EKOVENT EKO-RBG1 User manual

Installation- and maintenance instructions 2022-06
Firedamper EKO-RBG1
(incl, -R -C)

EKOVENT AB The right to changes is reserved 2022-06
2
Table of contents
Installation- and mainenance instructions
Product management.................................3
General assembly.......................................4
Mounting accessories ................................5
Owner of manufacturing site: EKOVENT AB, Vellinge
Certication by: RISE Certifiering 0402
Product type description: EKO-RBG1, -R, -C
Approval number : C900166
Fire resistance class: EI 60 (ve i< >o, ho i< >o) S
Assembly instructions .......................... 6-10
Operation and maintenance.....................11
Declaration of performance................ 12-13

EKOVENT AB The right to changes is reserved 2022-06
3
Product management
Transport
The re dampers must be transported to the
installation site using a truck or crane
with lifting fork.
Important !
To avoid damage the product must be
lifted, the product must not be pulled or
lowered hard against the surface.
Reception and inspection
of the delivery
Check the delivery for transport damage
and to ensure that it is copmplete as soon
as it arrives to the site. The approved
delivery is acknowledged by the
consignment note. Products with defects
may not be installed. Contact the supplier
immediatel
Storage
The storage of materials at the site should
be planned so that you get the minimum
possible internal transport. The re
dampers must protected against water and
always stored in a dry place. Furthermore,
they must be handled so that no
mechanical damage occurs to them.
Mounting
Should not be installed outdoors or in
damp area spaces.
Commissioning
The re dampers must not be put into
operation until the complete installation
is in operational condition.
Responsibility and training
Assembly must be carried out by personnel
with training and experience in installation
of re damper products. Electrical
installation requires authorization.
Personnel must read through and
understand this instruction manual before
assembly. For questions, contact the
manufacturer or nearest dealer.
– Damage due to incorrect transport,
handling or storage.
– That the user has failed to inspect,
maintain and to a reasonable extent
take care of the equipment.
EKOVENT AB hereby disclaims all responsibility for:
– Personal injury or property damage as a
result of the product has been used in viola-
tion of instructions and specications in this
manual.
EKOVENT’s liability shall be limited to repair
or replacement of faulty equipment part.
Certication by: RISE Certifiering 0402
Product type description: EKO-RBG1, -R, -C
Approval number : C900166
Fire resistance class: EI 60 (ve i< >o, ho i< >o) S

EKOVENT AB The right to changes is reserved 2022-06
4
Mounting
For the P and CE marking to apply assembly
must always be carried out according to the
supplied assembly instructions. The facility
must be equipped with a smoke detector which
indicates alarm and which activates closing the
re damper. The facility must be connected to
a monitoring system. Mounting device for xing
dampers in the wall/oor is included in the
damper delivery. At assembly, the following
minimum dimensions must be taken into
account:
– Minimum distance between dampers: 200 mm
– Minimum distance to wall/oor: 75 mm
Electrical connection
Electrical connection must be carried out by an
authorized person according to drawings and
current wiring diagram.
Wiring diagram EKO-RBG1
Wiring diagram EKO-RBG1-C
Wiring diagram EKO-RBG1-R
Indikeringsdiod
Pressure transmitter
Indicator diode
Actuator
Connecting according to
the supplier’s instruction
Installation- and mainenance instructions

EKOVENT AB The right to changes is reserved 2022-06
5
100
200
250
Anslutningsstos
EKO-ANS
Förlängningsstos
EKO-FLS
EKO JBG Mont med mått 2013
ØD
61
100
200 200
250 250
ØD
ØD 100 - 500 mm
Ingen förlängningsstos krävs
61 500 61
ØD
61
ØD 630 - 1000 mm
2 st förlängningsstosar krävs
500 100 61
Mounting accessories
Mounting frame EKO-MOP*
* Included in the EKO-RBG1-1 delivery.
Connection socket EKO-ANS

