Ebmpapst RM-ECd Manual

Operating and Maintenance Instructions
210-OMI13839.docx
ORIGINAL INSTRUCTIONS
Page 1 of 5
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]t.com
Table of Contents
Summary................................................................................................................................................................. 2
Specification ............................................................................................................................................................ 2
Installation ............................................................................................................................................................... 2
Mechanical Outline.................................................................................................................................................. 3
Connection Details .................................................................................................................................................. 3
Operation................................................................................................................................................................. 3
ESD ......................................................................................................................................................................... 4
Safety ...................................................................................................................................................................... 4
Transport and Storage............................................................................................................................................. 4
Maintenance and Servicing ..................................................................................................................................... 4
Declaration of Conformity........................................................................................................................................ 5
Part No
RM-ECd and CN1100
Description
0-10V/PWM fan speed Controller with Tacho Display
Issue
Date
Bug no
Comments
1
07/05/2014
1st Issue by Louis Abraka
2
03/02/2015
Bug 1770
Issue 2 –explained the CN1100
3

Operating and Maintenance Instructions
210-OMI13839.docx
ORIGINAL INSTRUCTIONS
Page 2 of 5
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]t.com
Summary
The control board can be used to generate 0-10V (control voltage - PWM) for multiple fans.
It displays the control voltage value on a legible LCD display.
Depending on the DIP switch settings, the speed of the connected fan can be measured and displayed on the
LCD screens instead.
Specification
Product
RM-ECd
CN1100
Supply Voltage
10V + 10% DC
10V + 10% DC
Supply Current
Up to 1 mA
Up to 1 mA
Inputs
Open Collector fan Tachometer (1)
Open Collector fan Tachometer (1)
Output
0-10V fan speed control signal
0-10V fan speed control signal
Operating Temperature
-20°C to +60°C
-20°C to +60°C
Enclosure
94x94x55mm, IP54 Rating
Unboxed version see Mechanical
outline below
Installation
The RM-ECd is supplied in a plastic box enclosure which has a clear lid.
Four breakout holes are available on the bottom of the plastic box for mounting.
Four fixing holes are also available on the controller board for fixing onto the enclosure.
A screw terminal block J1 is provided on the board for connecting signal wires.
See the mechanical out line below for the connections.

Operating and Maintenance Instructions
210-OMI13839.docx
ORIGINAL INSTRUCTIONS
Page 3 of 5
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]t.com
Mechanical Outline
Connection Details
1. 10V DC Power Supply
2. O/P => 0 -10V Control Signal
3. 0V
4. T => Tacho Signal
Operation
The board is designed to generate a control voltage depending on the potentiometer setting. This can be adjusted
by turning the spindle clockwise for a higher duty cycle PWM signal and vice versa. The range of the PWM is 0-
100% duty cycle which is equivalent to 0-10v. The potentiometer (R4) and spindle are located as seen in
mechanical outline. A DIP Switch (‘T’) on the board enables the user to toggle between control voltage display
and tacho count display. For control voltage display, set the DIP Switch ‘T’ to ON. For tacho count display, set the
same DIP switch to OFF. Only one fan tacho can be monitored or its reading displayed at any one time. To set
the number of pulses per revolution, use DIP switch S0 and Sl. See table below for the various configuration.
Set unused DIP switch S2 to OFF before powering the controller to prevent it entering TEST MODE.
S0
S1
Pulses per revolution
OFF
OFF
1
OFF
ON
2
ON
OFF
3
ON
ON
4

Operating and Maintenance Instructions
210-OMI13839.docx
ORIGINAL INSTRUCTIONS
Page 4 of 5
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]t.com
ESD
Many modern electronic components are susceptible to damage from Electro Static Discharge (Static Electricity).
PCB’s which are Static Sensitive should be stored and transported in anti-static packaging until they are required
to be installed. The board must be mounted in an enclosure or cover to prevent access.
Safety
The controller is only suitable for a low voltage (10V DC) supply
Electrical installations should only be carried out by qualified personnel
This appliance is intended to be enclosed in an enclosure which can be accessed by the user during
commissioning.
Transport and Storage
PCBs should be transported in anti static build-up bag or static dissipative bags.
Store in a dry environment
Storage temperature: -30’C to +60’C.
Maintenance and Servicing
There are no user serviceable parts.

Operating and Maintenance Instructions
210-OMI13839.docx
ORIGINAL INSTRUCTIONS
Page 5 of 5
ebm-papst UK Ltd
Chelmsford Business Park Chelmsford Essex CM2 5EZ
Telephone: +44(0)1245468555 Fax: +44(0)1245466336
e-mail [email protected]t.com
This manual suits for next models
1
Table of contents
Popular Control Unit manuals by other brands

Siemens
Siemens ASR61EX Mounting instructions

Cyclogic
Cyclogic CL-MC03** Series instruction manual

Siemens
Siemens SIMATIC TI525 Hardware and installation manual

Feig Electronic
Feig Electronic ID ISC.MRMU102-A installation manual

Tyco
Tyco DV-5 quick start guide

Alpha IP
Alpha IP RTA 61001-N Quick install guide

Holmatro
Holmatro HDC 8 (J) manual

Belden
Belden GRASS VALLEY AMX-1901 Guide to installation and operation

ICP DAS USA
ICP DAS USA PET-7053 quick start guide

Man&Tel
Man&Tel MT-3000 user manual

WAM
WAM VFS ACCOMPANIMENT TO THE INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Elatec
Elatec TWN4 PALON SQUARE M LF HF Integration manual