ECHOMAX RTE Owner's manual

Power
To turn the unit on press the “Power” button, the ED power
indicator will illuminate continuously.
To turn the unit off press the “Power” button, the ED power
indicator will turn off.
Internal Audible Alarm
Pressing the “Alarm” button will toggle the internal audible alarm
on and off.
When the internal audible alarm is enabled the BLUE alarm
indicator is turned off.
When the internal audible alarm is disabled the BLUE alarm
indicator is illuminated.
The status of the internal audible alarm is stored
in NVM and is retained for use after power
cycling the unit.
Note: the factory
default setting is
internal alarm
enabled.
RTE Active Waterproof Control Box
INSTALLATION AND OPERATION
ensitivity Level Tone Frequency ms of Activity
in 3 sec
1 (least sensitive) 500Hz 250
2 550Hz 200
3 600Hz 150
Connectivity
The waterproof control box has been designed for owner installation.
If, however, you do not feel confident seek the help of a professional.
elect a position for the backing plate on a bulkhead or steering
consul and drill or cut a 57mm hole as shown on the template
supplied overleaf making sure that there are no existing wires
behind the proposed installation.
Fit cable glands to the rear section and feed the RTE, power and
extension wiring through them remembering to keep the two cable
glands at the top so they are level with the PCB connectors. If no
extension alarm is being fitted blank the single lower hole with the
blanking plug and gasket provided. For ease of attaching the wiring
as shown on page two use thin nose pliers to remove and replace
the green male terminal connectors after the wires have been firmly
attached. Only leave sufficient inner cables so that the back plate
can be fixed in position.
Gently tighten waterproof glands.
Check that the O ring is in place and press the front of the control
to the backing plate until the two pop together and are flush.
Attach the front section to the back plate using the four Allen screws
and the Allen key provided.
Audible Alarm ensitivity
The sensitivity of the audible alarm is user adjustable and
can be set to 1 of 7 different levels. The sensitivity setting
will determine the amount of ADA activity, measured in
milliseconds within a 3 second window, required to sound
the audible alarm.
To enter into the alarm sensitivity adjustment mode, press
and hold the“Alarm” button for 5 seconds until the internal
speaker emits a tone.
Subsequent presses of the “Alarm” button will increase the
sensitivity level, which is indicated by the pitch of the tone
emitted by the internal speaker, refer to Table 1.below.
Fig. 2:
Connections at
rear of unit
Fig. 1:
Active control box
indicators
Dimensions
Length: 90mm Width: 72mm Depth: 15mm
Cut out diameter is 57mm
Overall depth 50mm (ex provision for cables)
4 650Hz 100
5 700Hz 50
6 750Hz 20
7 (most sensitive) 750Hz 20
Table 1: Alarm sensitivity chart
Once the level has reached 7 a further press of the “Alarm”
button will cause the sensitivity level to return to level 1.
Once the required sensitivity level has been reached the mode
will time out after 2 seconds of the last “Alarm” button press and
return to normal operation using the chosen sensitivity setting.
The sensitivity setting is stored in NVM and is retained for use
after power cycling the unit.
Note: the factory default setting is level 6.
Illumination
The brightness of the indicators can be adjusted for day and
night vision.
To adjust the illumination level of the indicators, press and hold
the “Alarm” button for 2 seconds; release the button
and the illumination level will change.
The illumination level is stored in NVM and is retained for
use after power cycling the unit.
Note: the factory
default setting is
day mode (the
brightest level).
& X-Band Indicators
The toggling of the internal alarm does not affect the operation
of the S-Band (YELLOW) or the X-Band (G EEN) indicators.
These indicators will illuminate each time the TE is hit with
the relevant ADA pulse.

