configuration is changed in order to
prevent malfunctioning of the config-
uration and/or ongoing timings.
PASSWORD
The passwords “PA1and “PA2” are used
to access level 1 and level 2 parameters.
To change them and assign them the
desired value, access the ‘parameter pro-
gramming menu’ in the “diS” label folder.
The password is requested:
- PA1 when entering the ‘parameter pro-
gramming menu’;
- PA2 in the “Cnf” folder containing the
level 1 parameters.
USING THE COPY CARD
The Copy card function can be used to
upload and download parameter maps
of one or more of the same type of
instrument. The accessory is connected
to the device using the special TTL serial
port on the instrument. The Copy card
can be used for the following functions:
Upload (UL)
The upload function reads the instru-
ment parameters and writes them onto
the Copy card
Download(dL)
The download function writes the para-
meter map present at that time on the
copy card onto the instrument memory.
NOTE:
Upload = instrument—-> Copy card
Download = Copy card —-> instrument
The operations are performed by access-
ing the folder with the ‘FPr’ label and
selecting the ‘UL’, ’dL’ or ‘Fr’ com-
mands. The operation is confirmed by
pressing the ‘set’ button. If the operation
is successful, a “y” is displayed whereas if
it is unsuccessful an “n” will be dis-
played.
Formatting the copy card
This function is necessary when using the
copy card for uploading for the first
time or when using the copy card on
device models that are not compatible.
NOTE: formatting deletes all the data
on the Copy card and cannot be
undone. Download from reset
Once the copy card has been connected
the instrument is switched on. When the
lamp test is over, one of the following
two labels will be displayed for 5 sec-
onds:
- dLY if the operation is successful
- label DLn if operation fails The display
will then go into default position (probe
or set point).
NOTE: after downloading the instru-
ment will begin to work with the new
parameter map that has just been
downloaded.
REMOTE CONTROL SYSTEMS
(/CS LX - /CSK LX models only)
Televis remote control systems can be
connected using the RS 485 serial input.
To configure the instrument to do this,
you need to access the folder with the
“Add” label and use the “dEA” and “FAA”
parameters.
ADVANCED FUNCTIONS
DOOR SWITCH INPUT
This is a clean contact digital input with
programmable polarity. The door switch
input functions are controlled by the
values of the following parameters:
(+ parameters dOA, PEA, dCO and DFO
for model EWDR 985/CSK (LX))
Parameter H11 is used to configure the
door switch input with values between
-8 and +8. Positive and negative values
are present in order to select the polari-
ty assigned to the input:
NOTE:
the ‘-’ sign indicates that the input is
activated when the contact is closed
The ‘+’ sign indicates that the input is
activated when the contact is open.
LIGHT CONTROLLER
Controls the light relay. The function can
be started in two different ways. If you
press the light button the light relay is
switched on if it was off and is switched
off if it was on. The light status is
recorded by the device as soon as the
button is pressed so that when power is
restored after a black-out the device can
continue to operate in the same way as
before the power failure. The following
parameters control how the light works:
The configuration of these parameters
controls the status of the light relay by
using the digital input as well as the nor-
mal button. The parameter dSd automat-
ically switches on the light relay when
the digital input is enabled and switches
it off when the digital input is disabled
following the delay set by parameter dLt.
Parameter H06 activates the light button
and enables the relay when the door is
open even when the instrument is pow-
ered but is ‘off’. The dedicated button
always deactivates the light relay even if
the digital input is on or during the dLt
delay only if the parameter OFL=Y.
DIAGNOSTICS
PROBE ALARMS
When one of the probes is outside the
nominal operating range or the probe is
open or has shorted, an alarm is gener-
ated if at least one of these conditions
persists for at least 10 seconds.
If at least one of these 3 alarms is sig-
nalled the alarm LED and relay are
enabled.
When activated code E1 appears on the
display. If several alarms are activated at
the same time, they are displayed alter-
nately for 2 seconds each.
An error condition in the room probe
leads to:
- E1 code appears on display
- activation of compressor as indicated
by Ont and OFt
- deactivation of maximum and mini-
mum alarm controller. An error condi-
tion in the defrost probe leads to:
- E2 code appearing on display
- end of defrost due to a time-out
Par Description
dOd Digital input switches off loads
dAd D.I. activation delay
OAO Alarm signal delay after disdisabling the
digital input (door closed)
tdO Time out door open. Time out
signal after activation of D.I.
(door open)
H11 Digital output configurability/polarity 1
H21...H25 Digital output configurability 1...5
Par Description
H06 Button/aux input/door switch light active
when instrument off
dSd Enabling light relay by door switch
dLt Delay Light Relay deactivation delay
OFL Light switch always disables light relay
OAO Alarm signal delay after disabling the
digital input (door closed)
tdO Time out door open. Time out
signal after activation of D.I.
(door open)
H11 Digital output configurability/polarity 1
H21...H25 Digital output configurability 1...5
Signal Description
E1 Faulty room probe
E2 Faulty defrost probe
E3 Faulty display probe
EWDR 983-985/CS (LX) - EWDR 985/CSK (LX) 2/12