Grozone Control The Simple One CLIMATE CONTROLLER Assembly instructions

1 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
SCC1 GROZONE CLIMATE CONTROLLER “The Simple One”Series...
ADVANCED USER GUIDE
PRODUCT OVERVIEW
Advanced User Guide - Table of Content
Section
Content
Page
1
Temperature Control with a Fan –Low Temp and High Temp limits
2
2
Temperature and Humidity Control with a Fan
3
3
Humidity Control
4
4
CO2 Enrichment with a burner or a tank
5
5
Output Priorities and Fail States
6
6
Factory Settings and Alternate Settings
7
Accessing the factory / alternate setting edit mode.
Changing the CO2 Elevation Parameter
Changing the OUTPUT CONTROL Parameter
Changing the PRIORITY AND FAIL STATES Parameter
9
10
11
12
IMPORTANT NOTICE
Basic information on this product are found in the QUICK START USER GUIDE shipped with the unit
also available online at www.grozonecontrol.com.
Quick Start User Guide - Table of Content
Section
Content
1
Output Descriptions
2
LED Indicators
3
Knob Settings
4
CO2 Sensor Calibration
5
Temperature Control with Fan (and Optional Heater)
6
Temperature and Humidity Control with Fan (and Optional Heater)
7
Humidity Control with a Humidifier or Dehumidifier
8
CO2 Enrichment with a Burner or a Tank

2 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
1- TEMPERATURE CONTROL WITH FAN (AND OPTIONAL HEATER)
To use this mode, you connect your cooling Fan into the FAN 120V Output, set the Slide Switch to
“Cooling” position.
COOLING
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
START / STOP THE FAN
To maintain the temperature around the DAY SETPOINT
(+/- 2°F or +/- 1°C)
Same as Day
ACTION OF
HIGHER
PRIORITY
STOP THE FAN TEMPORARILY
When CO2 output is activated
None, CO2 is enabled during
the Day only
RESUME FAN OPERATION AFTER A 10-MINUTE ON-DELAY
When CO2 output is deactivated when CO2 level is reached
ACTION OF TOP
PRIORITY
MAINTAIN THE FAN ON
in the unlikely event of a temperature sensor failure
Same as Day
OPTIONAL SAFETY HEATING
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
TURN ON / TURN OFF THE HEATER
To save your plants if the lamps alone are not able to ensure a minimum
temperature in your room in a cold weather.
Same as Day
ACTION OF
HIGHER
PRIORITY
NONE
Same as Day
ACTION OF TOP
PRIORITY
MAINTAIN THE HEATER OFF
in the unlikely event of a temperature sensor failure
Same as Day

3 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
2- TEMPERATURE AND HUMIDITY CONTROL WITH FAN (AND OPTIONAL HEATER)
To use this mode, you connect your cooling Fan into the FAN 120V Output, set the Slide Switch to
“Cooling & Dehumidifying” position.
COOLING
DEHUMIDIFYING
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
START / STOP THE FAN
To maintain the temperature and humidity around the DAY SETPOINTS
(+/- 2°F or +/- 1°C for temperature, and +/-2% for humidity)
Same as Day
ACTION OF
HIGHER
PRIORITY
STOP THE FAN TEMPORARILY
When CO2 output is activated
None, CO2 is enabled during
the Day only
RESUME FAN OPERATION AFTER A 10-MINUTE ON-DELAY
When CO2 output is deactivated when CO2 level is reached
ACTION OF
HIGHER
PRIORITY
STOP THE FAN
When Low Temperature Limit is reached in the event of excessive
cooling caused by cold and humid air intake not allowing to reach the
dehumidifying setpoint, even though cooling setpoint has been reached
already.
Same as Day
ACTION OF TOP
PRIORITY
USE THE FAN FOR COOLING ONLY
in the unlikely event of a humidity sensor failure
Same as Day
ACTION OF TOP
PRIORITY
MAINTAIN THE FAN ON
in the unlikely event of a temperature sensor failure
Same as Day
OPTIONAL SAFETY HEATING
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
TURN ON / TURN OFF THE HEATER
To save your plants if the lamps alone are not able to ensure a minimum
temperature in your room in a cold weather.
Same as Day
ACTION OF
HIGHER
PRIORITY
NONE
Same as Day
ACTION OF TOP
PRIORITY
MAINTAIN THE HEATER OFF
in the unlikely event of a temperature sensor failure
Same as Day