Power Connections
Use the 2 way terminal connector provided to
connect the unit to the ships supply. Ensure the
connector is wired as indicated in Fig. 3.
Note: If the alarm is active on Box 2 the Green LED indicator
on Box 1 will show an extended flash whenever a radar pulse is
detected. For correct indication, it is suggested to use the alarm
on Box 1 only.
When using an external alarm, the alarm should be wired to
Box 1, as shown in Figure 7.
Using Dual Control Boxes with Active-X & X- RTE
The standard control box may be dual stationed to an exterior
waterproof one as shown below.
0V +12V
PWR
SHIPS SUPPLY
0V +12V
Cutting Template
RTE Connections
Use the 3 way terminal connector provided
to connect the unit to the active X-S antenna.
Ensure the connector is wired as indicated in
Fig. 4. If an X Band TE is being wired just
connect the blue and brown wires.
External Alarm Connections
The unit has the ability to supply a switched signal for an external
alarm. This alarm will operate along with the internal audible alarm.
Use the 4 way terminal connector, provided, to connect the unit to
the external alarm. Ensure the connector is wired as indicated in Fig. 5.
The “EXT ALA M” connections are a switched relay.
The user must provide an external signal to be switched through
these relay connections.
To enable the external alarm the “EXT ALA M ENABLE”
connections must be linked together. It is suggested that this link
is made through a toggle switch to provide a means of disabling
the external alarm.
Note: disabling the internal audible alarm WILL NOT affect the ex-
ternal alarm.
Fig. 5:
External alarm
connectivity
Fig. 6: Dual station connection
Fig. 4: TE connectivity
0V +12V SNS
RTE
TO ACTIVE
X-S ANTENNA
BLUE
BROWN
GREEN
+
YELLOW
EXT
ALARM
EXT
ALAR M
ENABLE
EXTERNAL ALARM
SWITCHED CONTACTS
FOR EXTERNAL ALARM
CONNECT THE ENABLE
TERMINALS TOGETHER
INCLUDE A SWITCH IN
CIRCUIT TO GIVE TOGGLE
CONTROL OF THE EXTERNAL
ALARM FACILITY
2
Fig. 3: Power supply
Manufa tured by
E homax Produ ts in the UK
PO Box 6032, Dunmow CM6 3AS, UK.
Email: e homaxsales@aol. om www.e homax. o.uk
Tel: 00 44 (0) 1371 830216 Fax: 831733
HOLESAW
ÿ57mm(21/4")
90mm
72mm
48 mm
48 mm
DRILL
ÿ3mmx4
Box 2
For
Active X-
TO ACTIVE X
ANTENNA
TO ACTIVE X-
ANTENNA
TO EXTERNAL
ALARM
+12v
Box 1 ( tandard) Box 2 ( tandard)
HIP
UPPLY
+12v
Fig. 7: Connection of External Alarm
For further information on wiring external alarms, see the
Active-X and ActiveX-S Operation Manuals
FIT WITCH
WHEN U ING
EXTERNAL
ALARM
SHIPS
SUPPLY
To Active XS
*
S
HIP
UPPLY Note: Either of the two external alarm terminal options
marked can be used.
Only one control box can be used to indicate -Band
operation by attaching the yellow/green wire to either of
the connections marked above but not both.
✣
✣
✣
✣
✣
✣
To Active X-
Box 1 ( tandard)
Box 2 (Waterproof)
*
*
*
Popular Control Unit manuals by other brands

Unitronics
Unitronics Vision OPLC V100-17-CAN installation guide

Solvis
Solvis SolvisMax SolvisControl Customer operation

KMC Controls
KMC Controls VEB-4303-SDL Series installation guide

AirPatrol Lite
AirPatrol Lite Lite user manual

Telit Wireless Solutions
Telit Wireless Solutions WE310F5-I Hardware user's guide

VADO
VADO geo Installation & maintenance instructions

System Sensor
System Sensor M500SA Installation and maintenance instructions

Sentiotec
Sentiotec IS1 P-IS1-T Instructions for installation and use

weiland
weiland podis FCS 16 5 SI SA M32 installation instructions

Eaton
Eaton XVM PCBA Series instruction manual

Clifford
Clifford Window Roll-Up Module operating instructions

Carel
Carel E5V quick start guide