Elsteam UH06-OEM Operating instructions

ULTRASONIC HUMIDIFIER
USER, INSTALLATION
AND MAINTENANCE GUIDE
Rev 12.02-EN

2
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
1 Package content.................................................................................................. 3
2 Security measures............................................................................................... 3
3 Conformity......................................................................................................... 4
4 Working principle............................................................................................... 5
5 Characteristics.................................................................................................... 5
6 Installation ......................................................................................................... 5
6.1 Components (UH06-OEM).......................................................................... 5
6.2 Hydraulic connections................................................................................. 6
6.3 Steam Output............................................................................................... 6
6.4 Electrical connections.................................................................................. 6
6.5 Connections ................................................................................................ 9
6.6 Control System............................................................................................ 9
7 Led Indications................................................................................................. 10
7.1 Normal Operations.................................................................................... 10
7.2 Tank Cleaning ........................................................................................... 10
8 Alarm Conditions..............................................................................................11
8.1 Water Failure..............................................................................................11
8.2 Draining System Failure.............................................................................11
9 Tank draining ....................................................................................................11
10 Submerged Pump 220Vac ............................................................................. 12

3
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
Please before using your equipment read this guide carefully, by noting all the precautions
and safety instructions reported in it. Keep your equipment in good operative conditions.
Familiarize with the working and security instructions related to the operation of your
apparatus before trying to make it function. Keep this guide and any other booklet provided
with your apparatus to be able to refer to them later.
1 Package content
Package contains:
Ultrasonic Humidifier
This User guide
A single-phase 220 Vac // 0-14-48 Vac transformer
A feed 220V submerged pump (optional)
2 Security measures
People who are not familiar with this type of apparatus or which did not read
carefully this guide do not have to be authorized to use the humidifier.
The humidifier is designed to be used on alternative 220Vac only. Do not try to
connect it to a different type of supply. Please ask for different supply voltage.
Check that the sector supply voltage corresponds to that of the apparatus.
Your humidifier must always be switched-off before any maintenance operations.
All operations of maintenance and repairs must be carried out by the manufacturer,
his agency or another qualified personnel to avoid any problem.
Do not cover any opening of the humidifier and do not insert objects in the
openings

4
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
3 Conformity
IL COSTRUTTORE
ELSTEAM S.r.l.
Azienda
Via Enrico Fermi, 496 21042
VA
Indirizzo Cap
Provincia
Caronno Pertusella Italy
Città Stato
DICHIARA CHE LA MACCHINA
Umidificatore ad ultrasuoni UH
Descrizione Modello
UH
2008
Serie/Matricola Anno
costr.
Umidificatore ad Ultrasuoni
Denominazione commerciale
Umidificazione di ambienti
Uso previsto
E’ conforme alle direttive comunitarie
2006/95/CEE “Direttiva Bassa Tensione” del Consiglio 27 Dicembre 2006
89/336/CEE “Compatibilità Elettromagnetica EMC” modificata da:
-Direttiva 91/263/CEE del Consiglio del 29 aprile 1991
-Direttiva 92/31/CEE del Consiglio del 28 aprile 1992
-Direttiva 93/68/CEE del Consiglio del 22 luglio 1993
-Direttiva 04/108/CEE del Consiglio del 15 dicembre 2004
Claudio Cattaneo Dirigente
Responsabile Funzione
ELSTEAM S.r.l.- Via E. Fermi 496 – 21042 – Caronno Pertusella (VA) - ITALY
Società
2012
Anno

5
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
4 Working principle
The ultrasonic humidifier is an adiabatic humidifier based on the water atomization
generated with the vibration of a piezoelectric membrane.
The ultrasonic humidifier causes the evaporation of water by generating microscopic water
drops negatively ionized. Thanks to the negative ions, the air is purified by precipitation of
the pollutants in suspension. These humidifiers are particularly quiet.
The humidifier consists of a case, an electronic control board, a draining system, a tank, a
fan with speed control and a level detector.
The microcontroller based control system performs a cleaning of the water tank at the
switch ON and every 6 operating hours.
5 Characteristics
Technical Data
UH06-OEM UH12-206 UH18-306 UH24-406
Capacity 0,6 l/h 1,2 l/h 1,8 l/h 2,4 l/h
Output (diameter) 40 mm 2 x 40mm 3 x 40mm 4 x 40mm
Frequency 1.68 MHz nominal
Electrical Data
Tension 220 Vac, 50-60Hz single phase
Power 40VA 80 VA 120 VA 160 VA
Hydraulic Data
Water pressure 0,5 - 6 bar
Inlet Connection 3/4''
Out Connection 1/4''
Mechanical Data
Dimensions [mm
]
LxWxH 85x126x240 170x126x240 255x126x240 340x126x240
Weigth [kg]
with AC Supply 1,7 2,2 2,7 3,2
6 Installation
The humidifier must be installed in a room ventilated and protected, on a vertical surface,
plane and rigid. Use the two eyelets of the case and check that the tank is in horizontal
position. For multiples units (UH206...UH406) please use at least one eyelet for each unit,
to fix humidifier, to prevent lateral forces that may cause breakage of the tank.
The mains transformer can be installed remotely.
6.1 Components (UH06-OEM)