4 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
3- HUMIDITY CONTROL WITH A HUMIDIFIER OR DEHUMIDIFIER
To use this mode, you connect your Humidity Equipment (Humidifier or Dehumidifier) into the HUMIDITY 120V
Output, set the Slide Switch to either “Humidifying” or “Dehumidifying” according to your equipment type.
HUMIDIFYING - SLIDE SWITCH TO TOP POSITION
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
START / STOP THE HUMIDIFIER
To maintain the humidity around the DAY SETPOINT
Same as Day
ACTION OF
HIGHER
PRIORITY
NONE
Same as Day
ACTION OF TOP
PRIORITY
MAINTAIN THE HUMIDIFIER OFF
in the unlikely event of a humidity sensor failure
Same as Day
DEHUMIDIFYING - SLIDE SWITCH TO BOTTOM POSITION
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
START / STOP THE DEHUMIDIFIER
To maintain the humidity around the DAY SETPOINT
Same as Day
ACTION OF
HIGHER
PRIORITY
NONE
Same as Day
ACTION OF TOP
PRIORITY
MAINTAIN THE DEHUMIDIFIER OFF
in the unlikely event of a humidity sensor
Same as Day

5 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
4- CO2 ENRICHMENT WITH A BURNER OR A TANK
To use this mode, you connect your CO2 Generator into the CO2 120V Output. CO2 Enrichment will work during
the DAY ONLY.
CO2 ENRICHMENT
CONTROL ACTION
DAY OPERATION
NIGHT OPERATION
BASIC
OPERATION
(lowest priority)
START / STOP THE BURNER OR TANK
To maintain the CO2 PPM level around the DAY SETPOINT
NONE (Disabled at Night)
ACTION OF
HIGHER
PRIORITY
STOP THE BURNER OR TANK
When High Temperature Limit is reached in the event of excessive
heat caused by the burner in your room. See Chart below)
NONE (Disabled at Night)
ACTION OF TOP
PRIORITY
MAINTAIN THE BURNER OR TANK OFF
in the unlikely event of a CO2 Sensor Failure OR a Temperature
Sensor Failure.
NONE (Disabled at Night)
CO2 EMPTY TANK DETECTION:
The SCC1 is able to detect a defective CO2 enrichment period, during which the CO2 PPM level never builds up.
The SCC1 will declare a “CO2 Empty Tank” fault in two conditions:
Condition 1: High Temp limit has been reached twice in a row while CO2 PPM remains low.
When the High Temp Limit is reached while the CO2 level is still low (below setpoint –200 ppm), the SCC1 assumes the CO2 tank is
empty (CO2 tank or propane/natural gas burner tank); if this condition is met at the end of two consecutive “enrichment” cycles, the
SCC1 will declare an empty tank condition.
Condition 2: a 30-minute time has elapsed while CO2 PPM remains low.
The second method is time based. If the CO2 output is ON for 30 minute and the CO2 PPM level is still low after this delay, the SCC1
will also declare an empty tank condition.
Effect of CO2 Output:
When an empty tank condition is met, the SCC1 will DISABLE the CO2 Output and the CO2 Output indicator will flash as long as this
condition is present.
Resetting the Empty Tank Condition:
CLICK the CALIBRATION button to reset this fault. However the fault will appear again if the tank has not been refilled.
The condition will reset automatically if the CO2 PPM level rises in the room up to the CO2 setpoint and every morning when the lights
turn ON to allow the controller to validate whether the tank has been replaced or not.

