Gent Xenex1 Product guide

Operating manual and Log book for the range of
1,2,4 and 8 zone fire Control and Repeat panels
The panels are designed in
accordance with the requirements
of EN54 Part 2:1997 (and include
optional clauses 7.8, 7.11 & 10),
plus the requirements of EN54
Part 4:1997.
This publication covers the:
qConventional fire alarm panels:
1 zone panels:- XENEX1,
75585-01NMB, 13270-01 and
13270-01LB
2 zone panels:- XENEX2,
75585-02NMB, 13270-02 and
13270-02LB
4 zone panels:- XENEX4,
75585-04NMB, 13270-04 and
13270-04LB
8 zone panels:- XENEX8,
75585-08NMB, 13270-08 and
13270-08LB
qFire alarm repeat panels:
XENEX RPT, 75586-08NMB
and 13271-08 and 13271-08LB.
Panel code ending with LB
signify Less batteries.
This manual and logbook is
intended for use by the end user
and should be located in a secure
but accessible position close to
the panel. It is the responsibility of
the end user to maintain the
logbook.
An Installation and
Commissioning guide has
been supplied to your
installer with this panel.
Year 2000 Compliance
The panels are designed in
accordance with the requirements
of LPS2000.
Contents
Page
Description of main 2
controls and indicators
User responsibility 3
Operating instructions 5
Log book 7
Part 2 of 4188-424 Issue 2 1 03/01
http://www.firealarmengineers.com

Description of main
controls and
indicators
Controls (Only available when
access code is entered)
qNumeric keypad. Allows the
entry of numeric data, ie pass-
words, addresses, data, etc.
qShift key. The shift key gives
access to the main functions of
the panel.
qDisplay test key. Pressing the
Display Test key after entering
access code#(*) will initiate a
sequence which illuminates all
the indicators in turn enabling
the indicators to be checked.
#Coded entry is only
required if Cancel Buzzer or
Display test functions are
configured for operation at
Access level 2.
qCancel Buzzer. Pressing the
Cancel Buzzer button after en-
tering access code#(*) will stop
the internal buzzer sounding.
qSystem Reset. The system re-
set key when pressed after en-
tering access code(*) will return
the system to its normal operat-
ing state. If there are uncleared
fires or faults then these condi-
tions will re-occur.
qSound Alarms. Pressing the
Sound Alarms button after en-
tering access code(*) will sound
all of the system alarms. Should
only be pressed in an emer-
gency or at other agreed times,
ie sounder tests.
qSilence Alarms. Pressing the
Silence Alarms button after en-
tering access code(*) will si-
lence the system alarms.
Should only be pressed when
the emergency is over.
*Three digit code.
Indicators.
qFire. When lit indicates that the
system has detected a fire.
qFault. When lit or flashing indi-
cates that there is a fault condi-
tion on the system which
requires rectification.
qZoneFire/Fault/Disablement.
Indicates when there is a fire
(red indicator lit or flashing) or a
fault (yellow indicator flashing)
on the zone applicable to the in-
dicators. A lit yellow indicator in
conjunction with other indicators
is used to indicate various dis-
abled conditions.
qSystem Fault. This indicator
when lit indicates that there is a
fault in the panel’s processor.
qPower Fault. When lit or flash-
ing indicates that there is a
power supply fault present.
qEarth Fault. This indicator
when lit or flashing indicates
that there is an Earth Fault on
the system.
qSounder Fault. When flashing
in conjunction with a flashing
fault indicator indicates a
sounder fault. When lit in con-
junction with the disabled indi-
cator indicates that the
sounders are disabled.
qDisabled. Indicates in conjunc-
tion with the sounder or the
zone indicators a disabled con-
dition.
qTest. When lit indicates that the
panel is in Test mode.
qPower. When lit indicates that
the panel is powered up.
qDay/Night. When lit this indi-
cates that Day Mode has been
enabled. Night Mode is indi-
cated by the indicator being un-
lit.
qAccess/Function. The Ac-
cess/Function lamp will flash
when the shift key is pressed
and be lit when the coded func-
tions are accessed.
Description of main controls and indicators Fire Panels
03/01 2 Part 2 of 4188-424 Issue 2
Cancel
Buzzer System
Reset
Sound
Alarms Silence
Alarms
123
456
789
0
v
Shift or Function
key
Shift
Numeric
keypad
Display test
key
Display
Essential controls
Zones
FIRE
Fault
System
Power
Earth
Sounder
Disabled
Test
Day/Night
Access /
Function
Normally lit
to indicate
Power supply
healthy
The light is lit when
the Function key is pressed
or there is an entry to control
s
with coded access
ZONE Fire, Fault or Disablement indications
Other Fault
indications
1red
yellow
2 3 4 5 6 7
yellow
yellow
yellow
green
8
Power
yellow
Figure 1 Controls and indications
cd8m191
http://www.firealarmengineers.com

