If the fan does not perform as stated above, note the error and consult your local Franklin Electric representative or call the Franklin
Electric Technical Service Hotline at 1-800-348-2420.
FAN TEST
1. The fan can be unplugged from the drive and tested with a 9 V
battery to show functionality.
- Connect the red (+) lead from the battery to the red fan
connector, and the black (-) lead from the battery to the black
fan connector.
- Connect the battery clip to the 9 V battery. The fan should spin
freely and quietly. This test should not be run for more than
5 seconds.
2. Test that the fan power supply works properly.
- Cycle power to the drive.
- Verify that the fan runs for 3–5 seconds during the
power-up initialization.
* The bracket kit comes preassembled.
SUBDRIVE50 CONNECT
FAN REPLACEMENT INSTALL GUIDE
s WARNING
!
Serious or fatal electrical shock may result from contact with the internal electrical components. DO NOT, under any
circumstances, ATTEMPT TO CHANGE THE FAN until the power has been removed from the drive, capacitors are discharged, and
five minutes have passed for internal voltages to discharge! Before replacing the fan, make sure the fan is not working properly
by performing the simple test below: