190797-YAD / 190797M-YAD
TUSCAN UNIVERSAL CONTROLLER
INSTALLATION GUIDE
At the time of writing, this Installation &. Commissioning Guide accurately describes
the product. However, in the course of development of our products we may make
changes without notification.
Honeywell shall not be liable forerrorsorforincidental orconsequential
damages, directly or indirectly, in connection with the furnishing, performance or
misuse of this product or document.
All Installation andCommissioning workon Honeywell equipmentshouldbe
carried out by suitably qualified personnel only.
Normal safety precautions and good working practice should be observed, to prevent
damage or injury at all times.
We welcome comments about our products and documentation.
Contact us at :
Honeywell
Cooling & Refrigeration
Newhouse Industrial Estate
Motherwell ML1 5SB
Scotland
U.K.
Tel:+44 (0) 1698 481698
Fax: +44 (0) 1698 481699
www.honeywell.com/cooling
Copyright© Honeywell Control Systems. All rightsreserved.
Universal Controller - YAD
Generic
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P6) Logging
(P5) Honeycomb
(P4) Evaporator out
(P3) Evaporator in
(P2) Air off
(P1) Air on
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
Defrost
Fans
only Case
off Normal
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Fans
Suction line
valve
N/C Liquid line valve
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1 YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2) Position of probes should be in accordance
with case manufacturers instructions
10k 5k
Case lights /
blinds
Alarm wired to Relay 5 N/C
contact if bit switch 3 is ON
If gas defrost is
required, connect
N/C S.G.V. to
Relay 3 N/C contact
Defrost Heater
ZA-10002-YAD
Issue a : 5/11/96
Product Part No:
• Universal Controller 190797-YAD
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Features:
• Controls and monitors HT and LT Generic case
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 switches lights 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
Generic case option 6
7
LT Range (Frozen Food)
8
HT Range (Fresh Food)
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for
incidental or consequential damages in connection
with the furnishing, performance or use of this
product or document.
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT) Dsgn Act.
Cut in Temperature 0-49 to 30 / °C 0 (-20)
Differential Below 10 to 30 / °C 1.5 (2)
Control Weight 20 to 100 / % 50
Display Weight 30 to 100 / % 50
Log Probe: 0=Off ; 1=Product ;
2=Alarm ; 3=Prod/Alm 80 to 3 0
OT Alarm 5-49 to 60 / °C 5 (-16)
UT Alarm 4-49 to 60 / °C -2 (-25)
Alarm Delay 600:00 to 99:00/Min:Sec 20:00
Defrost Start 11 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 12 0 to 6 6
No Defrost Time 27 0 to 25 / Hrs. 7
Log OT Alarm 10 -49 to 60 / °C 5 (-15)
Log UT Alarm 9-49 to 60 / °C 0 (-25)
Latch Alarm: 0=Off ; 1=On 70 to 1 0
Gas Defrost Detect 13 0 to 30 / °C 18
Defrost Terminate Temperature 14 -49 to 30 / °C 10 (14)
Defrost Minimum Time 15 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 16 00:00 to 99:00/Min:Sec 24:00
(25:00)
Drain Down Time 17 00:00 to 20:00/Min:Sec 01:30
Defrost Min. Recovery Time 18 00:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 19 00:00 to 99:00/Min:Sec 30:00
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas 22 0 to 2 0
Defrost Alarm Temp. 23 -49 to 60 / °C 20
Defrost Mode: 0=Local ;
1=Remote 24 0 to 1 0
Defrost Hold: 0=Off ; 1=On 26 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 25 0 to 1 0
Pump Down 1 20 00:00 to 07:00/Min:Sec 00:00
Pump Down 2 21 00:00 to 07:00/Min:Sec 00:00
Hour 28 0 to 23
Minute 29 0 to 59
Day 30 0 to 31
Month 31 0 to 12
Year 32 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 33 0 to 2 0
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
