EKOVENT EKO-SRB1 Assembly instructions

Installation, operating and maintenance instructions 2021-03
Fire damper EKO-SRB1

2
EKOVENT AB We reserve the right to make changes 2021-03
Table of Contents
Installation, operating and maintenance instructions EKO-SRB1
Product handling ........................................3
General assembly.......................................4
Mounting accessories ................................5
Installation instructions........................... 5-6
Operation and maintenance.......................7
Declaration Of Performance.......................8
Certication: 0402 SP Certification
Product type description: EKO-SRB1
Aproval number: SC0848-13
Fire classication: E 60 (ve i< >o, ho i< >o) SC20 000
Owner of place of manufacture: EKOVENT AB, Vellinge

3
EKOVENT AB We reserve the right to make changes 2021-03
Product handling on the construction site
Transport
The re dampers are transported to the
construction site with a forklift or crane
with a lifting fork. To avoid damage, they
must be lifted, not dragged and never lo-
wered hard against the ground.
Reception and inspection
of the delivery
The re dampers are inspected imme-
diately when the delivery arrives at the
workplace. The inspection is to check that
the delivery corresponds to the order and
the consignment note. The approved deli-
very is acknowledged on the consignment
note. Products with defects or defects
must not be installed. Contact the supplier
immediately.
Storage
The storage of materials on the site should
be planned so that you get the least pos-
sible internal transport. The re dampers
must be protected against water and
always stored in a dry place. Furthermore,
they must be handled so that no mechani-
cal damage occurs to them.
Commissioning
The re dampers must not be put into use
until the entire installation is in operational
condition.
– Damage due to incorrect transport,
handling or storage.
– That the user has failed to inspect,
maintain and to a reasonable extent
take care of the equipment.
– Personal injury or property damage as
a result of using the product in violation
of the instructions and specications in
this manual.
EKOVENT AB hereby disclaims all responsibility for:
EKOVENT:s liability shall be limited to repair
or replacement of faulty equipment part.

4
EKOVENT AB We reserve the right to make changes 2021-03
General assembly
Why Fire dampers?
Fire dampers are one of several factors
in a building that together must provide
good re protection in the event of a re.
The re protection requirements are mainly
affected by building class, re load, heat
output, air supply, the rescue service’s
response time and the presence of re
protection technical installations. An al-
ternative to calculations or to prove that
selected solutions meet the set functional
requirements is to use P- and CE-marked
products.
Mounting
In order for the P- and CE marking to
apply, assembly must always take place
in accordance with the supplied assembly
instructions. Other details such as exible
wall sleeve and wall to damper caulking are
ordered separately. The hole size is always
the damper diameter + 55 mm.
Electrical connection
To be performed by a qualied electrician
according to drawings and current wiring
diagram.
Installation, operating and maintenance instructions EKO-SRB1
Wiring diagram actuator

5
EKOVENT AB We reserve the right to make changes 2021-03
Mounting accessories EKO-SRB1
Flexible wall sleeve EKO-GIS
Installation
Gipsväggstos EKO-GIS_mellanvägg 2013
90
Installation in flexible wall
sleeve EKO-GIS
Mounting instructions EKO-SRB1
1. Squeeze the wall sleeve EKO-GIS and
insert it into the hole.
2. Lock the wall sleeve with a sheet metal
screw or pop rivets in the overlap.
EKO SRBG Gipsväggsstos Mont 2013
Plåtskruv eller
popnit av stål

6
EKOVENT AB We reserve the right to make changes 2021-03
Installation, operating and maintenance instructions EKO-SRB1
Assembly instruction EKO-SRB1
Supporting construction - wall or floor in fire resistance class EI 60.
P-approval SC0848-13
1. The duct system should be suspen-
ded and insulated in accordance with
the re resistance of the supporting
construction in which the hole is made
(EI 60). Insulation of the ventilation
duct must be done in accordance with
“Installationsbrandskydd Ventilation
– Rör” section 21.3.4 (ISBN: 978-91-
633-1723-1) corresponding to the re
resistance of the supporting construc-
tion in which the hole is made (EI 60).
2. Mount the damper in the duct.
– No gaps between the damper and
the supporting construction.
Important! The smoke damper should always be installed with the blade
shaft horizontal..
Suspension
EKO-SRB1 Mont schakt 2014
Ø A+55
Fire sealant *
Fire sealant *
Duct Duct
Duct
Duct
EKO-
SRB1
EKO- SRB1
– The damper blade shaft must always
be installed horizontally.
3. Mount the thermal sensor with the sen-
sor probe in the air ow, ensuring that it
does not obstruct the movement of the
damper blade.
4. The following minimum dimensions
must be observed when mounting
– Minimum distance between dampers:
200 mm.
– Minimum distance to supporting con-
struction: 75 mm.
* Fire sealing must be done using an
approved method that complies with
the relevant re classication, e.g.
EKO-KER, EKO-GIS and re protection
sealant.