6 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
5- OUTPUT PRIORITIES AND FAIL STATES
Every CONTROL ACTION taken by the SCC1 is given a priority level. A higher priority action WILL ALWAYS
SUPERSEDE any lower priority action. Output Priorities can be modified with the Alternate Settings.
See Section 6- on next page.
SUMMARY OF CONTROL PRIORITIES AND RELATED ACTIONS (Factory Settings)
PRIORITY
LEVEL
ACTION
NAME
DESCRIPTION OF ACTION ON OUTPUTS
LOWEST
FAN,
HUMIDITY
and HEATER
OUTPUTS
CONTROLLING THE
TEMPERATURE and
HUMIDITY
IN YOUR ROOM
ALL OUTPUTS ARE AFFECTED:
FAN, HUMIDITY and HEATER Outputs are controlled according to Knob Settings.
MEDIUM
CO2 OUTPUT
GIVING CO2 OUTPUT
PRIORITY
OVER FAN OUTPUT
ONLY FAN OUTPUT IS AFFECTED:
The FAN Output is turned OFF when the CO2 Output is turned ON to avoid wasting CO2 outside.
FAN Output resumes operation after a 10-min delay following the CO2 enrichment (timer starts when CO2
Output is turned Off). This delay allows plants to absorb the injected CO2 before re-starting the cooling FAN.
IMPORTANT NOTICE: The CO2 Output priority is suspended while the Output Indicator is flashing during
2 conditions: 1- the High Temp limit has been reached, 2- the Empty tank condition has been met. Refer to
Section 2D of the Quick Start User Guide for further details.
HIGH
TEMPERATURE
LIMITS
LOW TEMPERATURE LIMIT
ONLY FAN OUTPUT IS AFFECTED:
The FAN Output is turned OFF in the “Cooling and Dehumidifying” mode when fan is unable to reach the
HUMIDITY SETPOINT while room temperature is getting too cold.
The Low Temperature Limit is set to 6°F below TEMPERATURE SETPOINT.
Using “Cooling and Dehumidifying” mode is NOT RECOMMENDED when outside air is cold and humid, so
cooling action is possible but dehumidifying action is impossible.
HIGH TEMPERATURE LIMIT
ONLY CO2 OUTPUT IS AFFECTED:
The CO2 Output is turned OFF whenever the temperature gets too high while using a burner that generates
excessive heat in the room. Since CO2 Output is given priority over the Fan Output, the fan will always be OFF
while the burner is ON. If your burner is oversized, high temperature condition (10°F above TEMPERATURE
SETPOINT) is likely to occur. If using a tank, the high temperature limit is not likely to be reached, UNLESS
YOUR TANK IS EMPTY.
TOP
SENSOR
FAILURES
TEMPERATURE SENSOR
FAILURE
FAN OUTPUT IS AFFECTED:
The FAN Output is maintained ON if a temperature sensor failure is detected (damaged, short-circuited or
disconnected). This ensures a proper ventilation at all times.
HEATER OUTPUT IS AFFECTED:
The HEATER Output is maintained OFF if a temperature sensor failure is detected (damaged, short-circuited or
disconnected).
CO2 OUTPUT IS AFFECTED:
The CO2 Output is maintained OFF if a temperature sensor failure is detected (damaged, short-circuited or
disconnected). (To enable CO2 Output while Temp Sensor Falure, use alternate setting)
HUMIDITY SENSOR
FAILURE
HUMIDITY OUTPUT IS AFFECTED:
The HUMIDITY Output is maintained OFF if a humidity sensor failure is detected (damaged, short-circuited or
disconnected).
FAN OUTPUT IS AFFECTED if Slide Switch set to “Cool & Dehumidify”:
The FAN Output will keep working in Cooling mode ONLY. This ensures a proper ventilation at all times.
CO2 SENSOR FAILURE
ONLY CO2 OUTPUT IS AFFECTED:
The CO2 Output is maintained OFF if a CO2 sensor failure is detected (sensor not responding or responds with
a value below 250 ppm). This is a factory setting.
Note: in case of a LIGHT SENSOR FAILURE, the SCC1 is likely to detect a NIGHT at all times, so DAY operation will be
disable.

7 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
6- FACTORY SETTINGS AND ALTERNATE SETTINGS
When shipped from the factory, the SCC1 is set with factory settings. These settings are those that a vast majority
of users will be using during their growing experiences. Advanced users may need to change some settings in order
to fix control problems or to improve control performances in some specific set-ups.
Review below the settings that can be changed by the users.
To make these changes, refer to section below: ACCESSING THE FACTORY / ALTERNATE SETTING
EDIT MODE.
The settings that can be changed are:
1- the CO2 ELEVATION
2- the Fan Output Control DIFFERENTIAL
3- the Humidity Output Control DIFFERENTIAL
4- the CO2 Output Control DIFFERENTIAL
5- the Aux Heater Output Control DIFFERENTIAL
6- the LOW TEMPERATURE LIMIT
7- the HIGH TEMPERATURE LIMIT
8- the Fan And CO2 Outputs PRIORITY MANAGEMENT
9- the Fan Output ON-DELAY
10- the Fan Output FAIL STATE
11- the (optional) AUX Fan Output FAIL STATE
1
FACTORY SETTING
ALTERNATE SETTING
CO2
ELEVATION
Sea level (or 0-ft elevation)
500-ft to 10 000-ft elevation in step of 500 feet.
2
FACTORY SETTING
ALTERNATE SETTING
FAN
OUTPUT
CONTROL
DIFFERENTIAL
Cooling only:
Starts +2°F above setpoint
Stops -2°F below setpoint
Cooling & Dehumidifying:
Starts +2°F OR +4% above setpoints
Stops -2°F below temp setpoint
AND
at humidity setpoints
Cooling only:
Starts +4°F above setpoint
Stops -4°F below setpoint
Cooling & Dehumidifying:
Starts +4°F OR +4% above setpoints
Stops -4°F below temp setpoint
AND
at humidity setpoints
(NOTE: See below Humidity Output Control Differential
to set alternate Humidity Differential value)
3
FACTORY SETTING
ALTERNATE SETTING
HUMIDITY
OUTPUT
CONTROL
DIFFERENTIAL
Dehumidifying:
Starts +4% above setpoint
Stops at setpoint
Humidifying:
Stops at setpoint
Starts -4% below setpoint
Dehumidifying:
Starts +8% above setpoint
Stops at setpoint
Humidifying:
Stops at setpoint
Starts -8% below setpoint
(NOTE: this alternate value will apply to
Cool & Dehumidify as well)

