Elektronikbau- und Vertriebs CETA 106 User manual

Operating manual
106
Heating circuit controller with differential temperature
Version 0950-10
Art. 0450021003
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 1 Freitag, 11. Dezember 2009 1:16 13

Scope of delivery ...............................................................................................................1
General ................................................................................................................................1
Intended use .....................................................................................................................1
Safety ..................................................................................................................................1
General key functions ...................................................................................................... 2
Version display (when starting) ..................................................................................... 2
Basic display .....................................................................................................................3
Functions with direct access ..........................................................................................4
Menu level .........................................................................................................................5
Parameter description .....................................................................................................8
Mounting ...........................................................................................................................17
Connection diagram ....................................................................................................... 18
Fault clearance ................................................................................................................19
Sensor resistance values ..............................................................................................20
Declaration of conformity .............................................................................................. 21
Technical Data ................................................................................................................22
Liability .............................................................................................................................22
Disposal ...........................................................................................................................22
© Elektronikbau- und Vertriebs GmbH
Heisterner Weg 8 - 12
D-57299 Burbach
This document may not be reproduced nor disclosed to third parties, particularly competitors, in original
or copy form without our prior explicit consent. The document is subject to our proprietary rights and
copyrights.
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 2 Freitag, 11. Dezember 2009 1:16 13

1
Scope of delivery
General
Systems with mixed heating circuit are controlled via the heating circuit controller.
Required heating circuit temperature is determined in the flow, depending on
outside temperature.
Systems with heat source and hot water tank are controlled via the differential
temperature controller (differential sensor not included in delivery). When the heat
source temperature exceeds the tank temperature by the value set on the
controller, the circulation pump is activated by the control and the heat absorbed
in the heat source is transported to the hot water tank.
Intended use
The unit is manufactured in accordance with state of the art technology and
approved safety regulations. Nevertheless, using the device can cause danger to
the user or third persons, or damage to the unit and other assets. The unit must
be used exclusively as heating circuit controller or differential temperature
controller.
Safety
All electrical connections, safety measures and protections have to be carried out
by an authorised professional electrician according to the valid standards and VDE-
guidelines, as well as the local regulations. The electrical connection must be a
fixed connection according to VDE 0100.
Hazard symbols in this operating manual
1. 1x Central unit CETA 106
2. 1 x Outside sensor AF200
3. 1x Flow sensor VF202B
4. 8x Screw, plate 2,9x19 mm
5. 3x Screw assembly 4x35 mm
6. 3x Plug U6
7. 2 x Cable clamp
Hazard!
This symbol indicates information that warns of possible safety
risks or severe and fatal injuries!
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 1 Freitag, 11. Dezember 2009 1:16 13

General key functions
2
1. General key functions
Prog
•Change selected submenus
•Change (parameter) setting
•Save value
+ (Plus) or - (Minus)
•Change parameter
•Change menu item
Esc
•Exit setting
•Keep old value
•Select next higher menu level
Esc-Long
•Return to basic display
2. Version display (when starting)
c 106= Type designation Ceta 106
1.5= Version display (due to update, it can
differ from example shown)
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 2 Freitag, 11. Dezember 2009 1:16 13

3
Basic display
3. Basic display
Explanation of symbols
Weekday
14:47 Time
44.0°C Temperature F1 heat storage tank 1
Display pump function T
Display pump function heating circuit
Automatic mode heating circuit after timer program I or II
Heating mode heating circuit
(Operating mode AUTOMATIC or HEATING)
Reduced mode heating circuit
(Operating mode AUTOMATIC or RED. HEATING)
Standby heating circuit
Summer switch-off heating circuit
Frost protection heating circuit
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 3 Freitag, 11. Dezember 2009 1:16 13

Functions with direct access
4
4. Functions with direct access
Manual operation
— Activate by pressing and holding button
— End function by pressing button
Adjustment room setpoint
Press buttons and in the basic display to directly set room day
temperature. Such a variation changes the parameter 06:02 (see parameter
description).
+Controller is in manual mode
Function: Manual operation allows manual start-up of the heating circuit or
measurement of emission without automatic functions. Manual
operation has no influence on an activated Delta-T control.
— The heating circuit pump runs continuously
— The mixing valve is de-energised
Caution!
This function shall only be used by an authorised
professional. Heating circuit temperatures are not monitored
during measurement of emission. Faulty operation or
unsupervised operation of this function may result in
damages to the heating system.
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 4 Freitag, 11. Dezember 2009 1:16 13

