescreen
display for daily operating options and hold down the
buttonfortheltersymboluntiltheexclamationsign
disappears and the device returns to normal operation.
Display
Thisfunctioncanbeusedtocongureandchangethe
following sub-items:
Language
This function can be used to choose between the
languages Danish, German, English and French.
Programme info
Thisfunctioncanbeusedtocongureandchangehow
the information about the program is displayed. It displays
the version of the software used.
Screen saver
Thisfunctioncanbeusedtocongureandchangehow
the screen saver is displayed.
Interval
Thisfunctioncanbeusedtocongureandchangehow
long the interval should be.
Auto wake-up
Thisfunctioncanbeusedtocongureandchangewhen
the auto wake-up starts.
Auto brightness
Thisfunctioncanbeusedtocongureandchangehow
the automatic brightness should be.
Bright day
Thisfunctioncanbeusedtocongureandchangehow
much light there should be on the display during daytime.
Bright night
Thisfunctioncanbeusedtocongureandchangehow
much light there should be on the display during the night
time.
Light day pause
Thisfunctioncanbeusedtocongureandchangehow
long the break should be for light in the display during the
daytime.
Light night pause
Thisfunctioncanbeusedtocongureandchangehow
long the break should be for light in the display during the
night-time.
Default reset
Use this function to return all settings to the factory
default.

11
Optima 310
Safety menu
Thisfunctioncanbeusedtocongureandchangethe
safetylevelintheoperatingcongurationinconnection
with child safety device. It is possible to add a password
for access to changes in the various set-points.
Information menu
The information menu can be used to get an overview of
the devices’ current operating status. If you want to see
the devices’ operating status over an operating period,
connect the control panel to a computer and use the
Optima data program. The device monitors the operating
status every minute and stores the data for up to one
year on the SD card.
• PressEnternexttotheinformationmenu.The
rstscreendisplayedshowsthecurrent
temperatures:
T1: Supply
T2: Room
T3: Fresh air
T4: Exhaust
T5: Pre-cooling surface
T6: Cooling surface
T7: Service water top
T8: Service water bottom
T9: Auxiliary sensors
• PressArrowdowntodisplaythecurrentspeeds
of the fans and the opening of the bypass
valve and the opening of the water valve:
Supply air in %
Extract air in %
Bypass valve in %
Water valve in %
Press the Arrow down again to display the current•
status of the operation relays: For extra electrical
heat level R5, R6 and R7, an extra relay circuit board
isttedwithR10,R11andR12.WhenR5isON,R10
is ON. When R6 is ON, R11 is ON. When R7 is ON,
R12 is ON.
•
R1: Compressor
R2: Electric cartridge
R3: Electrical after-heat
R4: Defrosting
R5: Heating service water
R6: Heating room
R7: Extra cooling
R8: Help function
R9: Help function
Press Arrow down again to display the current•
Alarms. An Alarm it is activated if the word ON
appears beside it. At ON there is an alarm, which can
also be seen on the screen saver and the image for
daily control options, where it says alarm above it.
The information menu shows which alarm it is. For
thealarmforchangelter,Changelterwillblinkover
the word Alarm. The alarm will read OFF when the
errorhasbeencorrectedorthelterischangedand
reset.
Possible error messages for:
Control system stopped ON
Error: Filter not changed after 14 days./ For water
frost error/The device is equipped with an
external switch between terminals 28 and 29. An
Alarm will be given when these are short circuited
and the device will stop.
ChangelterON
Error:Theltersmustbechanged
Pressure switch ON
Error: The high-pressure switch is disconnected
due to excessive pressure in the cooling system.
Water frost ON
Error: Water after-heat surface temperature too
low (risk of ice)
Com error ON
Error: The control panel cannot communicate
with the main circuit board (between display and
circuit board)
Press the Arrow down again to display the hour•
counter, which counts from the day the device is
putintooperation.Theguresshownshouldbe
multiplied by 10. This shows how many hours the
device has been running, how many hours the