8 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
4
FACTORY SETTING
ALTERNATE SETTING
CO2
OUTPUT
CONTROL
DIFFERENTIAL
DURING THE DAY ONLY
Stops on setpoint,
Starts -200 ppm below setpoint
DURING THE DAY ONLY
Stops on setpoint,
Starts -400 ppm below setpoint
5
FACTORY SETTING
ALTERNATE SETTING
AUX HEATER
OUTPUT
CONTROL
DIFFERENTIAL
Competing Equipment Auto Detection is NOT Set
Starts -8°F below setpoint, stops -2°F below setpoint
Competing Equipment Auto Detection is Set
Starts -8°F below setpoint, stops -2°F below setpoint
or
(*) Starts -12°F below setpoint, stops -6°F below setpoint
to avoid Fan and Heater to compete
(*) will use these values if Low Temp Limit set to Alternate Setting
6
FACTORY SETTING
ALTERNATE SETTING
LOW
TEMPERATURE
LIMIT
While using fan to cool & dehumidify, it stops the fan
if temperature reaches 6°F below setpoint even if it
is still too humid, to avoid freezing the crop. Limit
resets when temperature reaches setpoint.
While using fan to cool & dehumidify, it stops the fan
if temperature reaches 10°F below setpoint even if it
is still too humid, to avoid freezing the crop. Limit
resets when temperature reaches setpoint.
7
FACTORY SETTING
ALTERNATE SETTING
HIGH
TEMPERATURE
LIMIT
Relative to setpoint Temperature Limit:
While injecting CO2, CO2 output is stopped if the
temperature reaches 10°F above setpoint because of
excessive burner heat, then fan will restart
immediately. Limit resets when temperature reaches
setpoint.
Absolute Temperature Limit:
While injecting CO2, CO2 output is stopped if the
temperature reaches 90°F because of excessive burner
heat, then fan will restart immediately. Limit resets
when temperature reaches setpoint.
8
FACTORY SETTING
ALTERNATE SETTING
FAN AND CO2
OUTPUTS
PRIORITY
MANAGEMENT
(3 alternate settings)
The CO2 Output has a higher priority than the
FAN Output. The FAN stops when the CO2 output is
ON. FAN resumes operation following a ON-
DELAY when CO2 Output turns OFF.
RESETTING THE ON_DELAY:
the ON-DELAY is reset to allow the FAN output to turn ON
immediately when CALIBRATION pushbutton is pressed during
normal operation.
The CO2 Output has a higher priority than the
FAN Output. The FAN stops when the CO2
output is ON. FAN resumes operation
immediately (NO DELAY) when CO2 Output
turns OFF.
The FAN Output has a higher priority than the
CO2 Output. The CO2 stops when the FAN
output is ON. CO2 resumes operation
immediately (NO DELAY) when FAN Output
turns OFF.
The CO2 and FAN Outputs work
independently.
9
FACTORY SETTING
ALTERNATE SETTING
FAN OUTPUT
ON-DELAY
(3 alternate settings)
The FAN Output ON-DELAY (started as soon as the
high priority CO2 output turns OFF) is 10 minutes.
RESETTING THE ON_DELAY:
the ON-DELAY is reset to allow the FAN output to turn ON
immediately when CALIBRATION pushbutton is pressed during
normal operation.
The FAN Output ON-DELAY (started as soon as the
high priority CO2 output turns OFF) is either
5 minutes.
20 minutes.
30 minutes