6
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
6.2 Hydraulic connections
Hydraulic connection to the units must be realized with flexible pipes which do not cause
an action on the tank to avoid damaging the unit.
The hydraulic connections are positioned on the bottom side of the humidifier. Input
connection is 3/4" and output is 1/4”.
The minimal pressure at the entry of the pump should be lower than 0.5 at maximum flow.
6.3 Steam Output
The steam output is positioned in the upper part of the humidifier (top cover). The outlet
has a diameter of 40mm. To avoid the release of micro-droplets of water by the output
should be installed a distribution ramp of 40 cm minimum. The ramp can be made of PVC or
other material (as required by the application). In case you can not install a ramp of 40 cm
at the exit you can install a double stitched at 90° to create a trap for micro-drops.
6.4 Electrical connections
The person in charge of installation will have to ensure the following points :
Size of electrical cables must be appropriate for the maximum current being
provided.
The power supply cable will have to be protected using an appropriate cable gland.
All work concerning electrical installations WILL HAVE to be carried
out exclusively by qualified personnel (ex electricians or technicians
laying ou
t from a suitable formation). The customer IS responsible for
the adequacy of the personnel used.
Please check that power supply is disconnected before any
maintenance and installation operation.

7
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
Mains tran
sformer Connections
0V
BLUE
cable
Electronic Board
12/
14V
RED cable
Electronic Board
48
/59
V
VIOLET
cable
Electronic Board
0V
FASTON
Circuit breaker
220V
FASTON
Circuit breaker
Each connection of terminal will have to be firmly protected by a fixing of cable.
The electric terminals are positioned inside the apparatus (remove the screws which block
the lower panel of the case to reach them).
In case the mains transformer is not delivered already connected to the humidifier, please
use table below to connect.
Figure 1 shows positioning of electrical terminals on the electronic board.
Before the beginning of installation (and all operations o
f
maintenance and maintenance without panel) the power supply
must be disconnected on all the lines and insured against an
involuntary connection! Before making electric connections check
that the tension corresponds to those of the humidifier!
Figure 1 - Electronic Board
0V
220V
48V
0V
14V

8
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
N° Name Description
1,2 48Vac
AC Input 48Vac
Connect cables from mains transformer (4terminals 0 and 8Vac)
3 T GND
4,5 14Vac AC Input 14Vac
Connect cables from mains transformer (terminals 0 and 14Vac)
6 0 V External Regulator Reference Voltage
7 REG External Regulator Input Voltage (type 0 ... 10v) or enable signal
8 V+ External Regulator Power Supply (type 4 ... 20mA)
9 RTH External Regulator Input Signal(type 4...20mA)
10,11 ALRM Alarm Output
Normally opened. Closed during alarm conditions (Max. 2 A, 48 V).
12,13 REQ/
ALIM.
PUMP
Production Output.
These contacts are opened when the production is stopped. They close when
productions is required (Max. 2 A, 48 V).
If the submerged pump is used these contacts can be used to switch On/Off the pump
(Requires a different firmware)
Table 1: Electrical and Control Connections (connector#1 in Fig.1)
N° Name Description
1 Vac 48 Vac power supply for nebulizer board
2
3 In Control signal for nebulizer board
4
Table 2 : Nebulizer Board Connections (connector #2 in Fig.1)

9
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
6.5 Connections
6.6 Control System
The terminals of control and alarm signals are located on the electronic control board
(connector 1 – see Figure 1 - Electronic Board) (remove the lower panel of the case to reach
them). The openings for the cables are located on the lower side of the case. Use cables
with a section of max. 1sqmm.
The electronic controller embedded can use an external signal (from an external controller)
or internal proportional controller.
According to the operating process chosen, select suitable connection in the list.
Embedded Proportional Controller
External ON/OFF controller or Humidistat
Connect the external Controller to the
terminals REG and V+ as in the schematic
To use the embedded proportional controller
connect the humidity probe (4… 20 my) as
indicated in the schematic. The humidity
probe must be installed in the room or conduit
to be controlled.
If the enable signal is not used connect V+ et
REG
Use R13 potentiometer on the control board to
regulate the request of humidity (0% clockwise
and 100% counter-clockwise)