EKOVENT AB The right to changes is reserved 2022-06
64x
Installation- and mainenance instructions
Installation instructions – Installation on building part
Installation without damper caulking
i
H+10 mm
B+10 mm
1
• Supporting construction, exible wall installation plaster wall or equivalent in
re resistance class EI60, thickness 95-200 mm.
• Supporting construction, rigid wall or oor of concrete, brick or concreate blokcs
in re resistance class EI60, thickness 95-200 mm.
3
Attach the EKO-MOP mounting frame to
the building part. Use screws that secure
good attachment. For correct positioning
unfold the help arrows in the corners.
Fold them back before installation of the
damper.
Note! The re damper must always be
mounted with damper shafts horizontal.
Wall opening for the re damper installation:
Duct dim B+10 mm × H+10mm.
2
Important! Ensure that the diagonal
measurement of the hole is similar.
A
B

EKOVENT AB The right to changes is reserved 2022-06
7
4
Seal with re protection sealant between damper and wall.
Attach the re damper to the EKO-MOP mounting frame by
bend up the attachment ears.
Important! Check that the movement of the damper blades
is not obstructed.
Note! The re damper must always be mounted with the
damper shafts horizontal.

EKOVENT AB The right to changes is reserved 2022-06
8
Installation- and mainenance instructions
5
Seal with re protection sealant between the extension socket and the wall.
Attach the extension socket to the building part. Use screws that secure
good attachment.
6
Attach the damper to the extension socket.
Use self-drilling screws. Close with re
protection sealant in the gap between
the extension socket and the damper.
i
• Important! Check that the movement of the damper blades is not obstructed.
• Suspension device for dampers and ducts must correspond to the perforated
re technical class of the building part.
• When installing in a plaster wall, reinforcement must be in sheet metal 45x45 mm
or larger mounted as a frame in the wall construction.

EKOVENT AB The right to changes is reserved 2022-06
9
Installation instructions – Installation on duct
Applies only to installation on horizontal duct
i
H+30 mm
B+30 mm
1
• Supporting construction, exible wall of plaster board or equivalent
in re resistance class EI 60.
• Supporting construction, rigid wall of concrete, brick or concreate bloks
in re resistance class EI 60
2Attach the re damper with guide or
ange connection.
Important! Ensure that the hole
diagonal measures are equal.
Note! The damper must be mounted
so that the rectangular holes in the
plate around the insulation points to
the wall, and the sensor on the side
of the actuator should always be
furthest from the wall.
Note! The re damper must always
mounted with the damper shafts
horizontal.
Wall opening for the re installation:
Duct dimension B+30 mm × H+30mm.
ATTENTION! Installation side facing duct from re protected area!

EKOVENT AB The right to changes is reserved 2022-06
10
Installation- and mainenance instructions
3Carry out suspension of ducts and
dampers according to general regulations.
For reproong and insulation, use
type-approved solution according to
C000893 from Paroc or equivalent.
Note! For damper up to width and height
800 mm, insulate with EI60. Actuator and
motor shelf does not need to be
over-insulated.
Note! For dampers with larger width or
height than 800 mm, insulate with EI60
plus EI30. The actuator does not need to
be overinsulated.
i
• Important! Check that the movement of the damper blades is not obstructed.
• Suspension device for dampers and ducts must correspond to the perforated
re technical class of the building part.
• The re damper must always be mounted with the damper shafts horizontal.
150 mm