34 0 to 3 0
Polarity: 0=N/O ; 1=N/C 35 0 to 1 0
Sunday (Blinds) Up / Down 36/37 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday Up / Down 38/39 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday Up / Down 40/41 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday Up / Down 42/43 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday Up / Down 44/45 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday Up / Down 46/47 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday Up / Down 48/49 00:00 to 23:59/Hrs:Mins 08:00/20:00
Energy Saving: 0=Off ; 1=On 50 0 to 1 0
Entry Diff. 51 -49 to 60 / °C 4
Exit Diff. 52 -49 to 60 / °C 8
Exit Time 53 00:00 to 20:00/Min:Sec 00:30
Cycle Temp. 54 -49 to 60 / °C 5
Fan Diff. 55 0 to 60 / °C 4
Run on Time 56 00:00 to 20:00/Min:Sec 05:00
Def. Term. 57 -49 to 30 / °C 14
Gas Alarm: 0=Off ; 1=On 58 0 to 1 0
Minor Leak 59 0 to 3500 / ppm. 50
Major Leak 60 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08g / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
Generic
ZA-10002-YAD
Issue a : 5/11/96
Universal Controller - YAD
Coldroom
ZA-10003-YAD
Issue a : 5/11/96
Product Part No:
• Universal Controller 190797-YAD
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Features:
• Controls and monitors HT and LT Coldroom
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 -Remote 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
Coldroom option 6
7
LT Range (Frozen Food)
8
HT Range (Fresh Food)
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for
incidental or consequential damages in connection
with the furnishing, performance or use of this
product or document.
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P6) Logging
(P5) Defrost terminate
(P4) Evaporator out
(P3) Evaporator in
(P2) Air off
(P1) Air on
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Alarm or controlled remotely
by the Supervisor
Fans
Defrost heater / Drip Pan Heater
Suction line
valve
N/C Liquid line valve
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1
YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2)
Position of probes should be in accordance
with coil manufacturers instructions
Defrost
Door
open
Closed
5k
If gas defrost is
required, connect N/C S.G.V. to
Relay 3 N/C contact
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT) Dsgn. Act.
Cut in Temperature 0-49 to 30 / °C 0 (-20)
Differential Below 10 to 30 / °C 1.5 (2)
Control Weight 20 to 100 / % 50
Display Weight 30 to 100 / % 50
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod/Alm
80 to 3 0
OT Alarm 5-49 to 60 / °C 5 (-16)
UT Alarm 4-49 to 60 / °C -2 (-25)
Alarm Delay 600:00 to 99:00/Min:Sec 20:00
Log OT Alarm 10 -49 to 60 / °C 5 (-15)
Log UT Alarm 9-49 to 60 / °C 0 (-25)
Latch Alarm: 0=Off ; 1=On 70 to 1 0
Defrost Start 11 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 12 0 to 6 6
No Defrost Time 13 0 to 25 / Hrs. 7
Gas Defrost Detect 14 0 to 30 / °C 18
Defrost Terminate Temperature 15 -49 to 30 / °C 10 (14)
Defrost Minimum Time 16 00:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 17 00:00 to 99:00/Min:Sec 24:00
(25:00)
Drain Down Time 18 00:00 to 20:00/Min:Sec 01:30
Defrost Min. Recovery Time 19 00:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 20 00:00 to 99:00/Min:Sec 30:00
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas 23 0 to 2 0
Pump Down 1 21 00:00 to 07:00/Min:Sec 00:00
Pump Down 2 22 00:00 to 07:00/Min:Sec 00:00
Defrost Alarm Temp. 24 -49 to 60 / °C 20
Defrost Mode: 0=Local ;
1=Remote 25 0 to 1 0
Defrost Hold: 0=Off ; 1=On 26 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 27 0 to 1 0
Hour 28 0 to 23
Minute 29 0 to 59
Day 30 0 to 31
Month 31 0 to 12
Year 32 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 33 0 to 2 0