12
Optima 310
installation has run at the various speeds and how
many hours the relays have been connected (ON):
Total in operation:
Level 0
Level 1
Level 2
Level 3
Level 4
Relay 1 compressor
Relay 2 Electric cartridge
Relay 3 Electric after-heat
Relay 4: Defrosting
Relay 5 Heating of service water
Relay 6: Heating of room
Relay 7: Extra cooling
Relay 8 Help function
Relay 9 Help function
Press Exit to return to the main menu.•
Service menu
Usethisfunctiontocongureandchangethefollowing
sub-items:
Item 10: Level 1 Supply air
Level 1 is the lowest speed and is usually used when
thereisnobodyhome.Bothfanscanbecongured
independently of each other for all levels so that the
volume of air in the air supply and exhaust is equal, which
provides optimal operation. The calibration of the device
must be performed with specialised air measurement
equipment and can be performed without the use of
themainregulatingvalve.Conguringtheairvolumes
without expert advice is not recommended. Incorrect
congurationcanleadtomajorenergyconsumption.The
default setting is 40%.
Item 11: Level 2 Supply air
Level 2 is the recommended speed for the device to run
in order to provide the optimal indoor climate and should
be calibrated for the house’s ventilation requirement.
The default setting is 70%.
Item 12: Levels 3 and 4 Supply air
Level3isthehighestspeedthatcanbecongured.Itis
used e.g. if there are a number of guests or there is a lot
of activity in the kitchen.
The default setting in level 3 is 100%.
Level4alwaysrunsat100%andcannotbecongured.
It is used mainly in summer to lower the indoor
temperature.
Remember that greater volumes of air exchange require
greater levels of energy consumption.
Item 13: Level 1 Extract air
The fan speed is adjusted until the same air volume is
achieved as the supply in level one.
The default setting is 35%.
Item 14: Level 2 Extract air
The fan speed is adjusted until the same air volume is
achieved as the supply in level 2.
The default setting is 55%.
Item 15: Levels 3 and 4 Extract air
The air volume in level 3 is calibrated to the same air
volume as the air supply in levels 3 and 4.
The default setting in level 3 is 70%.
Level 4 always runs at 100%.
Item 16: Fine tuning (T2)
Itispossibletonetunethecontrolpanel’sroomsensor
so the display shows the current room temperature. The
temperature can be adjusted between 0 and -5°C.
Item 17: Timer levels 3 and 4
If automatic reconnection is used for speeds 3 or 4, you
can enter how many hours the installation should run on
level 3 or 4 before it is automatically returns to level 2.
The set-point can be set to between 1 and 9 hours. The
default setting is 3 hours.
Item 18: Filter/stop
Toensurethattheltersarechangedwhenthecontrol
panel blinks “Change Filter”, the set-point can be set to
ON. The device will then stop automatically after 14 days
iftheltershavenotbeenchanged.
Ifyoudonotwantthisprecaution,conguretheset-point