EKOVENT AB The right to changes is reserved 2022-06
11
Maintenance
External and internal control
Interval: At least every 3 years.
Check for damage and function:
• Wiring to actuators.
• Limit switches and smoke detectors.
• The damper casing must be free of
foreign matter details that can prevent
movement of the damper blade.
• Actuator attachment.
• Damper blade and sealing strip.
• The corrosion protection.
Function control
Automatic function check
Automatic function check must be
performed at intervals of 48 hours.
Occurring error functions appear in the
display.
Manual function check
See separate instructions for the
monitoring system.
Check that:
• the re damper is fully open during
operation
• the re damper closes completely
• the re damper opens fully
• the re damper closes completely in
the event of a power failure.
Cleaning
Preventive maintenance of the damper
shall be made according to the facility’s
needs. Clean up damper blade and damper
body inside with brush, vacuum cleaner or
dry cloth.
Note!
Water or other liquids must not be used.
Note!
After checking, the re damper must be left
in normal operating mode.
Warning!
Never put your hands inside the damper
when closes. Risk of crushing injuries.
Spare parts list
Actuator, see type designation on the
actuator.
Operation and maintenance

EKOVENT AB The right to changes is reserved 2022-06
12
Installation- and mainenance instructions
Prestandadeklaration
Brand-/brandgasspjäll EKO-RBG1
Typnummer och specikationer framgår av produktens etikett.
Avsedd användning: Brand-/Brandgasspjäll med ett brandskydd av minst 60 min i enlighet med den harmoniserade Europastandarden EN 15650:2010.
Tillverkare: EKOVENT AB, Mejselgatan 7, 23532 Vellinge, www.ekovent.se
Produktcertiering:
RISE, nr 0402, har utfört typprovning samt inledande granskning av tillverkningsstället och tillverkningskontrollen enligt system 1.
Denna prestandadeklaration baserar sig på EG-intyg 0402-CPR- C500091.
Prestandan för RBG1 överensstämmer med prestanda enligt ovanstående förteckning.
Prestandadeklarationen utfärdas på eget ansvar av EKOVENT AB.
Undertecknat för tillverkaren av:
Vellinge 2022-05-11, Michael Brändström Produktutvecklingschef/Ansvarig teknisk dokumentation.

EKOVENT AB The right to changes is reserved 2022-06
13
Prestandadeklaration
Brand-/brandgasspjäll EKO-RBG1-R/C
Typnummer och specikationer framgår av produktens etikett.
Avsedd användning: Brand-/Brandgasspjäll med ett brandskydd av minst 60 min i enlighet med den harmoniserade Europastandarden EN 15650:2010.
Tillverkare: EKOVENT AB, Mejselgatan 7, 23532 Vellinge, www.ekovent.se
Produktcertiering:
RISE, nr 0402, har utfört typprovning samt inledande granskning av tillverkningsstället och tillverkningskontrollen enligt system 1.
Denna prestandadeklaration baserar sig på EG-intyg 0402-CPR- C500091.
Prestandan för RBG1-R överensstämmer med prestanda enligt ovanstående förteckning.
Prestandadeklarationen utfärdas på eget ansvar av EKOVENT AB.
Undertecknat för tillverkaren av:
Vellinge 2022-05-11, Michael Brändström Produktutvecklingschef/Ansvarig teknisk dokumentation.

EKOVENT AB The right to changes is reserved 2022-06
14
Installation- and mainenance instructions
Notes:

EKOVENT AB The right to changes is reserved 2022-06
15
Notes:

HEAD OFFICE
Mejselgatan 7, 235 32 Vellinge
Tel +46 40 42 16 00
www.ekovent.se [email protected]
REGIONAL OFFICE GÖTEBORG
Boråsvägen 5, 435 31 Mölnlycke
Tel +46 31 2307 40
REGIONAL OFFICE STOCKHOLM
Vallgatan 9, 170 67 Solna
Tel +46 8 508 613 00
Table of contents
Other EKOVENT Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

Schako
Schako BKP-EN Additional operating instructions

SOLID AIR
SOLID AIR FDC2 Technical manual

Trox Technik
Trox Technik VFR Assembly and operating instructions

Greenheck
Greenheck VCD Series Installation, operation and maintenance manual

klimaoprema
klimaoprema FD25 product manual

Greenheck
Greenheck ESD-603 Installation, operation and maintenance manual