5
Menu level
5. Menu level
General menu structure
Basic display
Prog
Esc
01
Menu 01
02
Menu 02
+-
27
Calibration
28
Relay test
02:01
Parameter 01
02:02
Parameter 02
02:nn
Last parameter
+-
+-
+
-
+
-
Prog
Select menu level
Select parameters
Esc
Value 1
Prog
Value 2
+-
Value n
+-
Set parameter value
Prog
Return
without
saving
Return
and save
Esc
Basic display
Prog
Esc
01
Info
02
Prog.
Time programs
+-
27
Sensor
adj.
28
Relay test
+-
+-
+
-
+
-
Prog
Select menu level
Select menu level
Esc
HEZBEGINN
Prog
HEIZENDE
+-
+-
Set
parameter
value
Prog
Return
without
saving
Return
and
save
Prog
Menu structure time programs
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 5 Freitag, 11. Dezember 2009 1:16 13

Menu level
6
Overview of menu level
X2: Function only in bus connection
X3: Are hidden when activating code 03:09
X4: Only when connecting CETA RC
Basic display
01
Info
02
Time programs
06
Heating circuit
03:01
Outdoor actual
03:02
Outdoor long-term
03:03
Outdoor min
03:04
Outdoor max
06:01
Display
heating pump
08:03
'LVSOD\ǻ7SXPS
08:04
Temperature
heat supplier
08:05
Temperature
heat storage tank
08:07
Operating hours
ǻ7SXPS
Prog
Esc
See
See menu structure
time programs
03:01
Code entry
03:02
AutoSet function
03:03
Bus address
03:04
Building type
06:01
Function
06:02
Room day
06:03
Room night
08:08
6WDUWVǻ7SXPS
Esc
Prog
03
System
06:04
Oper.mode
06:05
Time program
06:11
Extended pump
running time
06:13
Room factor
06:14
Room
thermostat function
06:15
Room frost
protection limit
06:18
Minimum
temperature limit
08
Prog T
08:01
Delta-T
oper.mode
08:02
Switch-on
differential
08:03
Switch-off
differential
08:04
Minimum
runtime ofpump
08:05
Min.temp.
heat supplier
26
Time setting
26:01
Time
26:02
Weekday
27
Sensor adj.
27:01
Calibration
sensor 1
27:02
Calibration
sensor 2
27:03
Calibration
sensor 3
27:04
Calibration
sensor 4
28
Relay test
28:01
Relay test 1
28:02
Relay test 2
28:03
Relay test 3
28:04
Relay test 4
08:15
Reset counter
Esc
-
+-
+-
+-
+-
+
+-
+-
Prog
Esc
Prog
Esc
Prog
Prog
Esc
Prog
Esc
Esc
Prog
Esc
Prog
+
-
+
-
+
-
+
-
+
-
+
-
-
+
-
+
03:05
Climate zone
X3 X3 X3 3X
X3
X3 X3
X4
X3
X4
X3
X4
3X
See
See menu structure
time programs
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 6 Freitag, 11. Dezember 2009 1:16 13

7
Menu level
06:02
Mixing valve
open/closed
06:03
Flow actual
06:04
Flow setpoint
03:06
Time for
automatic exit
06:05
Room actual
06:06
Room setpoint
03:07
Anti-blocking
protection
03:09
Code heating
specialist
03:10
Total reset
06:06
Type ofreduced
operation
(ECO/ABS)
06:07
Heating
curve/conductance
06:08
Heating system
(exponent)
06:20
Heat generator
parallel shift
06:19
Maximum
temperature limit
06:09
System frost
protection
06:10
Summer
switch-off
06:24
Actuator
running time
08:06
Max.temp.
heat supplier
08:07
Fin.switch-off
temp.heat supplier
08:08
Max.temp.
heat supplier
08:09
Burner block
heat generator
08:10
Inhibition heat
supplier
X4
3X X3 X3
X3 3X3X
3X3X3X
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 7 Freitag, 11. Dezember 2009 1:16 13

