ELTA FANS SANO PIV Wall User manual

1
G
Please read this manual carefully before using the product and keep it in a safe place for reference.
This product was constructed up to standard and in compliance with regulations relating to electrical equipment and must be installed by technically
qualified personnel in accordance with all regulatory requirements. The manufacturer assumes no responsibility for damage to persons or property
resulting from failure to observe the instructions contained in this booklet.
• Outer fan casing manufactured from powder coated galvanised sheet steel providing a lightweight construction.
• An ultra-quiet EC motor/fan assembly for energy saving, mounted on ball bearings that guarantee a longer product life and is suitable for cold
climates.
• G2 lter tted as standard with large surface area to provide long lter life and efcient ltration of incoming air.
• All fans are individually tested before leaving the factory and are designed and manufactured to procedures dened in BS EN ISO 9001:2008.
• Power Supply 230V – 50/60Hz.
• The device should not be used for applications other than those specied in this manual.
• After removing the product from its packaging, verify its condition. In case of doubt, contact a qualied technician. Do not leave packaging within
the reach of small children or people with disabilities.
• Do not touch the appliance with wet or damp hands/feet.
• The device is not intended for use by persons (including children) with reduced physical, sensory or mental capacities or those with a lack of
experience and knowledge, unless they have been given supervision or instruction concerning use of the device from a person responsible for
their safety.
• Children should be supervised to ensure that they do not play with the device.
• WARNING: In order to avoid overheating, do not cover/close the air exit.
• Do not use the product in the presence of ammable vapours, such as alcohol, insecticides, gasoline, etc.
• If any abnormalities in operation are detected, disconnect the device from the mains supply and contact a qualied technician immediately. Use
original spare parts only for repairs.
• The electrical system to which the device is connected must comply with applicable regulations.
• Before connecting the product to the power supply or the power outlet, ensure that:
- The data plate (voltage and frequency) correspond to those of the electrical mains.
- The electrical power supply/socket is adequate for maximum device power. If not, contact a qualied technician.
• Operating temperature: 0°C up to +40°C.
• Do not leave the device exposed to atmospheric agents (rain, sun, snow, etc.).
Installation manual
SANO PIV WALL Positive input ventilation unit
G
TECHNICAL SPECIFICATIONS
Power
W max
Sound pressure
dB(A) @3m
28 27
Unit setting
Inlet grille
(5m duct 2x bends) Outlet grille
Flow Rate Watts Flow Rate Watts
113 3.7 14 4.5
2 17 4.8 17 5.2
3 21 6.4 21 6.9
4 25 9.2 25 9.3
5 29 11.1 29 12.7
6 33 16.8 34 16.8
PRECAUTIONS FOR INSTALLATION, USE AND MAINTENANCE
Fig. 1
Introduction
The Elta SANO PIV WALL is a positive input ventilation unit suitable for installation on a wall for
dwellings without a loft space. It continuously supplies fresh air through a discharge diffuser, that
should be situated in the central hallway or landing. The unit has multiple options for the inlet spigot;
on both sides and the back of the unit allowing multiple installation options. The unit can also be
configured to discharge air from the left or right hand side.
The power consumption shown is Normal mode.