Door Alarm Delay 34 00:00 to 99:00/Min:Sec 20:00
Drip Pan Heater: 0=Off ; 1=On 35 0 to 1 0
Fans Off when Door Open: 0=Off
1=On 36 0 to 1 0
Liquid Line Closed when Door
Open: 0=Off ; 1=On 37 0 to 1 0
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08c / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
Coldroom
ZA-10003-YAD
Issue a : 5/11/96
Universal Controller - YAD
3 Range
ZA-10004-YAD
Issue a : 5/11/96
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 switches lights 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
3 Range case option 6
7
LT Range (Frozen Food)
8
HT Range (Fresh Food)
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P6) Logging
(P5) Honeycomb
(P4) Evaporator out
(P3) Evaporator in
(P2) Air off
(P1) Air on
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
Defrost
Fans
only Case
off Normal
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Fans
Suction line
valve
N/C Liquid line valve
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1 YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2) Position of probes should be in accordance
with case manufacturers instructions
10k 5k
Case lights /
blinds
Alarm wired to Relay 5 N/C
contact if bit switch 3 is ON
If gas defrost is
required, connect
N/C S.G.V. to
Relay 3 N/C contact
Defrost Heater
Product Part No:
• Universal Controller 190797-YAD
Features:
• Controls and monitors HT and LT 3 Range case
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for incidental or
consequential damages in connection with the
furnishing, performance or use of this product or
document.
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT) Dsgn. Act.
Red Cycle Temperature 01 to 7 (-49 to 60) / °C 4 (-22)
Red OT Alarm Temp. 27 to 10 (-49 to 60) / °C 8 (-15)
Red UT Alarm Temp. 1-3 to 4 (-49 to 60) / °C 2 (-30)
Yellow Cycle Temperature 3-1 to4 (-49 to 60) / °C 1 (-22)
Yellow OT Alarm Temp. 54 to 7 (-49 to 60) / °C 5 (-15)
Yellow UT Alarm Temp. 4-6 to 1 (-49 to 60) / °C -1 (-30)
White Cycle Temperature 64 to 12 (-49 to 60) /°C 8 (-22)
White OT Alarm Temp. 811 to 14 (-49 to 60) / °C 12 (-15)
White UT Alarm Temp. 71 to 6 (-49 to 60) / °C 4 (-30)
Red Log OT Alarm 15 8 to 10 (-49 to 60) / °C 8(-15)
Red Log UT Alarm 14 -1 to 4 (-49 to 60) / °C 2(-25)
Yellow Log OT Alarm 17 5 to 7 (-49 to 60) / °C 5(-15)
Yellow Log UT Alarm 16 -2 to 1 (-49 to 60) / °C 0(-25)
White Log OT Alarm 19 12 to 14 (-49 to 60) / °C 12(-15)
White Log UT Alarm 18 3 to 7 (-49 to 60) / °C 4(-25)
Cycle Differential 10 0.5 to 4 / °C 1.5(2.0)
Case Type: 0=Red ; 1=Yellow ;
2=White 90 to 2 0
Alarm Delay Fixed / Min:Sec 05:00 (10:00)
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
13 0 to 3 0
Control Weight 11 0 to 100 / % 50
Display Weight 12 0 to 100 / % 50
Defrost Start 21 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 22 0 to 6 6
No Defrost Time 23 0 to 25 / Hrs. 7
Gas Defrost Detect 24 10 to 30 / °C 18.0
Defrost Minimum Time 26 00:00 to 05:00/Min:Sec 05:00
Defrost Maximum Time 27 00:00 to 26:00/Min:Sec 24:00 (25:00)
Defrost Terminate Temperature 25 6 to 14 / °C 10 (14)
Drain Down Time 28 00:00 to 03:00/Min:Sec 01:30
Defrost Min.Recovery Time 29 00:00 to 35:00/Min:Sec 20:00
Defrost Max.Recovery Time 30 15:00 to 35:00/Min:Sec 30:00
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas 35 0 to 2 0
Pump Down 1 31 00:00 to 07:00/Min:Sec 00:00
Pump Down 2 32 00:00 to 07:00/Min:Sec 00:00
Defrost Alarm Temp. 33 -49 to 60 / °C 20
Defrost Mode:0=Local;1=Remote 34 0 to 1 0
Defrost Hold: 0=Off ; 1=On 36 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 37 0 to 1 0
Hour 38 0 to 23
Minute 39 0 to 59
Day 40 0 to 31
Month 41 0 to 12
Year 42 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 43 0 to 2 0
Lights/Blind: 0=Local ;1=Remote
; 2=Man.Off ; 3=Man.On 44 0 to 3 0
Polarity: 0=N/O ; 1=N/C 45 0 to 1 0