Parameter description
8
6. Parameter description
01 Information level
Display Designation Description
03:01 Outdoor actual Current outside temperature
03:02 Outdoor long-term Average long-term value of outside temperature. Depending on
set building type (03:04), the value is averaged longer or shorter.
03:03 Outdoor min Minimum outside temperature value (0.00 to 24.00 h)
03:04 Outdoor max Maximum outside temperature value (0.00 to 24.00 h)
06:01 Display heating
circuit pump
0: Heating circuit pump is switched off
1: Heating circuit pump is switched on
06:02 Actuator heating
circuit Open/Closed
0: Actuator (mixing valve) in idle position
1: Actuator runs open
2: Actuator runs closed
06:03 Flow heating circuit
actual
Actual temperature on flow sensor of heating circuit F2
06:04 Flow heating circuit
setpoint
Flow setpoint temperature for heating circuit
06:05 Room actual Actual temperature in room X4
06:06 Room setpoint Room setpoint temperature for heating circuit
08:03 Display T-pump 0: Pump is switched off
1: Pump is switched on
08:04 Temperature heat
supplier
Sensor temperature of heat supplier (e.g. collector, solid fuel
boiler) at input F3
08:05 Temperature heat
storage tank
Sensor temperature of heat storage tank at input F1
08:07 Operating hours
T-pum p
Number of pump operating hours
08:08 Starts T-pump Number of pump starts
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 8 Freitag, 11. Dezember 2009 1:16 13

9
Parameter description
02 Time programs
Note: When switch-on and switch-off time are the same, cycle of operation is
switched off.
03 Parameter system
Weekday Cycle of
operation
Switch-on
time
Switch-off
time
1 I 06:00 22:00
1II12:0012:00
2 I 06:00 22:00
2II12:0012:00
3 I 06:00 22:00
3II12:0012:00
4 I 06:00 22:00
4II12:0012:00
5 I 06:00 22:00
5II12:0012:00
6 I 06:00 22:00
6II12:0012:00
7 I 06:00 22:00
7II12:0012:00
Display Designation Description
03:01 Code entry Setting range: 0 … 999
Factory setting: 0
Function:
Show parameters marked with X3.
03:02 Automatic set
function
0=OFF, no automatic sensor detection X3
1=ON, automatic sensor detection
03:03 Bus address Setting range 31 … 35 X3
Factory setting: 31
Function:
If more than one CETA 106 has to be connected via data bus
within a system, each unit must be set to a unique address.
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 9 Freitag, 11. Dezember 2009 1:16 13

Parameter description
10
06 Parameter heating circuit
03:04 Building type Setting range: 1: Light construction (mean value over 6 X3
hours)
2: Medium construction
(mean value over 24 hours)
3: Heavy construction
(mean value over 72 hours)
Factory setting: 2
Function:
This parameter considers the building type by adapting the
calculation of the outside temperature mean value according to
its setting.
03:05 Climate zone Setting range: -50°C … 0°C X3
Factory setting: -12?
Function:
The climate zone is the coldest outside temperature value to be
expected.
03:06 Automatic exit time Setting range: 0,5 ... 10 Min X3
Factory setting: 2 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
03:07 Anti-blocking
protection
Setting range: 0 = OFF X3
1 = ON
Factory setting: OFF
Function:
With this function activated, pump is switched on daily for ca. 20
seconds as protection against blocking during extended switch-
off phases (> 24h).
03:09 Code heating
specialist
Setting range: 0 … 999
Factory setting: 0
Function when setting is greater than 0:
Hide parameters marked with X3.
03:10 To t al re s e t Reset to factory settings
Display Designation Description
06:01 Function Setting range: 0=OFF
1=Unmixed circuit
2=Mixed circuit
Factory setting: 2
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 10 Freitag, 11. Dezember 2009 1:16 13

11
Parameter description
06:02 Room day Setting range: 5 … 30°C
Factory setting: 30°C
Function:
The set temperature is the room setpoint during active cycles of
operation in AUTOMATIC mode and during HEATING mode.
06:03 Room night Setting range: 5 … 30°C
Factory setting: 16°C
Function:
The set temperature is the room setpoint between the cycles of
operation in AUTOMATIC mode and during RED. HEATING mode.
06:04 Operating mode Setting range: 1: Automatic
2: Heating
3: Red. heating
4: Standby
Factory setting: 1
Function:
Automatic: Heating circuit operates in Heating or
Red. heating mode according to the time
program assigned under 06:05
Heating: Heating circuit operates continuously
according to set room day temp. (06:02)
Red. heating: Heating circuit operates continuously
according to set room night temp. (06:03)
under consideration of 06:06
Standby: Frost-protected switch-off of heating circuit
06:05 Time program Setting range: 1: Time program 1
2: Time program 2
3: Time program 1 and 2
Factory setting: 1
Function:
Depending on the setting, the heating circuit operates according
to time program 1, 2 or both, as set in menutree 02 (time
programs).
06:06 Type of reduced
operation (ECO/RED)
Setting range: 0: ECO
1: RED
Factory setting: 0
Function:
The settings are effective in Red. heating operating mode.
ECO: Frost-protected switch-off mode
RED: Reduced mode
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 11 Freitag, 11. Dezember 2009 1:16 13