2
• Do not immerse the device or its parts in water or other liquids.
• Turn off the main switch whenever a malfunction is detected or in case of cleaning/maintenance.
• For installation an omnipolar switch should be incorporated in the xed wiring, in accordance with the wiring regulations, to provide a full
disconnection under overvoltage category III conditions (contact opening distance equal to or greater than 3mm).
• Do not obstruct the fan or exhaust grille to ensure optimum air passage.
• Ensure adequate air supply into the room in compliance with existing regulations in order to ensure proper device operation
• If the environment in which the product is installed also houses a fuel-operating device (water heater, methane stove etc., that is not a “sealed
chamber” type), it is essential to ensure adequate air intake, to ensure good combustion and proper equipment operation.
• Install the product so that the impeller is not accessible from the air outlet side as veried by contact with the Test Finger (test probe “B” of the
norm EN61032) in compliance with the current safety regulations.
Unit Setting
The SANO PIV WALL unit runs continuously a low ventilation level supplying fresh clean air into your home. This fresh air dilutes the stale and humid
air in your home and is a great way to prevent and even cure condensation dampness and mould problems.
The unit setting is selected by the installer to suit the size, layout, thermal properties and moisture production in the home. Getting this setting right
is very important and is often based on the experience of the installer. It is as important not to over ventilate as it is to under ventilate a home. Elta
Fans Residential team has much experience in setting PIV units and can be contacted anytime for advice.
The unit has numerous automatic speed adjustments to optimise ventilation and energy use.
Normal Mode
The unit will run in this mode for the vast majority of its time supplying until the unit’s integral temperature sensor switches it to “Standby” mode,
or the “Override Boost” mode (if connected via a suitable switch) is activated by the occupants.
This rate is set via 3 RATE dip switches shown in the wiring diagram, when leaving the factory this is set to 21l/s.
Energy Saving Mode
When the temperature of air being brought into the home is above an adjustable temperature the unit will automatically switch to a lower speed.
This lower speed will reduce the energy used by the ventilation unit and the amount of uncomfortably warm air being brought in. This temperature
can be selected for conditions where condensation is less likely to occur such as the summer months.
This trigger temperature is adjustable between 15-25°C, via V1 trimmer (shown in the wiring diagram). The default when leaving the factory is
19°C. It is usually adjusted to 1°C above the temperature the home is heated to
The fan speed is adjustable between via the HY trimmerand can be set to between -50% and 50% of the trickle speed.
FOR EXAMPLE: The trickle is set at 21l/s, HY trimmer set to -20%: when triggered the boost will be 21+(-4.2)=16.8l/s.
It is recommended that the Heat Recovery Mode (boost above 0%) is not used for the WALL mounted PIV and the boost increase is set at or below
0% (default).
Summer Standby Mode
The summer shutdown function limits the chance of the house overheating when temperatures outside reach a level that is uncomfortable. The unit
will essentially switch off when the temperature reaches a “Standby” trigger temperature to save energy and prevent undesirable warm air being
introduced unnecessarily in to the home.
Some customers wish to have their unit operating all year round e.g. for Radon Gas control or pollen ltration during summer. That’s why an
adjustable trigger temperature has been incorporated.
This temperature set point is adjustable via V2 trimmer (shown in the wiring diagram) between 20° and 40°C, the default when leaving the factory
is 26°C.
Override Boost Mode
The unit’s automatic controls can be overridden to operate the unit at its maximum airow by means of a user switch.
The override boost can be triggered via a dedicated external volt free switch connecting GND and S3 terminals (shown in diagram). Purge operation
overrides any other speed settings.
This function can be incorporated at installation stage or later. The unit will function automatically with or without it.
To prevent excessively warm air being supplied to the home and to protect the components of the unit, the purge will not operate above 40°C.
OPERATION

3
MAINTENANCE
Make sure the mains supply of the unit is disconnected before performing any maintenance. The maintenance must be carried out by a qualied
technician and in accordance with local rules and regulations.
Filters of the unit require changing according to the lter change period. When the lters are dirty less air will be supplied by the unit and impact the
effectiveness of the unit. In areas of high pollution e.g. beside main roads more regular replacement may be required. Filters can be supplied by Elta Fans.
Filters should be checked annually or if a drop in ventilation rates are noticed.
The lter should be checked regularly to determine if it needs cleaning or replacement. External environmental conditions will determine how often
the lter will need to be cleaned or replaced. Reduced airow, perhaps accompanied by an increase in noise level, may provide indication that the
lter needs to be cleaned or replaced. The lter should be inspected and cleaned or replaced as required at intervals not exceeding 2 years
and always replaced at intervals not exceeding 5 years.
4
STANDARD CONFORMITY
2014/35/EU Low Voltage Directive (LVD)
2014/30/EU Electromagnetic Compatibility (EMC),
in conformity with the following standards:
Electrical Safety
EN60335-1(2008); EN 60335-2-80(2005); EN 60335-2-80/A2(2009)
Electromagnetic Compatibility
EN 55014-1(2006)+A1+A2; EN 55014-2(1997)+A1(2001)+A2(2008)+IS1(2007)
EN 61000-3-2(2006)+A1(2009)+A2(2009); EN 61000-3-3(2008).
5
23