13
Optima 310
to OFF and the device will continue to operate.
The default setting is OFF.
Item 19: Electric cartridge.
If item 3 is set to On and the button on the operating
panel for the electric cartridge is activated, you can
conguretheservicewatertemperatureatwhich
the electric cartridge turns off. The set-point can be
conguredtobetween0and65°C.Ifthetemperature
islowerthanconguredinitem2,theelectriccartridge
will act as back-up/frost protection, or if the container is
completely empty of water, the electric cartridge will act
as an auxiliary heating element. If the temperature is
higher than in item 2, the electric cartridge will heat the
upper part of the container until the set-point is reached.
Item 20 Disinfection
If this point item is set to ON, the service water will be
heated to 65°C, regardless of the temperature setting,
using the electric cartridge once every week in order to
disinfect the container.
The default setting is OFF.
Item 21 Heating water/air
The controls are set to OFF as default in order to
prioritise service water heating before heating the
diffusion air. If you want the control system to prioritise
theheatingofthediffusionair,conguretheset-pointto
ON. The default setting is OFF.
Item 22 Regulation water
If a water after-heat surface with a motor-operated valve
isttedtothedevice,itmaybenecessarytoadjustthe
regulation time.
The less regulation time, the faster the motor-operated
valve will regulate.
Theset-pointcanbeconguredtobetween1and250
seconds.
The default setting is 20 seconds.
Item 23: Regulation electricity
If an electrical after-heat surface or electrical pre-
heatsurfaceistted,itmaybenecessarytoadjust
theregulationtime.Theset-pointcanbecongured
to between 1 and 30 minutes. The default setting is 3
minutes.
Item 24: Minimum air volume
In order to achieve optimal performance, the device’s air
volumes correspond to at least the air volumes contained
in the data sheet for the device in question. If the air
supply and extraction volumes are set lower than the
minimum requirement, the heat pump will stop and only
preheated air from the heat exchanger will be blown into
all the rooms. For devices without a heat exchanger,
unheated fresh air will be blown directly into the rooms.
Item 25: After-heat
Ifanafter-heatsurfaceisttedtothedevice,youcan
decide when you want the after-heat surface to operate.
If the set-point is set to OFF, the after-heat service will
not work, even if it is required. If the set-point is set to
OFF, the after-heat surface will engage as required. It
conguresitselfaccordingtothetemperaturesetinitem
1.
Item 26 Solar collector (ΔT)
Ifasolarcollectoristted,itispossibletocongurethe
temperature difference between the water temperature in
the solar collector (T9) and the service water temperature
(T8) before the solar collector’s circulation pump
starts. The circulation pump will stop again when the
temperature in the solar collector has fallen to the service
water temperature. When the service water temperature
hasreachedtheconguredvalue,thesolarcollector’s
circulation pump will stop even if the temperature
differenceisgreaterthattheconguredvalue.Theset-
pointcanbeconguredtobetween0°Cand5°C.The
default setting is 5°C.
Item 27: Help functions (R9)
Help functions with relay 9 can be used for the following:
Iftheset-pointisconguredto0,thehelprelayis•
turned off.
Iftheset-pointisconguredto1,therelayisonwhen•
the device is running. This can e.g. be used to open
and close the fresh air and exhaust valve.
Iftheset-pointisconguredto2,therelayisonwhen•
there extra heat is required or when you want the
circulation pump to run when heating with the water
after-heat is required.
Iftheset-pointisconguredto3,therelaywillbe•
turnedonwhenachangeoflterisrequired.This
can be used to activate an external alarm.
If the set-point is set to 4, the relay will be turned on•
when extra cooling is required. This function is used if
apre-heatsurfaceisalsottedtothedevice.
Iftheset-pointiscongured5,thecontrolsystem•
can handle an earth heat-exchanger with the aid of
a valve. The relay will be turned on for one of the
following two conditions:
The external temperature, sensor T9, is lower1.

14
Optima 310
thantheconguredvalueinitem37(waterfrost
temperature, typically set at 5°C).
The outdoor temperature, sensor T9, is more than2.
1°Cabovetheconguredtemperatureinitem1and
1°C above the current room temperature.
Example: A temperature of 5°C is selected in item 37 and
a desired temperature of 21°C is selected in item 1 and
the outdoor temperature is 1°C above the current room
temperature.
T9 measures:
5°C 21°C (+1°C)
Valve Valves Valve
switches switches switches
to earth to fresh to earth
heat air from heat
outside
Item 28: Device stop
It is possible to ensure that the device cannot stop by
using the button for the icon:
Select speed in the daily control options by•
conguringtheset-pointtoOFF.
Thedevicewillstopiftheset-pointisconguredtoON.
Item 29: Stop defrosting
It is standard for the defrosting period when the cooling
surface has reached a temperature of 5°C, which is
the default setting. It may be necessary to change
this temperature to a higher value in special operating
conditions where the cooling surface is not completely
defrosted.
The temperature can be adjusted between 0 and 15°C. It
is not recommended to change the default setting without
expert advice.
The default setting is 5°C.
Item 30: Compressor Start/stop
The default temperature difference between start/stop
compressor is ± 0.4°.
It is recommended to change the temperature difference
for special operating situations.
The difference can be adjusted between 0.1 and 1.0°C. It
is not recommended to change the default setting without
expert advice.
The default setting is 0.4°C.
Item 31: Constant ON
If the house’s other heating system is not connected
to the heating pump system, the house’s other heating
system, e.g. boiler, can stop the water pump so that water
pump device with heat exchanger only blows pre-heated
air into all rooms. This will cause increasing problems
with draughts as the temperature falls outside. Devices
without heat exchangers will blow fresh air directly in.
Conguringtheset-pointtoONwilldisconnecttheroom
sensor. The heat pump will always operate and blow
warm air in when the fresh air temperature is below the
temperatureconguredinitem32.
Iftheset-pointisconguredtoOFF,theroomsensor
will regulate the heat pump regardless of the fresh air
temperature.
The default setting is OFF
Item 32: Constant
If constant =ON is connected in item 31, the required
freshairtemperaturecanbecongured.
Thetemperaturecanbeconguredtobetween0°Cand
10°C.
The default setting is 5°C.
Item 33: Reduce the volume of fresh air
For very low fresh air temperatures, lowering the air
supply volume is recommended in order to improve the
heat pump’s operating conditions and to also achieve a
higher diffusion air temperature, even though the same
volumeofairwillbetakenin.Byconguringtheset-
point to ON, the volume of diffusion air will be lowered
whenthefreshairtemperaturefallsbelowthecongured
temperature.Iftheset-pointisconguredtoOFF,there
will be no reduction of the diffusion air volume. This
congurationisusedwhenthereisapre-heatsurfaceon
the fresh air.
The default setting is OFF
Item 34: Fresh air temperature
When the set-point is ON in item 33, it is recommended
thatthefreshairtemperatureisconguredto-10°C.The