User Responsibility
It is recommended that the
persons responsible for the fire
alarm system, should become
familiar with the procedures on
how to operate the controls and
interpret indications given at the
control and repeat panels.
Adequate training should also
have been given from appointed
personnel.
Daily
The British Standard code of
practice for
Fire detection and
alarm systems for buildings,
BS 5839:Part1:1988
, states that
the system should be inspected
daily to ensure that a normal
indication is given at the control
and indicating equipment and that
any previously indicated fault
condition has received appropriate
attention.
a) It recommends entry into the
Log Book provided of all the
system events for future
reference.
b) The person inspecting the
protected premises can ensure
that the use of the area(s)
inspected has not changed
such that the detection and
alarm devices have become
inappropriate.
c) The area(s) can be inspected
to check that no unsafe
practices that could lead to fire
are being undertaken.
Weekly
At Weekly intervals a different Fire
detector or Manual Call Point of
the system should be tested to
ensure the system is capable of
operating under alarm condition.
a) The operation of the alarm
sounders should be checked,
which also provides a regular
reminder to those occupying
the premises that there is a fire
alarm system with a particular
characteristic sound.
b) The test should be performed
at a regular time to avoid
confusion between a test and a
genuine fire alarm.
Quarterly
At quarterly intervals the system
should be inspected and any work
necessary should be performed by
a trained maintenance engineer.
Battery Replacement
NOTE: Any servicing work on
the System must be carried out
by a servicing organisation.
Under normal operating conditions
the maintenance free lead acid
batteries in the Control and
Repeat panels can have a useful
life of up to 5 years from the date
of manufacture.
NOTE: It is recommended that
these batteries are replaced at
4 Yearly intervals from the date
the System is first
commissioned.
CAUTION: The batteries should
only be replaced by trained
service personal.
Fire Panels User Responsibility
Part 2 of 4188-424 Issue 2 3 03/01
http://www.firealarmengineers.com

Testing a Manual Call Point
Push the test key through the hole
in the underside of the call point to
engage the test cam mechanism
and push to operate the cam
mechanism.
At this point the test key is
retained in the call point and
pulling it out will reset the glass.
NOTE: The alarm sounders in
the system will be activated by
this test. To silence alarms
and reset the system, see
operating instructions.
Replacing a broken Glass
WARNING: Take appropriate
precautions when clearing
broken glass to prevent
injury.
NOTE: A weather resistant
version of manual call points
will have two gaskets, a
Cover/glass gasket and a
Spacer/cover gasket, which must
be installed in their respective
position.
These procedures assume the
cover on the manual call point is
open and any broken glass has
been cleared.
a) Insert the glass beneath the
opaque slider ①and locate
bottom of the glass into recess,
ensure the thumb wheel is up
as shown..
b) Place the test key on the cam
(thumb wheel) ②.
c) Fit the call point cover by
hooking it into the top of the
unit. Make sure that the glass
is properly seated (held down).
Withdraw the test key from the
call point ③and then use it to
fit the screw ④securing the
cover to the back box.
User Responsibility Fire Panels
03/01 4 Part 2 of 4188-424 Issue 2
BREAK GLASS
FI R E
CAM
SLIDER
3
4
CALL POINT COVER
THUMB WHEEL
SLIDER
1
2TEST KEY
CALL POINT
BACK BOX AND
MAIN ASSEMBLY
2HOLD ON
TO THE
COVER
Figure 2 Replacing a broken MCP glass
cd8m322
http://www.firealarmengineers.com

