Eaton VCP-W User manual

I.L. 5229B79H05
Effective 06/2014
Instructions for the Type VCP-W 27 kV Simple Manual Ground and
Test Device
Figure 1 Type VCP-W 27 kV Manual Ground & Test
Device
TABLE OF CONTENTS
1-1 Introduction .....................................................1
1-2 Description ......................................................1
1-3 Operation ........................................................2
1-3.1 Safe Practices .................................................2
Available Style Numbers & Options
STYLE NUMBER DESCRIPTION
1C94354G01………..1200/2000A Top & Bottom
1C94354G11………..1200/2000A Top & Bottom
with Direct Roll-On-Floor
(ROF) wheels installed*
*Roll-On-Floor option requires breaker cell to be
a Direct-Roll-In cell.
WARNING
READ AND UNDERSTAND THESE INSTRUCTIONS
BEFORE ATTEMPTING TO USE THIS DEVICE.
IMPROPER USE CAN RESULT IN DEATH, BODILY
INJURY AND/OR PROPERTY DAMAGE.
CAUTION
BECAUSE OF THE UNIQUE APPLICATION AND
VAST VARIETY OF SYSTEM AND USER
REQUIREMENTS, SPECIFIC OPERATING
PROCEDURES MUST BE DEVELOPED BY THE
USER. FAILURE TO DEVELOP THESE
PROCEDURES COULD LEAD TO IMPROPER USE
OR OTHER MORE SERIOUS CON-SEQUENCES.
1-1 INTRODUCTION
Type VacClad-W switchgear assemblies are
designed with all the bus work completely insulated
for safety. Since the current carrying parts are not
readily accessible, the Type VCP-W Simple Manual
Ground and Test Device is designed for insertion into
the breaker compartment to gain access to the
primary stationary contacts. It provides a convenient
means to:
1. Ground a circuit for maintenance work;
2. Apply potential for cable testing; and,
3. Access both bus and line circuits for “phasing
out” tests.
1-2 DESCRIPTION
The device consists of a drawout element that can be
inserted into a circuit breaker compartment in the
same manner as a Type VCP-W Circuit Breaker. It
includes six terminals and ground bus connections.
Each terminal is isolated from each other and the bus
connection by insulating barriers. The upper and lower
terminals are accessible by removing the respective
front panel. The ground connection is located in the
lower front section of the device.
VacClad-W switchgear is a two-high arrangement. In
the lower compartment the top terminals normally
connect to the main bus and the bottom terminals
normally connect to the incoming line or feeders. In
an upper
P a g e 2I.L. 5229B79H05
Effective 06/2014
Figure 2 Device shown with upper terminals grounded
Figure 3 Device shown with lower terminals grounded
compartment, the opposite normally holds true, i.e., the
top terminals connect to the incoming line or feeders
and the bottom terminals connect to the main bus. This
must be verified for each application. Because of this
two-high arrangement, the bus and the line positions of
the grounding and test device terminals will vary
depending upon whether the device is used in an
upper or lower compartment. Therefore, it is most
important that the bus or line terminals be correctly
identified for each compartment before using this
device.
1-3 OPERATION
1-3.1 SAFE PRACTICES
WARNING
A GROUND AND TEST DEVICE IS A SAFETY-
RELATED DEVICE. IT MUST BE RECOGNIZED
THAT IMPROPER USE CAN RESULT IN DEATH,
SERIOUS PERSONAL INJURY, OR PROPERTY
DAMAGE. THAT IS WHY IT IS MOST IMPORTANT
THAT THE USER DEVELOP SPECIFIC AND SAFE
OPERATING PROCEDURES FOR ITS USE.
The following general safe practices are recommended:
Store the device in a clean, dry area free from
dust, dirt, moisture, etc.
Keep all insulating surfaces, which include pri-
mary support insulation barriers, clean and dry.
Check all primary circuit connections to make
certain that they are clean and tight.
Permit only authorized trained personnel to use
this device.
TAKE EXTREME CARE WHILE USING THIS
DEVICE TO AVOID CONTACTING “LIVE” OR
“HOT” (ENERGIZED) TERMINALS.
CORRECTLY IDENTIFY LINE AND BUS TER-
MINALS FOR THE BREAKER COMPART-
MENT BEFORE USING THIS DEVICE.
Check for correct code plate(s) on the device.
Do not attempt to force the device into the com-
partment.
The grounding of either upper or lower terminals is
accomplished by connecting grounding links (provided
with the device) from either the upper or the lower
terminals to the device ground connection. Cable
testing or “phasing out” testing may be accomplished
by connecting suitable test equipment, as required to
the terminals.
I. L. 5229B79H05 P a g e 3
Effective 06/2014
Figure 4 Side and Front Views
1. 1200/2000 AMP Main Disconnect
2. Removable Grounding Link
3. Lifting Hole
4. Lev in Latch
5. Grounding Contact
6. Code Plate
7. Grounding Connector
8. Link Between Grounding Contact
9. Padlock Provisions
10. Insulating Barrier
11. Wheels
12. Upper Removable Panel
13. Lower Removable Panel
Key Cannot be Removed Until Breaker
or Dummy Element is Locked. Breaker
Can be Locked in “Test” Position Only,
Dummy Element Can be Locked in
“Test” Position or “Connected” Position.
P a g e 4I.L. 5229B79H05
Effective 06/2014
Style 5229B79H05
Printed in U.S.A.
NOTES
Eaton Corporation
Moo n To wns hi p, P A. 1510 8

