
RGF 300
14/53
1.5 rgf300 TECHNICAL CHARACTERISTICS
Voltage 420VAC +/- 10 % three-phase (230VAC and 500VAC on request)
Frequency 50 Hz (60 Hz)
SUPPLY Overvoltage protection for installation Category II (4 KV)
RGF 312 12 A up to 50°C environment, over decrease by 0.6 A/°C
RGF 320 20 A up to 50°C environment, over decrease by 1.0 A/°C
RGF 325 25 A up to 50°C environment, over decrease by 1.2 A/°C
RGF 340 40 A up to 50°C environment, over decrease by 1.8 A/°C
Rated
RGF 360 60 A up to 50°C environment, over decrease by 2.5 A/°C
CURRENT
Overload 200% of the rated current (max. 10” every 3’)
Control circuits 10VA
RGF 312 72 W @ 12A
RGF 320 120 W @ 20A
RGF 325 150 W @ 20A
RGF 340 240 W @ 40A
POWER Thermally dissipated
RGF 360 360 W @ 60A
OPERATING
PRINCIPLE Totally controlled three-phase cutting, with compensation for inductive loads and motors, without need for
connection to NEUTRAL
POWER unit
(Vers. M , V )
The output voltage depends on the control signal prevailing between the
two available at the inputs, which is chosen by means of the pre-
established mode, according to the specific appliance regulating curve.
The action can be :
DIRECT, with the output increasing as the input increases, or
REVERSE, with the output decreasing as the input increases.
Standard Config. : output increasing as the controlled variable increases
OPERATING
CHARACTERISTIC
Regulator
(Vers. M , V , X , Y)
The output voltage changes to keep set to the target point, selected with
the Set-Point, the quantity measured by the transducer prevailing
between the two available at the inputs, which is chosen by means of the
pre-established mode (greater or lesser in value).
The action mode, either direct or reverse, is chosen in consideration of
the controlled quantity, transducer characteristic and load action.
Standard: output increasing as the controlled variable increases
Vers. MTwo
0-20 mA, Ri = 100 hom analog inputs, priority to the greater std.
Vers. VTwo
0-10 Vdc, Ri = 10 khom analog inputs, priority to the greater std.
Control Vers. X, Y Two kohm analog inputs for the NTC sensors supplied (10KΩ
ΩΩ
Ω@
25°C), priority to the hottest sensor std.
Heat protection ON/OFF input, motor protection NC thermal contact
Start/Stop ON/OFF input :Off Vin=0 = Start / ON(VIN=24V) : Stop
Automatic/Manual ON/OFF input:Off (Vin=0) =Automatic /ON (VIN=24V)=Manual
INPUT
SIGNALS
Set-Point 1 / Set-Point 2 ON/OFF input for Set-point 1/2 commutation (Only with PB1064 )
Transducer supply Two +22Vdc (-10% / +20%) 40 mA non-stabilised outputs, protected
from short circuit
Potentiometer supply Two +10Vdc / 5 mA stabilized outputs
Auxiliary control 0-10V / 1 mA analog output for cascade control of other SLAVE units
OUTPUT SIGNALS
RL1 service relay NO/NC relay contact, free from potential, for separate or joint signalling
of : alarm signals absent / start enabling / voltage supply
Version & Input M: 0-20 mA V: 0-10 Vdc X: +10/+60°C Y: -20/+20°C
Target value 0 ... 20 mA 0 … 10 Vdc +10 ... +60 °C -20 ... +20 °C
Proportional range 0.4 … 4 mA 0.3 … 3.5 Vdc 3 … 30 °C
Minimum limit / Cut-Off Adjustable from 0% to 100%
Maximum limit Adjustable from 100% to 0%
Acceleration ramp Adjustable from 1” to 10”
Direct/Reverse presetting Action mode of input prevailing over output : Direct or Reverse
ADJUSTMENTS
AND
PRESETTINGS
Prevailing input presetting Selection mode for prevailing input : greater / smaller
AC LINE ALARM ON Red Signals locked state due to absence of one supply phase
T.K. ALARM ON Red
Signals locked state due to motor thermal protection NC contact opening
RL1 ON Green Signals RL1 service relay energised state
LED
SIGNALLING MANUAL MODE ON Yellow
Signals “MANUAL” operation state at fixed speed