Alarm Latch: 0=Off ; 1=On 20 0 to 1 0
Sunday (Blinds) Up / Down 46/47 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday (Blinds) Up / Down 48/49 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday (Blinds) Up / Down 50/51 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday (Blinds) Up / Down 52/53 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday (Blinds) Up / Down 54/55 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday (Blinds) Up / Down 56/57 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday (Blinds) Up / Down 58/59 00:00 to 23:59/Hrs:Mins 08:00/20:00
Energy Saving: 0=Off ; 1=On 60 0 to 1 0
Entry Diff. 61 -49 to 60 / °C 4
Exit Diff. 62 -49 to 60 / °C 8
Exit Tme 63 00:00 to 20:00/Min:Sec 00:30
Cycle Temp. 64 -49 to 60 / °C 5
Fan Diff. 65 0 to 60 / °C 4
Run on Time 66 00:00 to 20:00/Min:Sec 05:00
Def. Term. 67 -49 to 30 / °C 14
Gas Alarm: 0=Off ; 1=On 68 0 to 1 0
Minor Leak 69 0 to 3500 / ppm. 50
Major Leak 70 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08y / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:............................................
Controller
Name:
Designer:.....................................
Date:............................................
Engineer:......................................
Date:.............................................
Comments:
Universal Controller -
3 Range
ZA-10004-YAD
Issue a : 5/11/96
Universal Controller - YAD
Dyadic
ZA-10005-YAD
Issue a :5/11/96
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 switches lights 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
Dyadic case option 6
7
Not used....leave off
8
Not used....leave off
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P6) Logging
(P5) Honeycomb
(P4) Evaporator out
(P3) Evaporator in
(P2) Air off
(P1) Air on
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
Defrost
Fans
only Case
off Normal
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Fans
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1 YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2) Position of probes should be in accordance
with case manufacturers instructions
10k 5k
Compressor B
Compressor A
Defrost heater
Case lights /
blinds
Alarm wired to Relay 5 N/C
contact if bit switch 3 is ON
Product Part No:
• Universal Controller 190797-YAD
Features:
• Controls and monitors Dyadic case
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for incidental or
consequential damages in connection with the
furnishing, performance or use of this product or
document.
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
Setting Dsg
n. Act.
Red Cycle Temperature 01 to 7 / °C 4
Red OT Alarm Temp. 27 to 10 / °C 8
Red UT Alarm Temp. 1-3 to 4 / °C 2
Defrost Type:0=Elect.;1=Off Cyc. 30 to 1 0
Yellow Cycle Temperature 4-1 to 4 / °C 1
Yellow OT Alarm Temp. 64 to 7 / °C 5
Yellow UT Alarm Temp. 5-6 to 1 / °C -1
Defrost Type:0=Elect.;1=Off Cyc. 70 to 1 0
White Cycle Temperature 84 to 12 / °C 8
White OT Alarm Temp. 10 11 to 14 / °C 12
White UT Alarm Temp. 91 to 6 / °C 4
Defrost Type:0=Elect.;1=Off Cyc. 11 0 to 1 1
Red Log OT Alarm 20 8 to 10 / °C 8
Red Log UT Alarm 19 -1 to 4 / °C 2
Yellow Log OT Alarm 22 5 to 7 / °C 5
Yellow Log UT Alarm 21 -2 to 1 / °C 0
White Log OT Alarm 24 12 to 14 / °C 12
White Log UT Alarm 23 3 to 7 / °C 4
Lead Cyc. Diff 12 0 to 30 / °C 1.5
Lag. Cut In 13 0 to 3 / °C 1
Lag Cut Out 14 0 to 3 / °C 1
Case Type: 0=Red ; 1=Yellow ;
2=White 16 0 to 2 0
Control Weight 15 0 to 100 / % 50
Display Weight 16 0 to 100 / % 50
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
18 0 to 3 0
Off Cycle Defrost Max.Temp. 30 -49 to 60 / °C 10
Off Cycle Defrost Minimum Time 28 00:00 to 99:00/Min:Sec 05:00
Off Cycle Defrost Maximum Time 29 00:00 to 99:00/Min:Sec 24:00