Operating instructions
Normal indications
Under normal condition the panel
should give a healthy indication,
with only the green Power
light lit.
The control panel provides system
security by password entry to
controls.
Fire Condition
In the event of an automatic fire
detection the indications given are:
qFIRE light is lit.
qZones-fire light is lit.
qbuzzer sounds continuous tone.
qsystem alarm sounders are
activated
qif applicable, auxiliary equip-
ment is actuated
qif applicable, automatic link to
the Fire Brigade is initiated.
After the emergency is
over
After emergency is over silence
the alarms and reset the system:
a) Enter the 3 digit code
to gain access to
the controls.
b) Press the Silence Alarms
button.
Notice the system alarm
sounders are silenced and
local buzzer sounds continuous
tone.
c) After the cause of the alarm
has been investigated, ensure
smoke and excess heat have
had time to clear from
automatic detectors and
broken manual call point
glasses have been replaced
where necessary. Press the
System Reset button.
Notice the indications return to
their pre fire status.
Fire Panels Operating instructions
Part 2 of 4188-424 Issue 2 5 03/01
Cancel
Buzzer System
Reset
Sound
Alarms Silence
Alarms
123
456
789
0
v
Shift or Function
key
Shift
Numeric
keypad
Display test
key
Display
Essential controls
Zones
FIRE
Fault
System
Power
Earth
Sounder
Disabled
Test
Day/Night
Access /
Function
Normally lit
to indicate
Power supply
healthy
The light is lit when
the Function key is pressed
or there is an entry to control
s
with coded access
ZONE Fire, Fault or Disablement indications
Other Fault
indications
1red
yellow
2 3 4 5 6 7
yellow
yellow
yellow
green
8
Power
yellow
Figure 3 Controls and indications
cd8m191
n n n
http://www.firealarmengineers.com

To Sound Alarms
To re-sound the alarm sounders
during a fire condition:
a) Enter the 3 digit code
to gain access to
the controls.
b) Press the Sound Alarms
button.
Notice the system alarm
Sounders are activated.
To Silence Alarms
To silence system alarm sounders
after they have been actuated:
a) Enter the 3 digit code
to gain access to
the controls.
b) Press the Silence Alarms
button.
Notice the system alarm
Sounders are silenced.
To carry out a display test
a) #Enter the 3 digit code
to gain access to
the controls.
# Coded entry is only
required if Display test function
is configured for operation at
Access level 2.
b) Press the ‘shift‘ button and
then the display button.
Ensure that all the LEDs light in
sequence and the buzzer
sounds.
Fault Condition
In the event of an automatic fault
detection the indications given are:
qFault light is lit
qfault indicators are lit
qbuzzer sounds intermittent.
(except for system fault which is
a continuous sound)
To Cancel fault buzzer
a) #Enter the 3 digit code
to gain access to
the controls.
#Coded entry is only
required if Cancel Buzzer
function is configured for
operation at Access level 2.
b)b) After investigating fault, press
the Cancel Buzzer
button. Notice the buzzer is
silenced but other indications
remain active.
The fault indications are
normally automatically
extinguished once the fault
condition has been rectified.
Action to rectify fault
Suggested action to rectify fault
condition:
NOTE: All fault rectification work
must be done by suitably
qualified personnel.
The fault indicators may be
extinguished during a fire
condition.
The mains failure condition
overrides all other fault indications
in order to preserve battery
standby capacity.
NOTE: A comprehensive fault
finding guide is included in the
Installation and Commissioning
guide.
Operating instructions Fire Panels
03/01 6 Part 2 of 4188-424 Issue 2
v
v
nnn
nnn
nnn
n n n
Visual indications Audible
indication Signals out
Condition Zone
Fire
(1-8)
-Red
Fire
Common
-Red
Disabled
- Yellow Test -
Yellow Power -
Green Access/
Function
- Yellow
Buzzer Sounder
circuits Aux
Relay
contacts
Normally
de-
energised
Comm
on
fault -
Norma
lly
active
Comm
on fire-
Norma
lly
deacti
ve
Normal
indication On Normal Active Deact
ive
Fire On On On On On Change
over Active Active
New fire
(different
zone)
On On On On On Change
over Active Active
AL2, 3 or 4 On On Normal Active Deact
ive
Function
key press On Fast
Pulse Normal Active Deact
ive
Indications on panel
http://www.firealarmengineers.com

