
Eaton Din Rail UPS Advanced User Guide 9340DC—Rev A 15
CChhaapptteerr 66 TTrroouubblleesshhoooottiinngg
66..11 TTyyppiiccaall AAllaarrmmss aanndd CCoonnddiittiioonnss
Table 4. Troubleshooting
Problem Possible Cause Solution
UPS non-responsive (No LEDs or alar )
UPS is powered off Press ON/Off button for two (2) seconds.
Battery is Defective Replace the battery.
UPS Fault Contact Technical Support.
The UPS is always operating in Battery
Mode
Input ay not be properly connected Check the input connection
Input breaker is open
Before reconnecting equip ent, verify
the load atches the UPS capability
specified and output has short circuit
protection. Contact Tech support.
Actual backup ti e cannot be achieved
Battery voltage is to low Charge the battery at least 24 hours (8
hours = ~90%, 24 hours = 100%).
Overload Re ove unnecessary loads. Before
reconnecting equip ent, verify the load
atches the UPS capability specified.
Battery defect Replace the battery
UPS or charge failure Contact Tech Support
Fault Code Displayed
Overload
Re ove unnecessary loads. Before
reconnecting equip ent, verify the load
atches the UPS capability specified.
UPS short-circuit Contact Tech Support
UPS over-te perature
Re ove unnecessary loads. Before
reconnecting equip ent, verify the load
atches the UPS capability specified.
Make sure the UPS is installed in a pre-
tested area that is free of excessive dust
and has adequate airflow. Place the UPS
away fro other units at least 8 in.
(20.32 c ) to avoid interference. For best
perfor ance, keep the indoor
te perature between 32°F and 122°F (0°
C and 50°C).
UPS will not cold start Powerlock
UPS ust be initially connected to AC
power when upon unboxing. To
reactivate Powerlock, shut down the UPS
while AC ains is operating. Press the
power button continuously for 10 seconds
until you hear a BEEP fro the buzzer,
then release the power button to set the
powerlock feature.