Electric Defrost Max. Temp. 33 -49 to 60 / °C 10
Electric Defrost Minimum Time 31 00:00 to 99:00/Min:Sec 05:00
Electric Defrost Maximum Time 32 00:00 to 99:00/Min:Sec 24:00
Defrost Start 26 00:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 27 0 to 6 6
No Defrost Time 41 0 to 25/ Hrs. 7
Alarm Delay Fixed / Min:Sec 05:00
Drain Down Time 34 00:00 to 03:00/Min:Sec 01:30
Defrost Min. Recovery Time 35 00:00 to 35:00/Min:Sec 20:00
Defrost Max. Recovery Time 36 15:00 to 35:00/Min:Sec 30:00
Defrost Alarm Temp. 37 -49 to 60 / °C 20
Defrost Mode: 0=Local ;
1=Remote 38 0 to 1 0
Defrost Hold: 0=Off ; 1=On 40 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 39 0 to 1 0
Hour 42 0 to 23
Minute 43 0 to 59
Day 44 0 to 31
Month 45 0 to 12
Year 46 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 47 0 to 2 0
Lights/Blind: 0=Local ; 1=Remote
; 2=Man.Off ; 3=Man.On 48 0 to 3 0
Polarity: 0=N/O ; 1=N/C 49 0 to 1 0
Latch Alarm: 0=Off ; 1=On 25 0 to 1 0
Sunday (Blinds) Up / Down 50/51 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday (Blinds) Up / Down 52/53 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday (Blinds) Up / Down 54/55 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday (Blinds) Up / Down 56/57 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday (Blinds) Up / Down 58/59 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday (Blinds) Up / Down 60/61 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday (Blinds) Up / Down 62/63 00:00 to 23:59/Hrs:Mins 08:00/20:00
Gas Alarm: 0=Off ; 1=On 64 0 to 1 0
Minor Leak 65 0 to 3500 / ppm. 50
Major Leak 66 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08d / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:............................................
Controller
Name:
Designer:.....................................
Date:............................................
Engineer:......................................
Date:.............................................
Comments:
Universal Controller -
Dyadic
ZA-10005-YAD
Issue a : 5/11/96
Universal Controller - YAD
3 Section
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P6) Air off - Section 3
(P5) Air on - Section 3
(P4) Air off - Section 2
(P3) Air on - Section 2
(P2) Air off - Section 1
(P1) Air on - Section 1
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
Defrost
Fans
only Case
off Normal
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Suction line
valve 1
N/C Liquid line valve
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1
YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2)
Position of probes should be in accordance
with case manufacturers instructions
10k 5k
Suction line
valve 2
Suction line
valve 3
*
*
*If Electric Defrost Heater is
required, connect to N/O
contact
*
Case lights /
blinds
Alarm wired to Relay 5 N/C
contact if bit switch 3 is ON
ZA-10006-YAD
Issue a : 5/11/96
Product Part No:
• Universal Controller 190797-YAD
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Features:
• Controls and monitors HT and LT 3 Section case
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 switches lights 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
3 Section case option 6
7
LT Range (Frozen Food)
8
HT Range (Fresh Food)
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for
incidental or consequential damages in connection
with the furnishing, performance or use of this
product or document.
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT) Dsgn Act.
Cut in Temperature 0-49 to 30 / °C 0 (-20)
Differential Below 10 to 30 / °C 1.5 (2)
Control Weight 20 to 100 / % 50
Display Weight 30 to 100 / % 50
Section 1: OT Alarm 44 -49 to 60 / °C 5 (-16)
Section 1: UT Alarm 45 -49 to 60 / °C -2 (-25)
Section 2: OT Alarm 47 -49 to 60 / °C 5 (-16)
Section 2: UT Alarm 48 -49 to 60 / °C -2 (-25)