9 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
10
FACTORY SETTING
ALTERNATE SETTING
FAN OUTPUT
FAIL STATE
The FAN Output is turned ON when a Temperature
Sensor Failure is detected, regardless of DAY and
NIGHT Temperature Setpoints.
The FAN Output is turned OFF when a Temperature
Sensor Failure is detected, regardless of DAY and
NIGHT Temperature Setpoints.
11
FACTORY SETTING
ALTERNATE SETTING
AUX FAN
OUTPUT
FAIL STATE
The AUX FAN Output (optional OB1-V) follows the
regular FAN Output (ON or OFF) in the event of a
Temperature Sensor Failure, regardless of DAY and
NIGHT Temperature Setpoints.
The AUX FAN Output (optional OB1-V) sets the
OB1-V at IDLE SPEED in the event of a Temperature
Sensor Failure, regardless of DAY and NIGHT
Temperature Setpoints. IDLE SPEED value is set
directly on OB1-V module through an adjustment on
the side of the enclosure.
ACCESSING THE FACTORY / ALTERNATE SETTING EDIT MODE
Step 1- Follow the procedure to enter CO2 Sensor Calibration...
Day Enrichment Knob to CAL
Lock/Unlock Slide Switch to UNLOCK
HOLD pushbutton
...BUT YOU HAVE TO ABORT the Calibration AFTER 5 SECONDS (one blink per second)
by moving the Slide Switch back to the LOCK position. Then let the pushbutton go.
Step 2 - You are now given access to the FACTORY / ALTERNATE SETTING EDIT MODE.
TO EXIT this mode, simply return the Slide Switch to UNLOCK position.
Step 3 - The 11 settings that can be changed are grouped in 3 different PARAMETERS.
One PARAMETER can include up to 6 settings. Make sure to select the right PARAMETER from
these 3 choices.
SETTING NAME
PARAMETER NAME
1
CO2 Elevation
CO2 ELEVATION
2
Fan Output Control Range (also called Differential)
OUTPUT CONTROL
3
Humidity Output Control Range (also called Differential)
4
CO2 Output Control Range (also called Differential)
5
Aux Heater Output Control Range (also called Differential)
6
LOW TEMPERATURE LIMIT
7
HIGH TEMPERATURE LIMIT
8
Fan And CO2 Outputs PRIORITY MANAGEMENT
PRIORITY AND FAIL
9
Fan Output ON-DELAY
10
Fan Output FAIL STATE
11
AUX Fan Output FAIL STATE (optional)

10 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
Step 4 - Understanding the FACTORY / ALTERNATE SETTING EDIT MODE
In this mode, the KNOBS and LED INDICATORS take other meanings:
Day Temperature Knob: to select the PARAMETER (among 3).
Temperature Indicators: to indicate the selected PARAMETER.
Pushbutton: to select the right setting (up to 6 settings per PARAMETER)
Day Humidity Knob: to change the setting values.
Humidity and CO2 Indicators (A to F): to indicate the setting values.
Changing the CO2 ELEVATION PARAMETER
Turn the SELECT knob (Day Temperature) to position 1. The top PARAMETER indicator will lit.
CLICK the Pushbutton to select the VALUE Indicator (A to F) you need to turn ON (Lit) or OFF.
Rotate the SET/RESET knob (Humidity Temperature) to turn ON/OFF the selected indicator (selected
indicator is flashing; flashing will stop once value has been set or reset).
To EXIT and SAVE, make sure to move through all 6 indicators. Successful saving will blink the VALUE
indicators 4 times.
Indicator Name
Effect
Indicator Name
Add 500 ft
Add 500 ft to Sea Level if Indicator is Lit
Add 4000 ft
Add 4000 ft to Sea Level if Indicator is Lit
Add 1000 ft
Add 1000 ft to Sea Level if Indicator is Lit
Add 8000 ft
Add 8000 ft to Sea Level if Indicator is Lit
Add 2000 ft
Add 2000 ft to Sea Level if Indicator is Lit
Ex. Elevation has been set to 5000 ft, valid for Denver Colorado area.