Other manuals for VCP-W

3

This manual suits for next models

2

Other Eaton Test Equipment manuals

Eaton DILM32-XMAN Manual

Eaton

Eaton DILM32-XMAN Manual

Eaton Xiria User manual

Eaton

Eaton Xiria User manual

Eaton IZM6-TEST-KIT User manual

Eaton

Eaton IZM6-TEST-KIT User manual

Eaton MTK2000 Manual

Eaton

Eaton MTK2000 Manual

Eaton COOPER POWER SERIES Manual

Eaton

Eaton COOPER POWER SERIES Manual

Eaton SEFELEC 5 Series User manual

Eaton

Eaton SEFELEC 5 Series User manual

Eaton Cutler-Hammer 140D481G02R User manual

Eaton

Eaton Cutler-Hammer 140D481G02R User manual

Eaton ZSI User manual

Eaton

Eaton ZSI User manual

Eaton VCP-W Series User manual

Eaton

Eaton VCP-W Series User manual

Eaton CEAG AT-S+ Series Service manual

Eaton

Eaton CEAG AT-S+ Series Service manual

Eaton Sefelec RXS50 User manual

Eaton

Eaton Sefelec RXS50 User manual

Eaton MET User manual

Eaton

Eaton MET User manual

Popular Test Equipment manuals by other brands

Rigol DG4000 Series quick guide

Rigol

Rigol DG4000 Series quick guide

Fluke NetDAQ 2640A user manual

Fluke

Fluke NetDAQ 2640A user manual

HP 54600A User's and service guide

HP

HP 54600A User's and service guide

Instron 5940 Operator's guide

Instron

Instron 5940 Operator's guide

Bosch BAT 131 Original instructions

Bosch

Bosch BAT 131 Original instructions

AUTODIAGGER 100 operating manual

AUTODIAGGER

AUTODIAGGER 100 operating manual

PCE Instruments PCE-RT 2200 manual

PCE Instruments

PCE Instruments PCE-RT 2200 manual

MARTINDALE RC2000 instruction manual

MARTINDALE

MARTINDALE RC2000 instruction manual

Tektronix 4 Series Declassification and security instructions

Tektronix

Tektronix 4 Series Declassification and security instructions

SOFTSTARTUK MIP-6 instruction manual

SOFTSTARTUK

SOFTSTARTUK MIP-6 instruction manual

ANSMANN PowerCheck 12/24V quick guide

ANSMANN

ANSMANN PowerCheck 12/24V quick guide

multicomp pro MP720009 manual

multicomp pro

multicomp pro MP720009 manual

EXFO AXS-200/635i user guide

EXFO

EXFO AXS-200/635i user guide

Viavi OneAdvisor 800 Platform Quick Card User Guide

Viavi

Viavi OneAdvisor 800 Platform Quick Card User Guide

PCB Piezotronics ICP 481A Series Installation and operating manual

PCB Piezotronics

PCB Piezotronics ICP 481A Series Installation and operating manual

Hanna Instruments Pool Line HI9310014 instruction manual

Hanna Instruments

Hanna Instruments Pool Line HI9310014 instruction manual

Agilent Technologies 1100 Series user guide

Agilent Technologies

Agilent Technologies 1100 Series user guide

Amprobe BAT-500 user manual

Amprobe

Amprobe BAT-500 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.