Section 3: OT Alarm 50 -49 to 60 / °C 5 (-16)
Section 3: UT Alarm 51 -49 to 60 / °C -2 (-25)
Alarm Delay 17 00:00 to 99:00/Min:Sec 20:00
Latch Alarm: 0=Off ; 1=On 18 0 to 1 0
Defrost Start 400:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 50 to 6 6
No Defrost Time 60 to 25 / Hrs. 7
Section 1: Defrost Term. Temp. 46 -49 to 60 / °C 10
Section 2: Defrost Term. Temp. 49 -49 to 60 / °C 10
Section 3: Defrost Term. Temp. 52 -49 to 60 / °C 10
Defrost Minimum Time 700:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 800:00 to 99:00/Min:Sec 24:00
(25:00)
Defrost Min. Recovery Time 900:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 10 00:00 to 99:00/Min:Sec 30:00
Drain Down Time 11 00:00 to 20:00/Min:Sec 01:30
Defrost Alarm Temp. 12 -49 to 60 / °C 20
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas 13 0 to 2 0
Defrost Mode: 0=Local ;
1=Remote 14 0 to 1 0
Defrost Hold: 0=Off ; 1=On 15 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 16 0 to 1 0
Hour 19 0 to 23
Minute 20 0 to 59
Day 21 0 to 31
Month 22 0 to 12
Year 23 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 24 0 to 2 0
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
25 0 to 3 0
Polarity: 0=N/O ; 1=N/C 26 0 to 1 0
Sunday (Blinds) Up / Down 27/28 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday Up / Down 29/30 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday Up / Down 31/32 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday Up / Down 33/34 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday Up / Down 35/36 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday Up / Down 37/38 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday Up / Down 39/40 00:00 to 23:59/Hrs:Mins 08:00/20:00
Gas Alarm: 0=Off ; 1=On 41 0 to 1 0
Minor Leak 42 0 to 3500 / ppm. 50
Major Leak 43 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08t / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
3 Section
ZA-10006-YAD
Issue a : 5/11/96
Universal Controller - YAD
2 Section
Relay
1
Relay
2
Relay
3
Relay
4
Relay
5
Note: This simplified wiring diagram omits circuit protection
ON 1
2
3
4
5
6
7
8
(P4) Air off - Section 2
(P3) Air on - Section 2
(P2) Air off - Section 1
(P1) Air on - Section 1
Temperature Probes -
Bit switches
+
OPTIONS EXECUTE
PAGE
PAGE HOME
SELECT
Setup
Unit
Previous
controller Next
controller
Genus or alternative
Network cable
-1.5
Ent Esc
Alarm
Network
Defrost
Defrost
Fans
only Case
off Normal
white
green
red
Plant fault 2
Plant fault 1
N
L
E
Mains
Supply
DIN Box Display
Suction line
valve 1
N/C Liquid line valve
Setup unit extension cable
screen
red
white
black
green
blue
green
yellow
white
red
CN7
CN8
P2
P1
CN9
CN10
CN11
CN12
CN13
CN14
CN15
CN5
CN6
CN4
CN3
CN2
CN1
YAD
Controller on a
Genus Network
screen
white
black
CN7
Controller on a
Woodley Network
Controller
(Fig. 2)
Position of probes should be in accordance
with case manufacturers instructions
10k 5k
Suction line
valve 2
*
If Electric Defrost Heater is
required, connect to N/O
contact
*
*
Case lights /
blinds
Alarm wired to Relay 5 N/C
contact if bit switch 3 is ON
ZA-10053-YAD
Issue a : 5/11/96
Product Part No:
• Universal Controller 190797-YAD
Warning !
Before you work on this equipment, isolate the
electrical supply and also the live feed to any
incoming signals. Remember that live signals
may be derived from more than one source.
Features:
• Controls and monitors HT and LT 2 Section case
• Genus or alternative network compatible
• Full defrost control
Associated Documents:
∗ Datasheet: ZD 10001-YAD
∗ DIN Box Display: ZF 0920-DIN
∗ Set-up Unit: ZF 0795-DAD
∗ Using Probe Clips: ZG 56003
∗ Health and Safety: ZG 1056
Bit Switch Settings (Fig. 1) : (Shaded area = Switch Position)
Off On
Genus Network 1Alternative Network
Elm Probes 2Alternative Probes