10
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
External PROPORTIONAL controller (0..10V)
7 Led Indications
The working operation and status of the humidifier is indicated using 4 LEDs on the front
panel.
7.1 Normal Operations
In the case of normal operation the green led (1) is lit with an intensity proportional to the
mist production. If the external or internal controller does not require mist production, the
green led (1) blinks.
In the case of absence of water (insufficient pressure or solenoid input valve failure) the
yellow (4) led light to indicate that there is no mist production.
Red led (2) and (3) must be OFF.
7.2 Tank Cleaning
The microprocessor based control system, performs automatic tank cleaning at start-up and
every 6 hours of operation. This cleaning phase allows limestone deposit to be eliminated
from the tank.
During this cleaning phase green led (1) blinks to indicate that the humidifier is working,
but not producing mist.
Tank cleaning is performed in two phases signalled by a different state of red led (2):
Water input in the tank and starting of the siphon system (red led (2) is ON)
Cleaning and draining of the tank (red led (2) is blinking)
The yellow led (4) indicates the level of water in the tank.
Connect the external Controller to the
terminals REG and 0V as in the schematic
Pos Colours Description
1 GREEN
IN OPERATION
If fixed or blinking indicates that the humidifier is
working.
2 RED
TANK CLEANING
If ON indicates the cleaning phase
3 RED
FAN FAILURE.
If ON indicates a failure on the FAN
4 YELLOW
LOW WATER LEVEL
If ON indicates low water level in the tank

11
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
8 Alarm Conditions
In case of failure the micro-controller based board stops mist production and water input.
After a wait period of 5 minutes the humidifier automatically start with tank cleaning
phase.
During the stop phase green led (1) is OFF, red led (3) could signal FAN failure; red led (2)
and yellow led (4) identify the failure.
8.1 Water Failure
This failure is signalled with yellow led (2) blinking and green led (1) OFF.
8.2 Draining System Failure
Draining system failure during tank cleaning phase. The causes of this failure can be a
problem with draining solenoid valve or an obstruction in the draining system (pipes).
This failure is signalled with red led (2) blinking and green led (1) OFF.
9 Tank draining
When the humidifier is not used is mandatory to execute a manual draining. To complete
this operation execute following steps:
1. Close input valve
2. Switch OFF the unit
3. Switch ON the unit
4. Wait until tank is empty
1. Green LED blink
2. Yellow LED is ON
5. Switch OFF the unit

12
Elsteam S.r.l - via E.fermi, 496 - 21042 Caronno Pertusella (va) - Tel.+39 02 9659890 - Fax +39 02 96457007
E-mail: infocomm@elsteam.com/infotech@elsteam.com - Web: http://www.elsteam.com
p.iva 01463940120 - c.f.05046150156 - trib.di busto a. 16415-c.c.i.a.a. varese 174164 - cap.soc.i.v. euro 10400,00
10 Submerged Pump 220Vac
The unit can operate with a pump feeding the humidifier. In the case of use of a submerged
220Vac pump, power supply of the pump must be carried out according to the following
schematic.
Bornier #1
13 12 11 10 9 8 7 6 5 4 3 2 1
220 Vac ~ Pompe
Bornier #1
13 12 11 10 9 8 7 6 5 4 3 2 1
220 Vac ~ Pompe
The installation of the pump with the tank must respect the outline of below figure. The
tank can be installed in a position higher than the humidifier. If the tank is installed in a
position lower than the humidifier the difference between solenoid valve and the bottom of
the tank should not exceed 60cm with the standard pump provided by Elsteam.
1
Humidifier
2
Solenoid valve (optional)
3
Flexible pip
e
4
Pump
5
Tank
This manual suits for next models
3
Table of contents
Other Elsteam Humidifier manuals

Elsteam
Elsteam VEH20 Series User manual

Elsteam
Elsteam KT User manual

Elsteam
Elsteam AHU-VEH User manual

Elsteam
Elsteam HPN Series Installation manual

Elsteam
Elsteam ZEPHYR EHKT003M2 User manual

Elsteam
Elsteam MISTRAL User manual

Elsteam
Elsteam KT Series User manual

Elsteam
Elsteam HPN Series Operating instructions

Elsteam
Elsteam VEH Series User manual

Elsteam
Elsteam REH4 Installation and operating instructions