11 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
Changing the OUTPUT CONTROL PARAMETER
Turn the SELECT knob (Day Temperature) to position 2. The two top PARAMETER indicators will lit.
CLICK the Pushbutton to select the VALUE Indicator (A to F) you need to turn ON (Lit) or OFF.
Rotate the SET/RESET knob (Humidity Temperature) to turn ON/OFF the selected indicator (selected
indicator is flashing; flashing will stop once value has been set or reset).
To EXIT and SAVE, make sure to move through all 6 indicators. Successful saving will blink the VALUE
indicators 4 times.
Indicator Name
Effect on Settings
(Factory Setting in Bold)
Indicator Name
Effect on Settings
(Indicator OFF is Factory Setting)
COOL
Control Range
Indicator is Off : +/- 2°F around setpoint
Indicator is Lit : +/- 4°F around setpoint
HEAT
Control Range
Indicator is Off :
Fixed range, -8°F to -2°F below setpoint
Indicator is Lit:
Auto range, -8°F to -2°F OR -12°F to -6°F below
setpoint to avoid competing equipment to operate
simultaneously
HUMIDITY
Control Range
Indicator is Off : +/- 2% around setpoint
Indicator is Lit : +/- 4% around setpoint
CO2
Control Range
Indicator is Off : +0 / - 200 ppm below setpoint
Indicator is Lit : +0 / - 400 ppm below setpoint
Low Temp
Limit
Indicator is Off : -6°F below setpoint
Indicator is Lit : -10°F below setpoint
High Temp
Limit
Indicator is Off : +10°F above setpoint
Indicator is Lit : 90°F regardless of setpoint
Ex. COOL, HUMIDITY and CO2 Control Ranges have been set to alternate settings.

12 of 12
Grozone SCC1 Advanced User Guide –January 2012 www.grozonecontrol.com
Changing the PRIORITY AND FAIL PARAMETER
Turn the SELECT knob (Day Temperature) to position 3. The three PARAMETER indicators will lit.
CLICK the Pushbutton to select the VALUE Indicator (A to F) you need to turn ON (Lit) or OFF.
Rotate the SET/RESET knob (Humidity Temperature) to turn ON/OFF the selected indicator (selected
indicator is flashing; flashing will stop once value has been set or reset).
To EXIT and SAVE, make sure to move through all 6 indicators. Successful saving will blink the VALUE
indicators 4 times.
Ex. for FAN having priority over CO2 and FAN Fail State to OFF.
Indicator Name
Effect on Settings (Factory Setting in Bold)
FAN/CO2 (1)
and
FAN/CO2 (2)
FAN/CO2 (1)
FAN/CO2 (2)
OFF
OFF
The CO2 Output has a higher priority than the FAN Output. The FAN stops when the CO2 output is ON.
FAN resumes operation following a ON-DELAY when CO2 Output turns OFF.
OFF
ON
The CO2 Output has a higher priority than the FAN Output. The FAN stops when the CO2 output is ON. FAN
resumes operation immediately (NO DELAY) when CO2 Output turns OFF.
ON
OFF
The FAN Output has a higher priority than the CO2 Output. The CO2 stops when the FAN output is ON. CO2
resumes operation immediately (NO DELAY) when FAN Output turns OFF.
ON
ON
The CO2 and FAN Outputs work independently (no priority).
ON DELAY (1)
and
FAN/CO2 (2)
ON DELAY (1)
ON DELAY (2)
OFF
OFF
10 MINUTES
OFF
ON
5 MINUTES
ON
OFF
20 MINUTES
ON
ON
30 MINUTES
AUX FAN
FAIL STATE
and
FAN
FAIL STATE
when the
temperature
sensor fails.
AUX FAN FAIL STATE
FAN FAIL STATE
OFF
OFF
AUX FAN FAIL STATE is similar to
FAN FAIL STATE
(either ON or OFF)
FAN FAIL STATE is “ON at all times”
ON
ON
AUX FAN FAIL STATE is IDLE SPEED
FAN FAIL STATE is “OFF at all times”
End of Document
This manual suits for next models
1
Table of contents
Other Grozone Control Controllers manuals

Grozone Control
Grozone Control CO2D User manual

Grozone Control
Grozone Control HT2 User manual

Grozone Control
Grozone Control Temp-3 User manual

Grozone Control
Grozone Control SCO2 User manual

Grozone Control
Grozone Control TV12 User manual

Grozone Control
Grozone Control TV2 User manual

Grozone Control
Grozone Control TV2 User manual

Grozone Control
Grozone Control SCO2 User manual

Grozone Control
Grozone Control Dual Zone CO2 Controller User manual

Grozone Control
Grozone Control SCC1 User manual