7
EKOVENT AB We reserve the right to make changes 2021-03
Supporting construction - wall or floor in fire resistance class EI 60.
P-approval SC0848-13
Important! The smoke damper should always be installed with the blade
shaft horizontal..
Operation
Fire damper EKO-SRB1 is a P- and CE
marked damper for re separation of hea-
ting, ventilation and air conditioning instal-
lations in buildings. EKO-SRB1 is always
supplied with an electric safety actuator
complete with thermal sensor that discon-
nects the power to the actuator if the tem-
perature exceeds 72 °C. The facility must
have a smoke detector which indicates an
alarm and which closes the re damper
and which must be connected to moni-
toring systems EKO-MKE/SKE, EKO-KE,
EKO-TME/TSE, MME/SME or equivalent.
Automatic function check takes place eve-
ry 48 hours (or at more frequent intervals),
malfunction is shown in the display.
Maintenance
External and internal control
At least every three years, check the elec-
trical wiring for actuators, end position
contacts and smoke detectors as well as
the damper cover so that no foreign de-
tails can prevent the damper blade from
moving. Also check the attachment of
the actuator, damper blade and sealing
strip so that no damage has occurred.
Also check that the corrosion protection
is intact.
Function control
Automatic: see above.
Manuell: Manual: Manual function check
can be performed from the central unit
menu. During installation, manual function
check can also be performed on the re-
spective slave unit (applies to EKO-MKE/
SKE, EKO-TME/TSE, MME/SME). Manual
function check can be done by pressing
the test button for automatic function
check which is located on the front of
the monitoring unit (applies to EKO-KE).
Powerless damper closes. Check that
the damper is fully open during opera-
tion, closes and opens completely during
testing and closes completely in the event
of a power failure. Otherwise follow the
instructions for monitoring systems EKO –
MKE/SKE, EKO-KE, EKO-TME/TSE, MME/
SME.
Cleaning
We advocate preventive maintenance of
the damper according to the facilities
needs. Clean the damper blade and dam-
per (inside) with a brush, vacuuming or
wiping. NOTE! Water or other liquids must
not be used. Regular testing according to
the P-approval.
Note!
After inspection, the fire damper must
be left in normal working position.
Warning!
Never keep your hands inside the dam-
per when it closes. Risk of crushing
injuries.
Spare parts list
Actuator, see type designation of the ac-
tuator.
Operation and maintenance

EKOVENT AB We reserve the right to make changes 2021-03
8
EKOVENT AB We reserve the right to make changes 2021-03
Installation, operating and maintenance instructions EKO-SRB1
EKOVENTAB,Mejselgatan7
SE-23532VellingeSweden,+4640421600
DECLARATIONOFPERFORMANCE
FireDamperSRB1
Typeandbatchnumberaccordingtoproductlabel.
Firedampertobeusedinconjunctionwithfireseparatingelementstomaintainfire
compartmentationofatleast60minaccordingtoEN15650.2010
EKOVENTAB,Mejselgatan7,23532Vellinge,www.ekovent.se
Certificate:
SPTechnicalResearchInstituteofSweden,nr0402,hasperformedtypetesting,initialinspectionof
themanufacturingplantandfactoryproductioncontrol(FPC)undersystem1
ECCertificateofConformity0402-CPR-SC0844-13
Size
Type
Classification
Ø100mmtillØ630mm
Horizontalduct
E60(hoi<->o)S
Verticalduct
E60(Vei<->o)S
ClassificationaccordingtoEN13501-3
Nominalactivationconditions/sensitivity:
-Sensingelementloadbearingcapacity
-Sensingelementresponsetemperature
Pass
ISO10294-4
Responsedelay(reponsetime):
-Closuretime
Pass
EN1366-2
Operationalreliability:
-Cycling
Pass
EN1366-2
Durabilityofresponsedelay:
-Sensingelementresponseto
temperatureandloadbearingcapacity
Pass
EN1366-2
Durabilityofoperationalreliability:
-Openandclosingcycletests
20000cycles-Pass
EN15650:2010
TheperformanceofSRB1isinconformitywiththedeclaredperformanceabove.
ThisdeclarationofperformanceisissuedunderthesoleresponsibilityofEKOVENTAB.
Signedforandonbehalfofthemanufacturerby:
_______________________________________
Vellinge2017-09-20,MichaelBrändströmR&DManager
Declaration Of Performance

9
EKOVENT AB We reserve the right to make changes 2021-03
Notes:

HEAD OFFICE
Mejselgatan 7, 235 32 Vellinge
Tel 040-42 16 00
www.ekovent.se [email protected]
REGIONAL OFFICE GÖTEBORG
Boråsvägen 5, 435 31 Mölnlycke
Tel 031-23 07 40
REGIONAL OFFICE STOCKHOLM
Vallgatan 9, 170 67 Solna
Tel 08-508 613 00
Table of contents
Other EKOVENT Fire And Smoke Damper manuals
Popular Fire And Smoke Damper manuals by other brands

NCA
NCA HVC 100 Series installation guide

Metal Fab
Metal Fab TB5000 installation instructions

Mandik
Mandik SEDS-R manual

Nailor
Nailor 0100 Series OPERATIONS AND MAINTENANCE PROCEDURES

75F
75F Smart Damper Installation & operation instructions

Trox Technik
Trox Technik FKRS-EU Supplementary installation manual