15
Optima 310
set-pointcanbeconguredtobetween-15°Cand0°C.
The default setting is -10°C.
Item 35: Supply air volume
When the set-point is ON in item 33, it is recommended
tocongurethereduceddiffusionairvolumeto20%
lowerthevalueconguredinitem11.Thedefaultsetting
is 50%.
Item 36: Extra help functions
Extra help functions with relay 8 can be used for the
following:
Iftheset-pointisconguredto0,acirculationpump•
can be connected for a solar collector, which will be
controlled as described in item 26.
Iftheset-pointisconguredto1,acirculationpump•
can be connected for water after-heat surface. The
pump will only run when there is a heat requirement.
Iftheset-pointisconguredto2,therelayisonwhen•
the device is running. This can e.g. be used to open
and close the fresh air and exhaust valve.
Item 37 Ground heat exchanger
Ifanearthheatexchangeristtedtothedeviceand
menu 27 in item 5 has been selected, it is possible to
congurethelowesttemperatureatwhichtheearthheat
exchanger shall operate.
Thesetpointcanbeconguredtobetween0°Cand
10°C.
The default setting is 0°C.
Item 38 Changing temperature scale
The temperature scale can be changed on the sensors
T7, T8 and T9 from -30°C / 70°C to -10°C / 90°C by
removing the 3 jumpers on the main circuit board and
conguringittoON.Ifthejumpersareattached,thepoint
shouldbeconguredtoOFF.ThedefaultsettingisOFF
The default setting is OFF

16
Optima 310
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Monday
4.4 Schedule for weekly program
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Tuesday
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Wednesday
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Thursday
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Friday
Hours Mi-
nutes
Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Saturday
Hours Minutes Speed Red.
T2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
Sunday
Red. T2 = Reduced room temperature
4.5 Schedule for defrosting
Before cooling
surface °C
Cooling surface °C
15 -5
14 -5
13 -5
12 -6
11 -6
10 -7
9 -7
8 -8
7 -8
6 -9
5 -10
4 -10
3 -11
2 -12
1 -12
0 -13
-1 -14
-2 -14
-3 -15
-4 -15

17
Optima 310
4.6 Schedule for set points
Headline Default: Conguration area: Dato: Dato: Dato: Dato:
1 Temperature 20 10 - 30
2 Service water 52 0 - 55
3 Electric cartridge ON/OFF OFF ON / OFF
4 Timer levels 3 and 4 OFF ON / OFF
5 Change lter 3 1 - 6
10 Level 1air supply 40%
11 Level 2 air supply 70%
12 Level 3 air supply 100%
13 Level 1 extraction 35%
14 Level 2 extraction 55%
15 Level 3 extraction 70%
16 Fine tuning (T2) 3 0 - 5
17 Timer levels 3 and 4 3 1 - 9
18 Filter/stop OFF ON / OFF
19 Electric cartridge 50 0 - 65
20 Disinfection OFF ON / OFF
21 Heating air/water OFF ON / OFF
22 Regulation water 20 1 - 250
23 Regulation electricity 3 1 - 30
24 Minimum air volume 30 0 - 100
25 After-heat OFF ON / OFF
26 Solar collector 5 0 - 5
27 Help functions 0 0 - 5
28 Device stop OFF ON / OFF
29 Stop detrosting 5 0 - 15
30 Compressor dif. 0,4 0,1 - 1,0
31 Constant ON OFF ON /OFF
32 Constant 5 0 - 10
33 Reduce the volume of fresh air OFF ON /OFF
34 Fresh air temperature -10 -15 - 0
35 Diffusion volume 50 0 - 100
36 Extra help function OFF ON / OFF
37 Earth heat exchanger 0 0 - 10
38 Change temperature scale OFF ON /OFF