Parameter description
12
06:07 Heating curve/
conductance
Setting range: 0,05 … 3,50
Factory setting: 1,00
Function:
Determines the heating curve for the heating circuit.
06:08 Heating system
(Exponent)
Setting range: 1.00…10.00 X3
Factory setting: 1,10
Function:
Curvature of heating circuit's heating curve.
Recommendation:1.10: Underfloor heating or
other panel heating systems
1.30: Radiator heating
2.00: Convector and baseboard heating
>3,00: General ventilator applications with
high start temperatures
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 12 Freitag, 11. Dezember 2009 1:16 13

13
Parameter description
06:09 Frost protection Setting range: OFF (----) X3
-50 °C ... +10 °C
Factory setting: 3 °C
Function:
To keep the heating system from freezing in switch-off mode, the
controller is equipped with electronic frost protection.
Caution: Faulty operation can result in damages to
building!
06:10 Summer switch-off Setting range: OFF (----) X3
10 °C ... 30 °C
Factory setting: 20 °C
Function:
Switches off the heating operation when outside temperatures
exceed the desired outside temperature.
06:11 Extended pump
running time
Setting range: 0,0…60,0 Min X3
Factory setting: 5 min
Function:
This function determines extended run time of heating circuit
pump after heating circuit is switched off by time programs.
06:13 Room factor Setting range: 0…500% X3, X4
Factory setting: 100%
Function:
This function determines to what extent a deviation of the room
temperature from the setpoint affects the control of boiler flow
temperature.
Corrected room setpoint = set room setpoint - (deviation x room
factor) / 100
06:14 Room thermostat
function
Setting range: Off (----) X3, X4
0.5…5K
Factory setting: Off (---)
Function:
This function determines a room temperature limit; if limit is
exceeded, heating is turned off.
06:15 Room frost
protection limit
Setting range: 5…30 °C X3, X4
Factory setting: 10 °C
Function:
This function determines the room temperature during switch-off
mode with activated frost-protection.
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 13 Freitag, 11. Dezember 2009 1:16 13

Parameter description
14
08 Parameter Delta-T
06:18 Minimum
temperature limit
Setting range: 5…95°C X3
Factory setting: 20°C
Function:
This function limits the flow temperature of the heating circuit.
The set temperature will be maintained.
06:19 Maximum
temperature limit
Setting range: 5…95°C X3
Factory setting: 75°C
Function:
This function limits the flow temperature of the heating circuit.
The set temperature will not be exceeded.
06:20 Heat generator
parallel shift
Setting range: 0…20K X3
Factory setting: 4K
Function:
The demand value of the heating circuit, plus the shift value, is
transmitted to the heat generator.
06:24 Actuator running
time
Setting range: 0…10 Min X3
Factory setting: 2 min
Function:
Use this setting to adjust the control characteristic of the mixing
valve to the running time of the actuator in increments of 0.1
minutes (6 seconds).
Display Designation Description
08:01 Control mode Setting range: 0 = Delta T OFF
1 = Delta T ON
Factory setting: 1
Function:
The differential control can be switched on or off via the setting.
08:02 Switch-on difference Setting range: (Switch-off difference + 3K) ... 30K
Factory setting: 10K
Function:
If the temperature difference between the sensors of heat
supplier F3 and heat storage tank F1 exceeds the set value, the
pump turns on.
08:03 Switch-off difference Setting range: 2K ... (Switch-on difference - 3K) Factory setting:
5K
Function:
If the temperature difference between the sensors of heat
supplier F3 and heat storage tank F1 drops below the set value,
the pump turns off.
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 14 Freitag, 11. Dezember 2009 1:16 13