Log Book
To comply with
the requirements
of
BS5839 : Part 1 :
1988 and to allow
those concerned
with the fire
detection and
alarm systems to
monitor the long
term performance
of the system, it is
important that a
log is kept, which
includes all the
events relating to
the performance
of the system.
Log book for Part 2 of 4188-424 Issue 2 7 03/01
SITE ADDRESS
____________________________________________________________
____________________________________________________________
____________________________________________________________
Contract No.____________________________________________
Site ID:______________________________________________________
For Service
Normal Hours Mon-Fri__________________________________________
Tel._________________________________________________________
Outside Normal Hours__________________________________________
Tel._________________________________________________________
Manned Centre Telephone_______________________________________
Manned Centre Code No.________________________________________
Responsible Persons on SITE:____________________________________
For each zone record the location description.
Zone number Description of the zonal location
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
AL2 password
http://www.firealarmengineers.com

Fire Panels
03/01 8 Log book for Part 2 of 4188-424 Issue 2
System configuration record
This information will assist the servicing organisation to keep a record of how the system is configured.
Mark in the table below any deviation(s) from the standard factory settings.
Detection and zone circuit configuration
Zone number 12385678
Normal zone operation
(factory setting)
Non latching zone operation
First fire to be a pulsing indication
(factory setting)
First fire to be a steady indication
Zone short circuit to give a fault
(factory
setting)
Zone short circuit to give a fire
Sounders and system reset configuration
Silence alarms and reset to operate independently
(factory setting)
Silence alarms and reset to operate as per BS5839: Part 4
Reset to also action the silence alarms
Sound alarms to operate in fire condition only (
factory
setting)
Sound alarms to operate at any time
Auxiliary relay to energise with fire (factory setting)
Auxiliary relay to energise with sound alarms
Access level
Access levels AL1 AL2
Cancel buzzer (AL1 - factory setting)
Test A & B mode, Cancel Test (AL2 - factory setting) N/A
Display test (AL1 - factory setting)
Repeat panel information
Repeat panel EEPROM
location EEPROM
Data (address) Name of the area where the panel
is installed on site
1st Repeat panel
2nd Repeat panel
3rd Repeat panel
4th Repeat panel
http://www.firealarmengineers.com

Fire Panels Location of system devices
Log book for Part 2 of 4188-424 Issue 2 9 03/01
Location of system devices
Make copies of this page to record details of the system.
This information will assist the servicing organisation to keep a record of how the system is configured.
Zone
Type of system device Location 12345 678
http://www.firealarmengineers.com

Event log Fire Panels
03/01 10 Log book for Part 2 of 4188-424 Issue 2
Event log
Make copies of this page to record details of system events.
Date Time Events Action Date
complete Name
http://www.firealarmengineers.com

Fire Panels Event log
Log book for Part 2 of 4188-424 Issue 2 11 03/01
Event log
Make copies of this page to record details of system events.
Date Time Events Action Date
complete Name
http://www.firealarmengineers.com

Event log Fire Panels
03/01 12 Log book for Part 2 of 4188-424 Issue 2
http://www.firealarmengineers.com
This manual suits for next models
20
Other Gent Control Panel manuals