18
Optima 310
5. Function
5.1 Control system Optima 310
A Combi device is used to heat the service water and the
diffusion air to cover the house’s ventilation requirements
and partial ground heating
1: Service water heating
The service water temperature is controlled by sensor
T8,whichisttedinthebottomofthecontainer.When
heating of the service water is required, the compressor
starts and magnetic valves MA 3 and MA 6 open and the
servicewaterisheatedtotheconguredservicewater
temperature.
2: Room heating
Magnetic valves MA 2 and MA 5 are activated for room
warming. The room temperature is controlled by the
roomsensorT2,whichisttedinthecontrolpanel.If
thistemperaturehasbeenconguredtoe.g.21°C,the
compressor will start when the room temperature falls to
20.6°C. The compressor will stop when it has increased
the room temperature to 21.4°C. If the compressor
cannot maintain the room temperature, the motor-
operated valve (devices with water after-heat surface)
will begin to regulate (PI regulation) when the room
temperature has fallen to 20°C. For devices with electric
after-heatsurface,therstlevelwillengagewhenthe
room temperature has fallen to 20°C. When the room
temperature again reaches 20°C, the electric heat
level will disengage. Devices with an electrical pre-heat
surface will regulate in the same way as an electrical
after-heat surface.
3: No heat requirement
When there is no heat requirement for either service
water heating or room warming, the compressor stops,
but the fans continue to run and the heat in the extraction
air is recycled in the counter current heat exchanger and
is transferred to the diffusion air.
4: Defrosting
The device begins defrosting when the temperature
difference between the temperature before the cooling
surface and the cooling surface becomes too big, which
occurs when ice forms on the cooling surface.
The magnetic valve MA 4 opens, the air intake fan and
the electric heat surface stops until the ice is melted and
the cooling surface has reached a temperature of about
5°C, after which the magnetic valve closes again and the
air intake fan and the electric heat surfaces start again.
5.2 Extra capacity
Electric cartridge:
If there is a greater requirement for heat than the Combi
cansupply,theelectriccartridgecanbeconguredtoON
in the main menu with the shortcut key. When the electric
cartridgeissettoON,sensorT7,whichisttedatthe
centre of the container, will heat the upper half of the hot
watercontainertotheconguredtemperature.
5.3 Operating reliability
High pressure switch:
In order to protect the compressor from running more
than intended, a high pressure switch is built in that will
disconnect when the pressure becomes too great. The
red reset button on the pressure switch is activated in the
cabinet at the condensation outlet hose when the cause
of the error has been found.
Safety thermostat:
Located at the centre of the tank.
(Remember to disconnect the power to the machine
before performing an intervention). Only authorised
personnel should perform repairs.)
Overriding of the diffusion fan:
If the diffusion temperature exceeds 45°C, the diffusion
fan’s speed will increase in order to maintain the diffusion
temperature at 45°C