Relay 5 switches lights 3Relay 5 Switches Alarm
Not used....leave off 4Not used....leave off
5
2 Section case option 6
7
LT Range (Frozen Food)
8
HT Range (Fresh Food)
Please Note:
The features and specifications contained in this
Installation Guide may change without notice.
Elm Ltd. shall not be liable for errors or for
incidental or consequential damages in connection
with the furnishing, performance or use of this
product or document.
Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is
YAD.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display
or controller (Fig. 2).
6. Check / Set operating parameters - see
list
7. Save values - if changed
8. Log the controller on to the network then
verify settings on Genus InTouch panel,
Set-up Unit or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
• If the red LED beside the display
connector is ON or flashing, then the
controller is faulty.
You cannot log the controller on to
the network.
• There may be a controller with the same
name, already logged on the network.
• There may be a maximum 32 controllers
already on the network segment.
• Check on the InTouch panel, P.C. or
Supervisor.
Parameter DIN Range/Units Default
HT(LT) Dsgn Act.
Cut in Temperature 0-49 to 30 / °C 0 (-20)
Differential Below 10 to 30 / °C 1.5 (2)
Control Weight 20 to 100 / % 50
Display Weight 30 to 100 / % 50
Section 1: OT Alarm 44 -49 to 60 / °C 5 (-16)
Section 1: UT Alarm 45 -49 to 60 / °C -2 (-25)
Section 2: OT Alarm 47 -49 to 60 / °C 5 (-16)
Section 2: UT Alarm 48 -49 to 60 / °C -2 (-25)
Alarm Delay 17 00:00 to 99:00/Min:Sec 20:00
Latch Alarm: 0=Off ; 1=On 18 0 to 1 0
Defrost Start 400:00 to 23:59/Hrs:Mins 01:00
Number of Defrosts per Day 50 to 6 6
No Defrost Time 60 to 25 / Hrs. 7
Section 1: Defrost Term. Temp. 46 -49 to 60 / °C 10
Section 2: Defrost Term. Temp. 49 -49 to 60 / °C 10
Defrost Minimum Time 700:00 to 99:00/Min:Sec 05:00
Defrost Maximum Time 800:00 to 99:00/Min:Sec 24:00
(25:00)
Defrost Min. Recovery Time 900:00 to 99:00/Min:Sec 20:00
Defrost Max. Recovery Time 10 00:00 to 99:00/Min:Sec 30:00
Drain Down Time 11 00:00 to 20:00/Min:Sec 01:30
Defrost Alarm Temp. 12 -49 to 60 / °C 20
Defrost Type: 0=Elect.;1= (2)Gas
2=(3)Gas 13 0 to 2 0
Defrost Mode: 0=Local ;
1=Remote 14 0 to 1 0
Defrost Hold: 0=Off ; 1=On 15 0 to 1 0
Pulse Defrost: 0=Off ; 1=On 16 0 to 1 0
Hour 19 0 to 23
Minute 20 0 to 59
Day 21 0 to 31
Month 22 0 to 12
Year 23 0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On 24 0 to 2 0
Lights/Blinds: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
25 0 to 3 0
Polarity: 0=N/O ; 1=N/C 26 0 to 1 0
Sunday (Blinds) Up / Down 27/28 00:00 to 23:59/Hrs:Mins 08:00/20:00
Monday Up / Down 29/30 00:00 to 23:59/Hrs:Mins 08:00/20:00
Tuesday Up / Down 31/32 00:00 to 23:59/Hrs:Mins 08:00/20:00
Wednesday Up / Down 33/34 00:00 to 23:59/Hrs:Mins 08:00/20:00
Thursday Up / Down 35/36 00:00 to 23:59/Hrs:Mins 08:00/20:00
Friday Up / Down 37/38 00:00 to 23:59/Hrs:Mins 08:00/20:00
Saturday Up / Down 39/40 00:00 to 23:59/Hrs:Mins 08:00/20:00
Gas Alarm: 0=Off ; 1=On 41 0 to 1 0
Minor Leak 42 0 to 3500 / ppm. 50
Major Leak 43 0 to 3500 / ppm. 200
Manual Defrost: 0=Off ; 1=On 99 0 to 1 0
YAD08t / 65EAEE
Display Alarm Messages:
AL Temperature alarm
Ft Probes 1 and 2 are faulty
LA Log probe alarm
Pn probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE EEPROM fault
rr Internal program fault
E1 Plant fault 1
E2 Plant fault 2
ES
Energy-Saving Mode
Store:.............................................
Controller
Name:
Designer:........................................
Date:..............................................
Engineer:........................................
Date:..............................................
Comments:
Universal Controller -
2 Section
ZA-10053-YAD
Issue a : 5/11/96