15
Parameter description
08:04 Minimum running
time of pump
Setting range: OFF (----)
0.5 ... 60 min
Factory setting: 3 min
Function:
Minimum switch-on time of pump per start.
08:05 Minimum
temperature heat
supplier
Setting range: OFF (----)
5 ... 80 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, pump turns on only after
the sensor of heat supplier F3 has exceeded the set value.
08:06 Maximum
temperature heat
supplier
Setting range: OFF (----)
30 ... 110 °C
Factory setting: 90 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-on after the sensor of heat supplier F3 has
exceeded the set value.
08:07 Final switch-off
temperature
Heat supplier
Setting range: OFF (----)
70 ... 210 °C
Factory setting: OFF
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat supplier F3 has
exceeded the set value.
08:08 Maximum
temperature heat
storage tank
Setting range: OFF (----)
50 ... 110 °C
Factory setting: 75 °C
Function:
Irrespective of switching differentials, the pump performs a
forced switch-off after the sensor of heat storage tank F1 has
exceeded the set value. This switch-off takes priority over
functions 08:07 and 08:06.
08:09 Burner block
Heat generator
Setting range: 0 ... 2
Factory setting: 1
Function: 0 = OFF
1 = Burner block when pump is active
2 = Burner block only for DHW when pump
is active
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 15 Freitag, 11. Dezember 2009 1:16 13

Parameter description
16
26 Time setting
27 Sensor calibration
08:10 Inhibition heat
generator
Setting range: OFF (----) ... 24h
Function:
After burner block is active, the heat generator is also blocked for
the duration of the set time
08:15 Reset counter Setting range: 0 = no reset
1 = Reset counter
Factory setting: 0
Function:
When value is changed to 1 and confirmed, all counters (heat
balance, operating hours and starts) are reset.
Display Designation Description
26:01 Time Setting range: 00:00 ... 23:59
Factory setting: Current time
Function:
Setting of current time.
26:02 Weekday Setting range: 1 ... 7
Factory setting: Current weekday
Function:
Setting of current weekday.
Display Designation Description
27:01 Calibration F1 Setting range: -5K ... +5K
Factory setting: 0K
Function:
Correction of measured sensor value at input of heat storage
tank F1
27:02 Calibration F2 See 27:01 on input flow sensor heating circuit
27:03 Calibration F3 See 27:01 on input heat supplier Delta-T
27:04 Calibration F4 See 27:01 on input outside sensor
Display Designation Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 16 Freitag, 11. Dezember 2009 1:16 13

17
Mounting
28 Relay test
7. Mounting
Drilling pattern for wall fastening
Display Designation Description
28:01 Test output 1 Setting range: 0 = OFF
1 = ON
Factory setting: 0
Function:
By changing the value, the output switches heat circuit pump on
and off (test function), independent of function.
28:02 Test output 2
(mixing valve open)
See 28:01 for mixing valve output open
28:03 Test output 3
(mixing valve
closed)
See 28:01 for mixing valve output closed
28:04 Test output 4
(charge pump
Delta-T)
See 28:01 on input charge pump Delta-T
Hazard!
Mounting must be performed by an authorised professional electrician!
Ensure that unit is de-energised before opening it!
1. Remove terminal area cover from
casing.
2. For mounting, first put a screw
into the wall.
3. Hang controller into the opening.
4. Use controller as template for the
other screw holes.
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 17 Freitag, 11. Dezember 2009 1:16 13

Connection diagram
18
Rail mount
8. Connection diagram
1. Insert mounting feet into rail
mount opening.
2. Lock hook in place by pushing
down.
Hazard!
Connection must be performed by an authorised professional
electrician! Ensure that unit is de-energised before opening it!
230V connections Low voltage connections
L=Phase 230V mains
1=L1 (230V) Pump for mixed heating circuit (MKB)
2=L1 (230V) Mixing valve OPEN
3=L1 (230V) Mixing valve CLOSED
N=Neutral 230V mains, mixing valve, pumps
Connection solar charging pump SOP (isolated), (option)
=Earthing
Bus connections for networking (see parameter 03:03)
Connections without function
RC=Connection CETA RC, (option)
F1=Sensor heat storage tank Delta-T (KVT20), (option)
F2=Sensor flow heating circuit (VF202B)
F3=Sensor heat supplier Delta-T (PT1000), (option)
F4=Sensor outside temperature (AF200)
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 18 Freitag, 11. Dezember 2009 1:16 13
Table of contents