4
DIMENSIONS (mm)
Duct work should be kept as simple as possible minimising duct length and the number of bends. This will optimise the Units effectiveness.
Ducting from the external to the unit should be kept as short as possible as condensation can form on the cold ductwork if it is not insulated.
The unit comes tted with round 100mm spigots for easy tment of round rigid ducting. If rectangular 110x54 ducting is required a rectangular to
round adaptor can be tted directly to the spigot. To do this the spigot must be cut to 25mm length.
Enough room needs to be allowed to access the side screws for maintenance. Allen Keys are supplied with every unit to minimise the space
requirement.
The blades of internal grilles tted in the central hallway should be pointing upwards to better spread the fresh air.
The unit should be connected to a smoke alarm to stop the unit in the event of a re to stop the spread of smoke and prevent evacuation. Guidance
should be sort from Approved Document B (Fire Safety).
When the ducting is passed through re boundaries adequate re protection should be incorporated. Guidance should be sort from Approved
Document B (Fire Safety).
INSTALLATION
WHAT IS IN THE BOX
1. Ventilation unit
2. Filter
3. O&M Manual
4. 4x Screw + wall plug
5. 4x Wood screw
6. Installer label
7. 1x Extra end panel (inlet bottom left or outlet top right)
8. 1x Extra end panel (inlet bottom right or outlet top left)
9. 1x Blank panel (if back inlet used)
Weight: 6.1 kg
aera aqi lu
Peso/Weight: Scala/Scale:Codice/Code:No. Dis/No. Drawing:
ARCHIVIO CAD:
----
Firma/Sign.Data/DateDescrizione/DescriptionRev.
-
Firma/Signature:Data/Date:Materiale/Material:
Descrizione/Description:
AERAULIQA SRL
Sede legale / Registered office: via Corsica 10, 25125 Brescia
Sede operativa / Warehouse-offices:
via M.Calderara 39/41, 25018 Montichiari(BS)
Tel: +39 030 674681 Fax: +39 030 6872149
C.F. e P.IVA 03369930981 - REA BS-528635
www.aerauliqa.it
Questo documento è protetto dalle leggi vigenti in materia di privacy e copyright. Nè è vietata la copia, la diffusione senza
autorizzazione di Aerauliqa srl
This document is protected by privacy and copyright laws. No part of this document may be reproduced, adapted, trasmitted or
disclosed without the specific written consent of Aerauliqa srl. All right are reserved.
1:5
T:\Archivio Progetti Industriale\In-
Line_Box\PIV\PIV-Wall\Definitivo\Rev-
02\Rev-03\
605
515
354
277 77
100
210
aera aqi lu
Peso/Weight: Scala/Scale:Codice/Code:No. Dis/No. Drawing:
ARCHIVIO CAD:
----
Firma/Sign.Data/DateDescrizione/DescriptionRev.
-
Firma/Signature:Data/Date:Materiale/Material:
Descrizione/Description:
AERAULIQA SRL
Sede legale / Registered office: via Corsica 10, 25125 Brescia
Sede operativa / Warehouse-offices:
via M.Calderara 39/41, 25018 Montichiari(BS)
Tel: +39 030 674681 Fax: +39 030 6872149
C.F. e P.IVA 03369930981 - REA BS-528635
www.aerauliqa.it
Questo documento è protetto dalle leggi vigenti in materia di privacy e copyright. Nè è vietata la copia, la diffusione senza
autorizzazione di Aerauliqa srl
This document is protected by privacy and copyright laws. No part of this document may be reproduced, adapted, trasmitted or
disclosed without the specific written consent of Aerauliqa srl. All right are reserved.
1:5
T:\Archivio Progetti Industriale\In-
Line_Box\PIV\PIV-Wall\Definitivo\Rev-
02\Rev-03\
605
515
354
277 77
100
210
aera aqi lu
Peso/Weight: Scala/Scale:Codice/Code:No. Dis/No. Drawing:
ARCHIVIO CAD:
----
Firma/Sign.Data/DateDescrizione/DescriptionRev.
-
Firma/Signature:Data/Date:Materiale/Material:
Descrizione/Description:
AERAULIQA SRL
Sede legale / Registered office: via Corsica 10, 25125 Brescia
Sede operativa / Warehouse-offices:
via M.Calderara 39/41, 25018 Montichiari(BS)
Tel: +39 030 674681 Fax: +39 030 6872149
C.F. e P.IVA 03369930981 - REA BS-528635
www.aerauliqa.it
Questo documento è protetto dalle leggi vigenti in materia di privacy e copyright. Nè è vietata la copia, la diffusione senza
autorizzazione di Aerauliqa srl
This document is protected by privacy and copyright laws. No part of this document may be reproduced, adapted, trasmitted or
disclosed without the specific written consent of Aerauliqa srl. All right are reserved.
1:5
T:\Archivio Progetti Industriale\In-
Line_Box\PIV\PIV-Wall\Definitivo\Rev-
02\Rev-03\
605
515
354
277 77
100
210

5
IPIV UNIT
6
7
8
Inlet options from right hand side.
Inlet options from left hand side. Outlet louvre accessory shown right hand side.
Outlet louvre accessory ordered separately: 410-PIV-GE-R (Right hand side), 410-PIV-GE-L (Left hand side).
Supply air into hallway.

