Installation Instructions
QUBE SQU
1.0 General
1.1 It is important these Installation and Maintenance Instructions are fully adhered to.
1.2 Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta Fans Ltd or its agents for
clarification.
1.3 All electrical installation must be carried out by suitably qualified and competent personnel in accordance with all current statutory
requirements.
1.4 These instructions cover only the Elta Fans Ltd product and do not include the supply or installation of any safety equipment that may be
required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.
1.5 Any declarations made by Elta Fans Ltd about product installation and safety, are dependant on the fan equipment being used within
installations which themselves meet the requirements of the relevant Standards and Directives of your region.
1.6 The Qube fan range is designed for use in an ambient temperature of -20°C up to +50°C and up to 95% relative humidity. The fan is
not suitable for corrosive or explosive atmospheres.
1.7 The Qube-HT fan range is designed for use for in duct ambient temperature of -20°C up to +120°C. The fan is not suitable for corrosive
or explosive atmospheres.
1.8 The installer should provide easy access to the fan to facilitate future maintenance.
1.9 The installer should ensure the fan is adequately supported.
1.10 This product is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the product by a person
responsible for their safety. Children should be supervised to ensure that they do not play with the product.
1.11 At end-of-life, the unit must be disposed of in an environmentally friendly manner by suitably qualified and competent personnel in
accordance with the requirements of applicable Standards and Directives.
2.0 Installation
WARNING – The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed in
accordance with the local regulations.
2.1 Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate.
2.2 If there are any queries concerning the fan equipment, Elta Fans Ltd should be contacted prior to the installation.
2.3 The fan must be securely mounted and the panels adjusted to suit the desired position to suit the application, straight through or 90°
airflow. The fan can be mounted at any angle.
2.4 Check the details on the motor/fan rating plate to ensure that the correct power supply (voltage, frequency and phase) is available.
An incorrect power supply will lead to permanent damage to the motor.
2.5 Refer to the appropriate wiring diagram. Ensure that all earth connections are made.
2.6 Means for electrical disconnection must be incorporated in the wiring installation in accordance with the relevant wiring and electrical
regulations.
2.7 Precaution must be taken to locate the exhaust discharge terminal so as to avoid the backflow of gases into the room from the open flue
of gas or other fuel burning appliances.
3.0 Storage
3.1 The storage place must be vibration free, clean, dry and not subject to extreme temperature variations.
3.2 When storing for prolonged periods, whereby non rotation of motor occurs, we recommend electrical and bearing inspection, as they
may have incurred damage or require possible re-lubrication.
4.0 Start Up
4.1 Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram.
4.2 At initial start-up, check that impeller rotation and airflow direction is correct.
4.3 Check that the motor amperage draw does not exceed the nameplate rating.
5.0 Fan Maintenance
5.1 Inspection of the fan at least once every 12 months is recommended to ensure that the motor, fan blades, and supporting guards, are
clean. Any build up of dust and deposits on the blades or guards should be removed using a non-abrasive cleaner.
5.2 ll fastenings should be checked for tightness. In addition, all rotating items should be checked.
5.3 Bearings are of the ‘sealed for life’ type and will not need a detailed inspection.
5.4 The Qube-HT range has an easily removable motor/impeller assembly, and panel arrangement fixed to Multi-thread “U” nuts, ideal
for frequent cleaning.
AC