This manual suits for next models

1

Other Honeywell Controllers manuals

Honeywell rm7890a User manual

Honeywell

Honeywell rm7890a User manual

Honeywell PP904A User manual

Honeywell

Honeywell PP904A User manual

Honeywell 023350.17 Instruction manual

Honeywell

Honeywell 023350.17 Instruction manual

Honeywell PCR-310 User manual

Honeywell

Honeywell PCR-310 User manual

Honeywell ML6174 Series User manual

Honeywell

Honeywell ML6174 Series User manual

Honeywell CN05 Series User manual

Honeywell

Honeywell CN05 Series User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell AQUASTAT L4188A User manual

Honeywell

Honeywell AQUASTAT L4188A User manual

Honeywell NPB-2X-RS485 User manual

Honeywell

Honeywell NPB-2X-RS485 User manual

Honeywell HR 40 User manual

Honeywell

Honeywell HR 40 User manual

Honeywell ML4125 Operation manual

Honeywell

Honeywell ML4125 Operation manual

Honeywell T775A User manual

Honeywell

Honeywell T775A User manual

Honeywell Elster Jeavons J125 User manual

Honeywell

Honeywell Elster Jeavons J125 User manual

Honeywell LYNX Touch Series User manual

Honeywell

Honeywell LYNX Touch Series User manual

Honeywell WV8840A User manual

Honeywell

Honeywell WV8840A User manual

Honeywell M896 User manual

Honeywell

Honeywell M896 User manual

Honeywell Temaline TS2 User manual

Honeywell

Honeywell Temaline TS2 User manual

Honeywell DBC2000 Series User manual

Honeywell

Honeywell DBC2000 Series User manual

Honeywell M7061 User manual

Honeywell

Honeywell M7061 User manual

Honeywell V4055F Operation manual

Honeywell

Honeywell V4055F Operation manual

Honeywell T775U2006 User manual

Honeywell

Honeywell T775U2006 User manual

Honeywell AUTOMATIC CONTROL Installation and operation manual

Honeywell

Honeywell AUTOMATIC CONTROL Installation and operation manual

Honeywell T775 Series User guide

Honeywell

Honeywell T775 Series User guide

Honeywell T775L Series User manual

Honeywell

Honeywell T775L Series User manual

Popular Controllers manuals by other brands

Danfoss EKC 326A instructions

Danfoss

Danfoss EKC 326A instructions

GME SD-220 user manual

GME

GME SD-220 user manual

Gree XE71-42/G owner's manual

Gree

Gree XE71-42/G owner's manual

Mitsubishi Electric MELSEC L series manual

Mitsubishi Electric

Mitsubishi Electric MELSEC L series manual

Sensys Networks VDS240 installation guide

Sensys Networks

Sensys Networks VDS240 installation guide

Desoutter CVI3 Series Installation and upgrades

Desoutter

Desoutter CVI3 Series Installation and upgrades

Harman AMX JPK-1300 Hardware reference manual

Harman

Harman AMX JPK-1300 Hardware reference manual

EMKO ESM-4410 instruction manual

EMKO

EMKO ESM-4410 instruction manual

Lutz-Jesco TOPAX MC operating instructions

Lutz-Jesco

Lutz-Jesco TOPAX MC operating instructions

DEUTSCHMANN AUTOMATION LOCON 15 Series instruction manual

DEUTSCHMANN AUTOMATION

DEUTSCHMANN AUTOMATION LOCON 15 Series instruction manual

Kimo LEKTROMIK S Series product manual

Kimo

Kimo LEKTROMIK S Series product manual

GRAUPNER PS 5,9V operating manual

GRAUPNER

GRAUPNER PS 5,9V operating manual

Phoenix Contact MCR-FL-D-T-2SP-24 manual

Phoenix Contact

Phoenix Contact MCR-FL-D-T-2SP-24 manual

ABB RELION REM615 Product guide

ABB

ABB RELION REM615 Product guide

TPS SAS908X-7-DF manual

TPS

TPS SAS908X-7-DF manual

ABBA TSRPT600 installation guide

ABBA

ABBA TSRPT600 installation guide

DH Instruments GPC1-10000-AF Operation and maintenance manual

DH Instruments