6
WALL MOUNTING
Before mounting ensure the desired location leaves enough room for access and maintenance. There are multiple mounting congurations make
sure you have decided on the most suitable before drilling any holes.
The back panel can be removed and offered up to the wall ensuring that is level. The mounting hole positions can now be marked and rear duct
entry if required.
Drill the marked holes and insert the supplied wall plugs.
Double check the holes line up with the rear panel and reassemble the unit in the desired conguration.
Lift the unit up and align the mounting holes with the wall plugs.
The supplied screws can then be screwed in securing the unit to the wall.
9
13
12
10 11
pencil
Rear inlet option.

7
17
18 19
14 15
16
WARNING: Air outlet only on top.

8
20 Control box
ELECTRICAL WIRING
The unit must be earthed
Trimmer label Operation Range Default
V1 Heat recovery trigger temperature 15 to 25°C 19°C
V2 Summer standby trigger temperature 20 to 40°C 25°C
HY % change of Heat Recovery mode -50% of trickle to 50% of trickle 0
To adjust the trickle ow rate use the dip switches shown in the diagram of gure 20.
NORMAL MODE SPEED SETTING
DIP1 DIP2 DIP3 DIP4
000x
001 x
010x
01 1 x
10 0 x
101 x
110x
PLEASE NOTE: Do not change the setting of DIP4 switch.
1 2 3 4
1
0
RATE
DIP SWITCHES
0
50
100
150
200
250
0 5 10 15 20 25 30 35 40 45 50 55 60
Pa
l/s
iPIV WALL
Dip 000
Dip 001
Dip 010
Dip 011
Dip 100
Dip 101
Dip 110 (PURGE)
SANO PIV WALL

9
TRIMMER SETTING
15°C
16,5°C
18,5°C 20°C 21,5°C
23,5°C
25°C
V1
20°C
23°C
27°C 30°C 33°C
37°C
40°C
V2
0
-50% TRICKLE +50% TRICKLE
HY
-40% +40%
-20% +20%

10
a) Mark -ELTA FANS
b) Model -SANO PIV WALL
c) SEC class -B
c1) SEC warm climates kWh/m2.a -10,6
c2) SEC average climates kWh/m2.a -26,1
c3) SEC cold climates kWh/m2.a -53,1
Energy label -No
d) Unit typology -Residenal - unidireconal
e) Type of drive -Mul-speed drive
f) Type of Heat Recovery System -Absent
g) Thermal eciency of heat recovery %N/A
h) Maximum ow rate m3/h 120
i) Electric power input at maximum ow rate W635
j) Sound power level (LWA)dBA 43
k) Reference ow rate m3/h 84
l) Reference pressure dierence Pa 50
m) Specic power input (SPI) W/m3/h 0,119
n1) Control factor -0,65
n2) Control typology -Local demand control
o1) Maximum internal leakage rate %N/A
o2) Maximum external leakage rate %2
p1) Internal mixing rate %N/A
p2) External mixing rate %N/A
q) Visual lter warning -N/A
r) Instrucons to install regulated grilles -check the instrucon booklet
s) Internet address for preassembly/disassembly instrucons -www.eltafans.com
t) Airow sensivity to pressure variaons %N/A
u) Indoor/outdoor air ghtness m3/h N/A
v1) AEC - Annual electricity consumpon - warm climates kWh 0,9
v2) AEC - Annual electricity consumpon - average climates kWh 0,9
v3) AEC - Annual electricity consumpon - cold climates kWh 0,9
w1) AHS - Annual heang saved - warm climates kWh 12,8
w2) AHS - Annual heang saved - average climates kWh 28,3
w3) AHS - Annual heang saved - cold climates kWh 55,4
ErP Directive - Regulations 1253/2014 - 1254/2014

11
GUARANTEE
The product is offered with a ve year warranty.
First year of warranty covers parts and labour, following this period the warranty covers replacement parts only based on maintenance
having being carried out in accordance with our literature and terms and conditions of sale.
Proof of Purchase, Periodic inspection and maintenance will be required in the event of any warranty claim.

Elta Fans Limited
Building Services
46 Third Avenue
Pensnett Trading Estate
Kingswinford
West Midlands
DY6 7US
United Kingdom
T: +44 (0) 1384 275800
F: +44 (0) 1384 275810
003755 - 00 - 1117
Table of contents