19
Optima 310
6. Connecting to a PC
6.1 Function description of
data logger
Thedataloggersoftwareisforconguringandmonitoring
Genvex devices. The hardware part of the data logger
is required if you want a connection to the device. The
data logger can only be connected to Optima 180, 200,
250, 300 and 310. The guide assumes a correct and
functioning set-up of the software. See any installation
guide for the software.
The user interface in Genvex data logger
The data logger can be used for several purposes.
Settings for parameters in the control system.•
Setting up and changing the clock program in the•
control system.
Reading of the data logger in the control panel for the•
past 6 years.
A “Live” logging of the device’s current operation.•
Subsequent analysis of a device’s operation•
User interface
The program is constructed with the primary picture in
the centre of the screen where the graphs are shown
that represent the information that is collected from the
control system. At the top is the menu line for the various
settings.
On the left side is shown the values that are read either
“here and now” or the values that lie underneath the red
line. The red line appears when you click on a random
locationonthedisplay.Theguresintheleftcolumn
will then be all of the values that lie below the line. The
colours of the graph in the logging area correspond to
the colours shown on the left hand side. The exact time
oftheloggingwillbedisplayedintheeldatthebottom.
Tip:Clickontheeldfortheclocktochangetheeldto
display “LOG NO.”. This can be useful if you want to refer
toallofaspeciclogging.Atthetopoftheactuallogging
area on the screen there is an area with grey and white
lines. These lines will be red if an exit or function is active.
Hold the mouse cursor over the line for a moment and
a small help text will appear. The left side of the logging
area is a scale for temperatures. The right hand side of
the logging area is the scale for percentages e.g. for the
fan speed. The bottom represents the time-line. A logging
can contain a number of pages and a there will therefore
be a page number in the bottom corners of the logging
area. Change the page by clicking on the red arrow.
Hold down the left mouse button for a moment over the
red arrow to bring up a dialogue box. You can enter the
page number you wish to scroll to here.
The status menu is at the bottom of the page. This line
shows the date and time, whether the data logging is
started or stopped and the control to which the software
iscongured(Canbechangedin“Settings”).
Menus
Files:
Retrieve data – Retrieves data saved earlier on the hard
disc
Saves data – Saves the current logging
Save window – Saves only the current window
Print – Prints the current window
Terminate – Terminates the software
View:
View graphs – Opens a check-box that gives the
possibility to select or deselect the graphs shown on the
screen. This is often to provide an overview.

20
Optima 310
Zoom – To make the picture bigger or smaller
View average – To view an average of the graphs in the
selected window.
Functions:
Startlogging–Opensadialogueboxtoenterale
name. It is a good idea to include the Optima version to
thelename,e.g.writeOpt310aspartofthename.A
new logging is then started from the control panel. The
logging is taken every 20 seconds and is then displayed
on the screen. After a while, the logging will begin to form
an image. If you do not click on the picture to bring up the
red line, the values on the left side will refer to the last
logging.
Stop logging – Stops the logging. The display on the
screen is saved automatically.
One logging – Performs only one single logging. It is not
saved automatically.
Comments to data – A comment to the logging can be
added here.
Delete data – The data can be deleted here.
Data from control system:
Set-points in control system – Opens the box below.
Here, all set-points from the hard disc or the control panel
can be retrieved, changed and then sent back to the hard
disc or the control panel.
The set-points for defrosting can be changed on the right
of the image. Take care when changing these settings.
The “Service menu” displayed is protected with a
password.
The password is not supplied.
Clock/week program in control system – Opens the box
below.
In this box, the clock program in Optima can be made
in a simpler and clearer manner. Select the day of the
week to be programmed by clicking on it. Monday has
been selected in the example. The clock program for
Monday is selected using arrow-up and arrow-down in
the lower window, immediately to the left of the buttons
with the days of the week. Select 1, 2, 3 or 4 under level.
If 0 is selected, the control system will skip the item. If 4
is selected, the device will stop. When the clock program
has been made for the selected day, the day can be
copied to the other days by clicking on the day of the
week. The buttons on the right hand side of the window
are used to receive and send the change times to and
from the control panel and to retrieve and save the clock
program to the hard disc. Terminate closes the window.
Data logging in control system – Here you can retrieve
the saved logging in the control panel to the program.
The logging can cover a maximum of 11 days and is
logged at 2 minute intervals. If the time of the last logging
deviates from the selected time, this should be changed
if possible. This is to accommodate the time-line at the
bottom of the screen. This may e.g. be relevant if the
logging is retrieved from a transmitted loose log circuit
etc.
Table of contents
Other Genvex Control Panel manuals
Popular Control Panel manuals by other brands

BadgePass
BadgePass BP 1501 Quick reference guide

Amerec
Amerec A3 Assembling and Operating Instructions

Dualtech
Dualtech DALM1000 IP Installation and user instructions

Zonefirst
Zonefirst H32 Uni-Zone Installation and operating information

Exhausto
Exhausto EON-TOUCH-6 manual

Spectron
Spectron BE56-2U user manual